Technical specifications
FIGHTER 410P
32
IP 21
Rated output, compressor
650 W
Required headroom
2 185 mm
Depth
615 mm
Volume total
240 litres
Volume water heater
170 litres
Output immersion heater
8,0 kW (switchable)
Rated output exhaust air fan
170 W
Max pressure in storage heater
0,9 MPa (9 (bar)
Breaking value, low pressure pressostat
0,15 MPa (1.5 (bar)
Design pressure in double jacket volume
0,25 MPa (2.5 (bar)
Refrigerant type
R290 (propane)
Cut-out temperature compressor
54 °C
Cut-out temperature, temperature limiter for immersion heater
88 °C
Cut-out temperature, temperature limiter for compressor
88 °C
Cut-out temperature immersion heater
52 – 65 °C
*
(52 – 60)
Sound level in room where installed
47 – 50 dBA
Height (excl. foot: 15 – 40 mm)
2 095 mm
Width
600 mm
Weight
200 kg
Volume double jacket
70 litres
Supply voltage
230 V~ 1-phase + N
Rated output, circulation pump
100 W
Rated output supply air fan
170 W
Enclosure class
IP 21
Breaking value, high pressure pressostat
2,45 MPa (24.5 (bar)
Max pressure in double jacket volume
0,25 MPa (2.5 (bar)
Refrigerant volume
495 g
Cut-in temperature compressor
51 °C (Controlled by separate sensor)
Cut-in temperature immersion heater
49 – 62 °C
*
(49 – 57)
*
See the section Electrical connection — Blocking immersion heater operation
For the Installer
Inlet temperature
40 °C
COP
2,60
Total Power input
0,715 kW
Exhaust air:
Air flow
150 m3/h
Inlet wet bulb temperature
12 °C
COP and heating capacity according to EN 14511-2:2004
Heating capacity
1,75 kW
Current
3,6 A
Rating condition:
Inlet dry bulb temperature
20 °C
Water:
Outlet temperature
45 °C