Technical
specifications
1X230 V, 3X230 V, 3X400 V
S1255-16
S1255-12
S1255-6
Model
Output data according to EN 14511
4 – 16
3 – 12
1.5 – 6
kW
Heating capacity (P
H
)
0/35 nominal
8.89
5.06
3.15
kW
Heating capacity (P
H
)
1.83
1.04
0.67
kW
Supplied power (P
E
)
4.85
4.87
4.72
COP
0/45 nominal
8.63
4.78
2.87
kW
Heating capacity (P
H
)
2.29
1.27
0.79
kW
Supplied power (P
E
)
3.77
3.75
3.61
COP
10/35 nominal
11.22
6.33
4.30
kW
Heating capacity (P
H
)
1.84
1.03
0.66
kW
Supplied power (P
E
)
6.11
6.12
6.49
COP
10/45 nominal
10.92
5.98
3.98
kW
Heating capacity (P
H
)
2.32
1.30
0.83
kW
Supplied power (P
E
)
4.72
4.59
4.79
COP
SCOP according to EN 14825
16
12
6
kW
Rated heating output (P
designh
)
5.5 / 4.2
5.4 / 4.3
5.5 / 4.1
SCOP cold climate, 35 °C / 55 °C
5.2 / 4.1
5.2 / 4.1
5.2 / 4.0
SCOP average climate, 35 °C / 55 °C
Energy rating, average climate
A+++ / A+++
A+++ / A+++
A+++ / A+++
The product's room heating efficiency class 35 °C / 55 °C
1
A+++ / A+++
A+++ / A+++
A+++ / A+++
The system's room heating efficiency class 35 °C / 55 °C
2
A / XL
A / XL
A / XL
Efficiency class hot water heating / declared tap profile
3
Noise
36 – 47
36 – 47
36 – 43
dB(A)
Sound power level (L
WA
)
EN 12102
at 0/35
21 – 32
21 – 32
21 – 28
dB(A)
Sound pressure level (L
PA
)
calculated values according to EN ISO
11203 at 0/35 and 1 m range
Electrical data
2 – 180
2 – 180
3 – 140
W
Output, Brine pump
3 – 140
2 – 60
2 – 60
W
Output, Heating medium pump
IPx1B
Enclosure class
Equipment Compliant with IEC 61000-3-12
For Connection Design Purposes, Compliant with IEC 61000-3-3 technical requirements
WLAN
11
dbm
2.412 - 2.484 GHz max power
Wireless units
4
dbm
2.405 - 2.480 GHz max power
Refrigerant circuit
R407C
Type of refrigerant
1,774
GWP refrigerant
2.2
2.0
1.16
kg
Fill amount
3.90
3.55
2.06
ton
CO
2
equivalent
3.2 (32 bar) / 0.15 (1.5 bar)
MPa
Cut-out value pressure switch HP / LP
Brine circuit
0.05 (0.5 bar) / 0.45 (4.5 bar)
MPa
Min/max system pressure brine
0.51
0.29
0.18
l/s
Nominal flow
95
115
64
kPa
Max external avail. press at nom flow
see diagram
°C
Min/Max incoming Brine temp
-12
°C
Min. outgoing brine temp.
Heating medium circuit
0.05 (0.5 bar) / 0.45 (4.5 bar)
MPa
Min/Max system pressure heating medium
0.22
0.12
0.08
l/s
Nominal flow
71
73
69
kPa
Max external avail. press at nom flow
NIBE S1255