MEL  1030, 0040, 1060, 1090, 2090, 2120

25

Installa  on and Opera  on Manual

If you give external voltage to the socket in order to connect the poten   al-free contact, the controller will get damaged. 

A jumper-pin is factory installed in the socket.

CAUTION

7. Ac  va  on and Opera  on

The microprocessor temperature controller is a simple electronic system used to control the hea  ng process. The system con-
trols the heater or set of electrical heaters supplied from the power mains 230V AC (1 phase) or 400V AC (3 phases).

The following 

fi

 gure presents the device with descrip  on of control bu  ons and informa  on LEDs.

No.

Name

Descrip  on

1

Alarm LED

The LED pulses if alarm state is detected.

2

Hea  ng LED

The LED glows if hea  ng is ac  vated. For the 3-phase system, the LED starts pulsing 1oC 
before the pre-set temperature.

3

Bu  on -

Reduces the pre-set value or, if pressed for approx. 3 seconds, changes the controller state 
(ON/OFF) (see more: DIAGRAM).

4

Bu  on +

Increases the pre-set value or, if pressed for approx. 3 seconds, enters the hysteresis chan-
ging menu (see more: DIAGRAM).

5

LED display

Displays current temperature, se   ngs, alarms and controller state.

!

ON/OFF

C

o

25,6

1

2

3

4

5

If the MEL controller is connected to 230V/400V AC mains (depending on its version), the informa  on screen is started with 
current so  ware version and then the controller OFF mode is ac  vated.

In this mode, the hea  ng process control is o

  – all heaters are disconnected from the mains. Pressing the „-” bu  on for 3 

seconds, changes the controller mode into ON and displays current temperature. From this moment, the heater(s) control 
process is ac  vated.

GB

Содержание MEL 0040

Страница 1: ...MEL 1030 MEL 0040 MEL 1060 MEL 1090 MEL 2090 MEL 2120 MODU GRZEJNY Z MIKROPROCESOROWYM REGULATOREM TEMPERATURY INSTRUKCJA INSTALACJI I OBS UGI HEATING MODULE WITH MICRO PROCESSOR TEMPERATURE CONTROL...

Страница 2: ...elektryczne 6 6 1 Pod czenie do 3 faz 4 kW 6 kW 6 6 2 Pod czenie do 1 fazy 3 kW 6 6 3 Pod czenie do 3 faz 9 kW 12 kW 6 6 4 Pod czenie do sterowania zewn trznego 6 7 Uruchomienie i obs uga 7 7 1 Menu...

Страница 3: ...rowie i rodowisko kt ry m g by narasta z powodu niew a ciwego sk adowania odpad w Informacj o punktach utylizacji zu ytego sprz tu elektrycznego i elektronicznego uzyskasz u przedstawiciela lokalnych...

Страница 4: ...jscowienie i monta Modu elektryczny mo e by instalowany wy cznie poziomo zar wno w poziomych jak i w pionowych zbiornikach kt rych konstrukcja uwzgl dnia mo liwo instalacji modu u elektrycznego o para...

Страница 5: ...z powodu ryzyka zamarzni cia wody w pierwszej kolejno ci nale y od czy modu grzejny od zasilania elektrycznego UWAGA Nie zasila urz dzenia z tych samych linii elektrycznych co urz dzenia wysokiej moc...

Страница 6: ...tyku bezpotencja owego Schemat 1 Schemat 2 Przeka nik 230 V N Styk bezpotencja owy Schemat 4 Modu grzejny fabrycznie wyposa ony jest w zwork kt r nale y zast pi przeka nikiem zgodnie ze schematem 3 Je...

Страница 7: ...nie aktywne Dla systemu 3 fazowego dioda pulsuje 1o C przed temperatur zadan 3 Przycisk Zmniejsza warto nastawy lub przytrzymuj c ok 3 sekundy zmienia stan sterownika ON OFF wi cej patrz DIAGRAM 4 Prz...

Страница 8: ...i szej tabeli zestawiono wszystkie monity alarm w wraz z ich opisem Nazwa funkcji Parametr Zakres nastaw Nastawa producenta NASTAWA TEMPERATURY GRZANIA 15 75 C 50o C NASTAWA HISTEREZY TEMPERATURY 1 10...

Страница 9: ...ia temperatur nast puje automatycznie po up ywie 5 sekund liczonych od ostatniego naci ni cia przycisku Poni ej przedstawiony zosta opis parametr w 7 4 Ustawienie temperatury W tym menu u ytkownik ust...

Страница 10: ...k Zakres regulacji temperatury 5 75 o C 3 Rozdzielczo pomiar w 0 1 o C Czas pomiar w 0 5 s Odczyt danych Wy wietlacz LED 7 segmentowy Zabezpieczenie Temperaturowe niezale ne STB 95 o C Temperaturowe p...

Страница 11: ...MEL 1030 0040 1060 1090 2090 2120 11 1 12 2 12 3 13 4 13 5 13 6 15 6 1 3 4 6 15 6 2 1 3 15 6 3 3 9 12 15 6 4 15 7 16 7 1 ON 17 7 2 18 7 3 18 7 4 18 7 5 18 8 19 9 19 10 19 11 BIAWAR 29 RUS...

Страница 12: ...MEL 1030 0040 1060 1090 2090 2120 12 1 Nibe Biawar Sp z o o 2 2006 95 EC 2004 108 EC RUS...

Страница 13: ...MEL 1030 0040 1060 1090 2090 2120 13 80oC BIAWAR 2 3 4 5 1 2 1 1 3 4 5 2 4 6 1 2 7 2 8 9 10 16 5oC 50 C RUS...

Страница 14: ...MEL 1030 0040 1060 1090 2090 2120 14 L 1 2 RUS...

Страница 15: ...030 0040 1060 1090 2090 2120 15 6 3 400 3 1 230 1 6 1 3 4 6 L1 L1 N N L2 L3 L2 L3 H1 H2 H3 L1 L1 N N L2 L3 L2 L3 H1 H2 H3 6 2 1 3 6 4 MEL 1 2 230 V N 4 3 EOn L1 L1 N N L2 L3 L2 L3 H1 H2 H3 6 3 3 9 12...

Страница 16: ...MEL 1030 0040 1060 1090 2090 2120 16 7 230 1 400 3 1 2 3 1oC 3 3 ON OFF 4 3 5 ON OFF C o 25 6 1 2 3 4 5 MEL 230 400 OFF 3 ON RUS...

Страница 17: ...MEL 1030 0040 1060 1090 2090 2120 17 85 oC Protect OFF No Liquid OFF No Hea ng OFF 15 75 C 50o C 1 10 C 2o C 7 1 ON RUS...

Страница 18: ...MEL 1030 0040 1060 1090 2090 2120 18 7 2 7 3 ON 3 5 7 4 3 3 0 5 C 15 75 C 7 5 1 10 C 5 RUS...

Страница 19: ...MEL 2090 MEL 2120 3 kW 4 kW 6 kW 9 kW 12 kW NTC 10 k 5 75 o C 3 0 1 o C 0 5 s 7 STB 95 o C 80 o C 1 C 3 60 NTC 10 230 V 400 V 13 1 A 5 8 A 8 7 A 13 1 A 17 4 A 5 C 50 C 1 3 1 4 1 5 1 7 1 8 1 9 IP 54 1...

Страница 20: ...n 22 6 Electrical connec on 24 6 1 Connec ng to 3 phases 4 kW 6 kW 24 6 2 Connec ng to 1 phase 3 kW 24 6 3 Connec ng to 3 phases 9 kW 12 kW 24 6 4 Connec ng to external control 24 7 Ac va on and Opera...

Страница 21: ...resources and prevents nega ve impact to human health and the environment which could increase due to incorrect waste disposal Informa on on waste equipment management points is available from local...

Страница 22: ...le can be installed only horizontally both in horizontal and in ver cal tanks whose structure allows for installa on of an electrical module of parameters according to the TECHNICAL DATA table as well...

Страница 23: ...the risk of water freezing first disconnect the hea ng module from electrical power supply CAUTION Do not feed the device from the same power lines as high power equipment without appropriate network...

Страница 24: ...ontact Diagram 1 Diagram 2 Relay 230 V N Poten al free contact Diagram 4 The hea ng module is factory equipped with a jumper pin which must be replaced with a relay according to Diagram 3 If the relay...

Страница 25: ...s if hea ng is ac vated For the 3 phase system the LED starts pulsing 1oC before the pre set temperature 3 Bu on Reduces the pre set value or if pressed for approx 3 seconds changes the controller sta...

Страница 26: ...The following table includes all alarm messages with descrip ons Func on Parameter Range of se ngs Factory se ng HEATING TEMPERATURE SET 15 75 C 50o C TEMPERATURE HYSTERESIS SET 1 10 C 2o C 7 1 Func o...

Страница 27: ...temperature display is automa c 5 sec a er the last pressing of the bu on Descrip on of parameters is presented below 7 4 Se ng temperature In this menu you are able to set the temperature to which t...

Страница 28: ...rement resolu on 0 1 o C Time of measurements 0 5 s Reading data 7 segment LED display Protec on Temperature independent STB 95 o C Temperature programmable 80 o C Detec ng lack of water detec ng incr...

Страница 29: ...8A BU 300 8A BU 500 8A BU 750 8A BU 1000 8A BUW 300 8A BUW 500 8A BUW 750 8A BUW 1000 8A BUZ 400 150 BUZ 500 200 BUZ 500 300 BUZ 750 200 BUZ 1000 200 W E 400 81 PC W E 100 81 W E 125 81 W E 150 81 W...

Страница 30: ...ku zasilania energii elektrycznej uszkodze powsta ych na skutek przepi burz powodzi po ar w i podobnych zdarze losowych uszkodze powsta ych wskutek niew a ciwej instalacji i monta u element w eksploat...

Страница 31: ...WY W d KZ WK W Zt Ed 1 KUPON 3 KUPON 2 KUPON W d WK W Zt Ed hWKE d B E D K Z hE h W d WK W Zt Ed hWKE d B E D K Z hE h W d WK W Zt Ed hWKE d B E D K Z hE h DATA NAPRAWY NR RACHUNKU DATA NAPRAWY NR RAC...

Страница 32: ...W WZ t z d WZ z zd Ez WK W Ed d WZ z W d WK W WZ t z KdZK K_ W d WK W WZ t z d WZ z zd Ez WK W Ed DATA PRODUKCJI DATA PRODUKCJI W d WK W WZ t z d WZ z zd Ez WK W Ed DATA PRODUKCJI KUPON INSTALACJI ZER...

Отзывы: