ELECTRICAL CONNECTION
LEK
AA5-X2
AA5-X9
AA5-F1
AA5-X4
AA5-S2
AA5
AA5-X10
SF1
W102
W101
Switch
SF1
Accessory card
AA5
Terminal block, sensors and external blocking
AA5-X2
Terminal block, communication
AA5-X4
Terminal block, circulation pump and reversing valves
AA5-X9
Terminal block, reversing valves
AA5-X10
DIP switch
AA5-S2
Fine wire fuse (T4A, 250V)
AA5-F1
Cable with connection plug, supply
W101
Cable, communication with heat pump or previous
accessory card
W102
TRANSPORT AND STORAGE
HPAC S40 must be transported and stored horizontally and
dry.
NOTE
Do not use the pipes as a handle.
MOUNTING
HPAC S40 is installed on the wall.
First screw the enclosed suspension bracket into place on
the wall. Then hang HPAC S40 on the bracket. HPAC S40
can now be slid sideways to some extent, which facilitates
the fitting of the pipes.
UN
TIP
Install the accompanying securing plate anywhere
at the bottom rear of the cooling module for fur-
ther fastening.
INSPECTION OF THE INSTALLATION
In accordance with current norms, the heating/cooling in-
stallation must undergo an installation check before being
used. The inspection must be carried out by a suitably
qualified person and should be documented.
The above applies to closed heating/cooling installations.
Replacement of the heat pump or the HPAC module is not
permitted without renewed inspection.
HPAC S40 | GB