Installation

Settings

Modbus Master

RTU

Method

9600 baud

Speed

8 bits

Word length

None

Parity

1

Stop bits

Fixed 0x01 up to and including
Modbus 40 v.7.

Selectable 1 - 247 from and including
Modbus 40 v.10.

Address

Caution

Software version Modbus 40 v.10 is required to
be able to manage selectable addresses. To
check software version, enter menu 3.1 “Service
info” in your climate unit.

The climate unit’s software must be software
version 5539 (4150R7 for NIBE F1345) or later
for it to work with Modbus 40 v.10. If it is not,
perform a software update. Visit
www.nibeuplink.com to download your update
file.

Climate unit

1. Start the climate unit and select MODBUS 40 in menu

5.2 “System settings” (menu 5.2.4 for NIBE F1345,
F1355, SMO 40, VVM 225, VVM 310, VVM 320,
VVM 325 and VVM 500).

2. Enter the address of MODBUS 40 in menu 5.3.11.

(This menu is only visible if MODBUS 40 has software
version Modbus 40 v.10 or later)

Communication

TIP

ModbusManager

can be downloaded via

www.nibe.eu/modbus.

Updating Modbus database

For ModbusManager there is a database, which contains
all the parameters that can be logged/set for the differ-
ent products. To ensure that you have access to all select-
able parameters and products you should update the
ModbusManager database. This is done in Modbus Up-
dater that is part of ModbusManager. Modbus Updater
is located in the same installation location as Modbus-
Manager. When you have opened Modbus Updater,
press "Update database" to start the database update.

Read the values

There are two ways of reading the values from the cli-
mate unit, automatically or manually.

Automatic reading: can retrieve up to 20 predefined
parameters at the same time.

Manual reading: takes longer and only one value at a
time can be retrieved.

Automatic reading

For smaller installations where 20 or fewer parameters
must be retrieved, it is appropriate to connect with a
LOG.SET file. In such cases, all parameters are updated
twice a second.

In larger installations with multiple parameters, it is ap-
propriate to use a LOG.SET file for the 20 most important
parameters, which requires the timeout time to be adjus-
ted to 2,1 seconds. The parameters found in the LOG.SET
file are retrieved twice a second, whereas the other
parameters are retrieved at 2,1 seconds per parameter.

TIP

Place the most important parameters in the
LOG.SET file, alarms and certain temperatures
for example. Outdoor temperature, heating
curves and other values that are changed less
often do not need to be placed in the LOG.SET
file.

Visit www.nibe.eu/modbus to read more about
LOG.SET.

1. Create a LOG.SET file that contains the predefined

values that are to be read out. The file is created in
ModbusManager. See section "Create a log settings
file in ModbusManager" 
for instructions.

2. Save LOG.SET to a USB-memory.
3. Insert the USB-memory device into the climate unit's

display unit.

4. Enter menu USB.
5. Enter menu "logging".
6. Tick “activated".
7. Wait fifteen seconds and then remove the

USB-memory device.

Retrieve the values for the Modbus-master by using the
"Read holding registers" command with the desired
parameter addresses. Use ModbusManager, see LOG.SET
in a text editor or see the examples list on page 14 to
see which parameter address a value has.

See section The Modbus command on page 14 for fur-
ther information about different commands.

Create a log settings file in ModbusManager

First install the software ModbusManager on your com-
puter. The software can be downloaded from
www.nibe.eu/modbus.

MODBUS 40 | GB

12

Содержание MODBUS 40

Страница 1: ...E K MODBUS 40 SE Installatörshandbok Kommunikationsmodul GB Installer manual Communications module DE Installateurhandbuch Kommunikationsmodul FI Asentajan käsikirja Tiedonsiirtomoduuli IHB 1712 9 031725 ...

Страница 2: ......

Страница 3: ...com och installera denna TIPS För att administrera Modbus via Microsoft Windows ladda ner och installera ModbusMa nager från www nibe se kommunikation Kompatibla produkter Tillbehöret passar till följande produkter från NIBE F750 F1145 F1155 SMO 40 VVM 225 F1255 F1245 VVM 310 VVM 320 F1345 F1355 VVM 325 VVM 500 F370 F470 F730 Innehåll Apparatlåda 1 st Väggfäste 1 st Komponentplacering MODBUS 40 L ...

Страница 4: ...gskortet AA3 i värmepumpen 12 11 10 9 8 7 12V A B GND Värmepump AA3 X4 AA9 X1 MODBUS 40 AA3 X4 F1345 utan 2 0 Plint X1 på SMS kortet AA9 i MODBUS 40 ansluts till plint X6 4 7 i värmepumpen B GND 12V A 4 5 6 7 X6 MODBUS 40 Värmepump AA9 X1 AA3 X6 F1345 med 2 0 F1355 Plint X1 på SMS kortet AA9 i MODBUS 40 ansluts till plint AA101 X10 7 10 i värmepumpen B GND 12V A 6 7 8 9 10 11 AA101 X10 MODBUS 40 V...

Страница 5: ...40 eller RMU 40 Ifall MODBUS 40 ska anslutas tillsammans med SMS 40 RMU 40 måste MODBUS 40 vara första enheten inkopplad till klimatanläggningens anslutningsplint Inkoppling till och från MODBUS 40 sker i plint AA9 X1 Det går inte att koppla in fler än två enheter till klimatan läggningen Ingångskort huvudprodukt MODBUS 40 SMS 40 RMU 40 SMS 40 Tillbehör_singular translation hint 2 value SMS 40 SMS...

Страница 6: ... eller manuellt Automatisk avläsning kan hämta upp till 20 fördefini erade parametrar samtidigt Manuell avläsning tar längre tid och endast ett värde i taget kan hämtas Automatisk avläsning Mindre anläggningar där 20 eller färre parametrar ska hämtas är lämpliga att koppla upp med en LOG SET fil I dessa fall uppdateras samtliga parametrar två gånger i sekunden I större anläggningar med fler parame...

Страница 7: ...metrar i ett doku ment som kan öppnas i valfritt kalkylprogram TÄNK PÅ Filnamnet måste vara LOG SET för att klimatan läggningen ska läsa filen Besök www nibe se kommunikation för att läsa mer om LOG SET filer Manuell avläsning TÄNK PÅ Manuell avläsning är tidskrävande och endast ett värde i taget kan läsas max timeout 2 1 s Parametern behöver dock inte finnas med i LOG SET filen Hämta ett värde ti...

Страница 8: ...VVM 310 VVM 320 VVM 325 och VVM 500 Felaktigt anslutna kablar mellan MODBUS 40 och vär mepump inomhusmodul Detta ger kommunikations larm i värmepumpens inomhusmodulens display Felaktig mjukvara i värmepumpen Mjukvaruversionen i värmepumpen ska vara högre än 3000 Se avsnitt Allmänt på sida 3 Modbus 40 felaktigt ansluten mot Modbus master Kontrollera att A är ansluten mot och B mot OBS Hitta mer inf...

Страница 9: ... nibeuplink com and install it TIP To administer Modbus via Microsoft Windows download and install ModbusManager from www nibe eu modbus Compatible products The accessory is suitable to following products from NIBE F750 F1145 F1155 SMO 40 VVM 225 F1255 F1245 VVM 310 VVM 320 F1345 F1355 VVM 325 VVM 500 F370 F470 F730 Contents Unit box 1 x Wall bracket 1 x Component locationMODBUS 40 L E K AA9 X2 AA...

Страница 10: ... connected to terminal block X4 9 12 on the input board AA3 in the heat pump 12 11 10 9 8 7 12V A B GND Heat pump AA3 X4 AA9 X1 MODBUS 40 AA3 X4 F1345 without 2 0 Terminal block X1 on the SMS card AA9 in MODBUS 40 is connected to terminal block X6 4 7 in the heat pump B GND 12V A 4 5 6 7 X6 MODBUS 40 Heat pump AA9 X1 AA3 X6 F1345 with 2 0 F1355 Terminal block X1 on the SMS card AA9 in MODBUS 40 is...

Страница 11: ... LEK AA3 X4 MODBUS 40 together with SMS 40 or RMU 40 If MODBUS 40 is to be connected with SMS 40 RMU 40 MODBUS 40 must be the first unit connected to the cli mate unit s terminal block Connecting to and disconnecting from MODBUS 40 oc curs in terminal AA9 X1 No more than two units can be connected to the climate unit Input board main product MODBUS 40 SMS 40 RMU 40 SMS 40 Tillbehör_singular transl...

Страница 12: ...eters at the same time Manual reading takes longer and only one value at a time can be retrieved Automatic reading For smaller installations where 20 or fewer parameters must be retrieved it is appropriate to connect with a LOG SET file In such cases all parameters are updated twice a second In larger installations with multiple parameters it is ap propriate to use a LOG SET file for the 20 most i...

Страница 13: ...ters in a docu ment that can be opened in any calculation program Caution The file name must be LOG SET for the climate unit to read the file Visit www nibe eu modbus to read more about LOG SET files Manual reading Caution Manual readout is time consuming and only one value at a time can be read max timeout 2 1 s The parameter does not have to be included in the LOG SET file Retrieve a value for t...

Страница 14: ...O 40 VVM 225 VVM 310 VVM 320 VVM 325 and VVM 500 Incorrectly connected cables between MODBUS 40 and heat pump indoor module Gives a communica tion alarm in the heat pump s indoor module s display Incorrect software in the heat pump The software version in the heat pump must be higher than 3000 See section General on page 9 Modbus 40 incorrectly connected to Modbus master Check that A is connected ...

Страница 15: ... und installieren Sie sie TIP UmModbusüberMicrosoftWindowszuverwal ten laden Sie ModbusManager von www nibe eu modbus herunter und installieren Sie die Software Kompatible Produkte Das Zubehör passt für folgende Produkte von NIBE F750 F1145 F1155 SMO 40 VVM 225 F1255 F1245 VVM 310 VVM 320 F1345 F1355 VVM 325 VVM 500 F370 F470 F730 Inhalt Gerätegehäuse 1 St Wandhalterung 1 St Position der Komponent...

Страница 16: ... F1255 Anschlussklemme X1 an der SMS Platine AA9 in MODBUS 40 wird mit Anschlussklemme X4 9 12 an der Eingangsplatine AA3 in der Wärmepumpe verbunden 12 11 10 9 8 7 12V A B GND Wärmepumpe AA3 X4 AA9 X1 MODBUS 40 AA3 X4 F1345 ohne 2 0 Klemme X1 an der SMS Platine AA9 in MODBUS 40 wird mit Klemme X6 4 7 in der Wärmepumpe verbun den B GND 12V A 4 5 6 7 X6 MODBUS 40 Wärmepumpe AA9 X1 AA3 X6 F1345 mit ...

Страница 17: ...en mit SMS 40 oder RMU 40 Wenn MODBUS 40 gemeinsam mit SMS 40 RMU 40 angeschlossen werden soll muss MODBUS 40 als erste Einheit mit der Anschlussklemme des Klimatisierungssys tems verbunden werden Der Anschluss für und von MODBUS 40 erfolgt an An schlussklemme AA9 X1 Es können maximal zwei Einheiten mit dem Klimatisie rungssystem verbunden werden Eingangsplatine Hauptprodukt MODBUS 40 SMS 40 RMU 4...

Страница 18: ...em auszulesen automatisch oder manuell Automatische Auslesung Es können gleichzeitig bis zu 20 vordefinierte Parameter abgerufen werden Manuelle Auslesung Dieser Vorgang dauert länger und es kann nur jeweils ein Wert abgerufen werden Automatische Auslesung Für kleinere Anlagen von denen 20 oder weniger Para meter abgerufen werden sollen empfiehlt sich eine Verbindung per LOG SET Datei In diesen Fä...

Страница 19: ... Datei auf dem Computer oder di rekt auf einem USB Stick Wählen Sie Export to file in Menü File wenn Sie alle Wärmepumpenparameter in einem Dokument speichern wollen das sich in einem beliebigen Tabel lenkalkulationsprogramm öffnen lässt ACHTUNG Der Dateiname muss LOG SET lauten damit das Klimatisierungssystem die Datei lesen kann Unter www nibe eu modbus erfahren Sie mehr über LOG SET Dateien Man...

Страница 20: ...25 und VVM 500 Falsch verbundene Kabel zwischen MODBUS 40 und Wärmepumpe Inneneinheit Dadurch wird auf dem Display von Wärmepumpe Inneneinheit ein Kommu nikationsalarm ausgegeben Falsche Software in der Wärmepumpe Die Software version in der Wärmepumpe muss neuer als 3000 sein Siehe Abschnitt Allgemeines auf Seite 15 Modbus 40 falsch angeschlossen an Modbus Master Kontrollieren Sie ob A mit und B ...

Страница 21: ...llinnoidaksesi Modbus a Microsoft Win dows lla lataa ja asenna ModbusManager osoitteesta www nibe eu modbus Yhteensopivat tuotteet Lisävaruste sopii seuraaviin NIBE tuotteisiin F750 F1145 F1155 SMO 40 VVM 225 F1255 F1245 VVM 310 VVM 320 F1345 F1355 VVM 325 VVM 500 F370 F470 F730 Sisältö Kojerasia 1 kpl Seinäteline 1 kpl Komponenttien sijainti MODBUS 40 L E K AA9 X2 AA9 X1 AA9 Sähkökomponentit Lisä...

Страница 22: ...ämpöpumpussa 12 11 10 9 8 7 12V A B GND Lämpöpumppu AA3 X4 AA9 X1 MODBUS 40 AA3 X4 F1345 ilman 2 0 Liitin X1 MODBUS 40 n SMS kortissa AA9 kytketään lämpöpumpun liittimeen X6 4 7 B GND 12V A 4 5 6 7 X6 MODBUS 40 Lämpöpumppu AA9 X1 AA3 X6 F1345 ja 2 0 F1355 Liitin X1 MODBUS 40 n SMS kortissa AA9 kytketään lämpöpumpun liittimeen AA101 X10 7 10 B GND 12V A 6 7 8 9 10 11 AA101 X10 MODBUS 40 Lämpöpumppu...

Страница 23: ...K AA3 X4 MODBUS 40 ja SMS 40 tai RMU 40 Jos MODBUS 40 ja SMS 40 RMU 40 yhdistetään MOD BUS 40 n täytyy olla ensimmäinen lämmitysjärjestelmän liitinrimaan kytketty yksikkö MODBUS 40 n kytkennät tehdään liittimeen AA9 X1 Lämmitysjärjestelmään voi liittää enintään kaksi yksikköä Tulokortti päätuote MODBUS 40 SMS 40 RMU 40 SMS 40 Tillbehör_singular translation hint 2 value SMS 40 SMS 40 B A 12V GND B ...

Страница 24: ...mästä kahdella tavalla automaattisesti tai käsin Automaattinen luku voi noutaa samanaikaisesti jopa 20 esimääritettyä parametria Manuaalinen luku vie kauemmin ja kerralla voidaan noutaa vain yksi arvo Automaattinen luku Pienemmät järjestelmät joissa noudettavia parametreja on20taivähemmän kannattaayhdistääLOG SET tiedos tolla Näissä tapauksissa kaikki parametrit päivitetään kaksi kertaa sekunnissa...

Страница 25: ...aikki parametrit asiakirjaan jonka voi avata halutussa taulukkolaskentaohjelmas sa MUISTA Tiedoston nimen pitää olla LOG SET jotta läm mitysjärjestelmä lukee tiedoston Lisätietoa LOG SET tiedostosta on osoitteessa www nibe eu modbus Manuaalinen luku MUISTA Manuaalinen luku on aikaa vievää ja vain yksi arvo voidaan lukea kerralla maks aikakatkaisu 2 1 s Parametria ei kuitenkaan tarvitse olla LOG SE...

Страница 26: ... VVM 225 VVM 310 VVM 320 VVM 325 ssa ja VVM 500 MODBUS 40 n ja lämpöpumpun sisäyksikön väliset kaapelit kytketty väärin Tuo tiedonsiirtohälytyksen lämpöpumpun sisäyksikön näyttöön Virheellinen ohjelmisto lämpöpumpussa Lämpöpum pun ohjelmistoversion pitää olla uudempi kuin 3000 Katso luku Yleistä sivulla 21 Modbus 40 kytketty virheellisesti Modbus isäntään Tarkasta että A on kytketty plussaan ja B ...

Страница 27: ...Wiring diagram 0 000 MJN 2017 02 03 Production GBN 2012 05 15 WIRING DIAGRAM SMS40 MODBUS40 ELSCHEMA SMS40 MODBUS40 450119 4 27 MODBUS 40 ...

Страница 28: ......

Страница 29: ......

Страница 30: ......

Страница 31: ......

Страница 32: ...WS name Gemensamt WS version a366 working edition Publish date 2017 04 27 15 50 NIBE AB Sweden Hannabadsvägen 5 Box 14 SE 285 21 Markaryd info nibe se www nibe eu 031725 ...

Отзывы: