Technical specifications
VPA 300/200
Type
16
bar
Maximum water supply pressure
5.5
bar
Operating pressure, tap water
3.5
bar
Expansion vessel, tap water, charge pressure
3.5
bar
Pressure reduction valve, setting
6
bar
Max design pressure
285
litres
Volume, water heater
200
litres
Volume primary double jacket
25
litres
Volume expansion vessel
660
kg
Mass, unit, filled with water
2.5
bar
Maximum primary working pressure (primary side)
7
bar
Max operating pressure of T&P-valve
6
bar
Set opening pressure expansion valve
1h 55min
...h ...min
Heating up time from 15°C to 60 °C, 14 kW power*
377
litres
Volume of water drawn off, above 40 °C**
10.4
kW
Heat transfer (60/50 °C at 60 °C hot water temperature)*
13.2
kWh
Heat content at 50 °C
90
°C
Max temperature, heating fluid
90
°C
Max operating temperature T&P-valve
25
kW
Maximum power supply
25
kW
Discharge capacity of T&P-valve
082 024
Part No
Copper
Corrosion protection
* Primary flow to achieve the maximum capacity VPA 300/200: 2300 l/h.
** At incoming temperatures 10 °C and hot water draining of 30 l/min.
Tested according to standard EN 12897:2006
Energy labelling
NIBE
Supplier
VPA 300/200 UK
Model
C
Energy efficiency class
111
W
Heat loss
487
l
Volume
Accessories
Immersion heater
Immersion heater IU 31 - IU34
See table (page 11)
Connection box K11
Connection box with thermostat and overheating protec-
tion. (When connecting Immersion heater )
Part no. 018 893
19
Chapter 4 |
Technical data
VPA 300/200