Electrical Connection of F2040
F2040 Communication board (AA23)
➢
The mains cable is pre-wired in the unit and must be terminated in a local rotary isolator. (not a cooker switch)
➢
The rotary isolator must be supplied by 6 or 10 Square cable back to the Fuse board. (dependent on distance and
sized by the electrician)
➢
The circuit breaker must be 25 Amp
“motor”
rated.
➢
The communication (comms) cable must be screened cat5 or equivalent. It must also be separated from power supply
runs and the foil screen grounded on one end only.