Reversing valves
Valve positions
The heating/cooling modes are controlled by 4 reversing valves, which, depending on the outdoor temperature, switch
between the different modes.
FLOWCONTROL
FLOWCONTROL
FLOWCONTROL
FLOWCONTROL
41
41
41
41
7KH ZLQGRZV RQ WKH
YDOYHV FDQ VKRZ EOXH RU
UHG GHSHQGLQJ RQ ZKHWKHU
) SURYLGHV KHDWLQJ RU
FRROLQJ
QN16
QN14
QN15
QN13
red
red
red
red
Heating
blue
blue
red
red
Passive cooling
blue
blue
blue
blue
Active cooling.
The above applies to powered systems.
The arrow indicates in which position the valve is set.
Valve position checks
FLOWCONTROL
If the valve motors have become loose and the valves
have come out of position, adjust the position of the
valves using a wrench to obtain the right valve setting.
Adjust the valves according to the previous table "heat-
ing" and install with the valve motors unpowered, set to
default position (current on, control current off) and one
window on the motor displaying red.
At input control signal the valves rotate 90°.
Caution
When changing the heating/cooling mode, there
is a delay of approximately 60 seconds before
the valves change their positions.
16
GB