MENU 7.2.11 - VENTILATION HEAT
EXCHANGER (ERS)
Highest fan speed
Setting range: 1 – 100%
Lowest fan speed
Setting range: 1 – 100%
Controlling sensor
Setting range: HTS 1 – 4
Highest fan speed
Here, you set the lowest permitted fan speed under
demand-controlled ventilation.
Lowest fan speed
Here, you set the highest permitted fan speed under
demand-controlled ventilation.
Controlling sensor
Here, you select which exhaust air module(s) will be
affected by which HTS unit(s). If two or more HTS units
control an exhaust air module, the ventilation is adjusted
according the units’ average value.
MENU 7.2.15 - HUMIDITY SENSOR (HTS)
climate system 1 HTS
Setting range: 1–4
limit RH in the room, syst.
Setting range: on/off
prevent condensation, syst.
Setting range: on/off
Up to four humidity sensors (HTS 40) can be installed.
Here you select whether your system(s) is/are to limit
the relative humidity level (RH) during heating or cooling
operation.
You can also choose to limit min. cooling supply and
calculated cooling supply to prevent condensation on
pipes and components in the cooling system.
Technical specifications
HTS 40
85x85x35
(mm)
Plastic spacer WxHxD
85x85x14
(mm)
Dimensions WxHxD
12 VDC 40 mA
(supplied from the heat pump/indoor
module)
Rated voltage
067 538
Part No.
17
HTS 40 | GB