Pipe installation must be carried out in accordance with
current norms and directives.
F2120 can only operate up to a return temperature of
about 55 °C and an outgoing temperature of about
65 °C from the heat pump.
F2120 is not equipped with external shut off valves on
the water side; these must be installed to facilitate any
future servicing. The return temperature is limited by
the return line sensor.
Water volumes
Depending on the size of F2120, an available water
volume is required to prevent short operating times
and to enable defrosting. For optimal operation of
F2120, a minimum available water volume of 10 litres
times the size number is recommended. E.g. F2120-12:
10 litres x 12 = 120 litres.
NOTE
The pipe work must be flushed before the heat
pump is connected, so that any contaminants
do not damage the components.
Pipe coupling heating medium
circuit
■
F2120 can be connected to the heating system ac-
cording to one of the system solutions that can be
downloaded from the website www.nibe.eu.
■
The heat pump must be vented by the upper connec-
tion (XL1) using the venting nipple on the enclosed
flexible hose.
■
Install the enclosed particle filter before the inlet, i.e.
the lower connection (XL2) on F2120.
■
All outdoor pipes must be thermally insulated with
at least 19 mm thick pipe insulation.
■
Install shutoff and drain valves so that F2120 can be
emptied in the event of prolonged power failures.
■
The supplied flexible hoses act as vibration dampers.
The flexible pipes are fitted so an elbow is created,
thus acting as vibration damping.
Charge pump
The charge pump (not included in the product) is
powered and controlled from the indoor module/con-
trol module. It has a built-in anti-freezing function and
must therefore not be switched off when there is a risk
of freezing.
At temperatures below +2 °C the charge pump runs
periodically, to prevent the water from freezing in the
charge circuit. The function also protects against excess
temperatures in the charge circuit.
Pressure drop, heating
medium side
F2120 -8, -12, -16, -20
0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
0
0,05 0,1
0,15 0,2
0,25 0,3
0,35 0,4
0,45 0,5
0,55 0,6
0,65 0,7
0,75 0,8
0,85 0,9
Tryckfall [kPa]
Flöde [l/s]
Tryckfall F2120
F2120-8
F2120-12/-16/-20
Pressure drop kPa
Flow litre/second
F2120-8
F2120-12/-16/-20
Heat insulation
LEK
Heat insulation
21
Chapter 4 |
Pipe connections
NIBE™ F2120
4 Pipe connections
Содержание F2120-12
Страница 1: ...Installer manual LEK NIBE F2120 8 12 16 20 Air water heat pump IHB GB 1621 1 331385...
Страница 2: ......
Страница 15: ...Removing the side cover LEK 15 Chapter 2 Delivery and handling NIBE F2120...
Страница 22: ...Installing flex hoses LEK Data Serie nr Art nr 711453 OUT IN XL1 XL2 NIBE F2120 Chapter 4 Pipe connections 22...
Страница 55: ...Electrical circuit diagram 1x230V 55 Chapter 10 Technical data NIBE F2120...
Страница 56: ...NIBE F2120 Chapter 10 Technical data 56...
Страница 57: ...57 Chapter 10 Technical data NIBE F2120...
Страница 58: ...NIBE F2120 Chapter 10 Technical data 58...
Страница 59: ...3x400V 59 Chapter 10 Technical data NIBE F2120...
Страница 60: ...NIBE F2120 Chapter 10 Technical data 60...
Страница 61: ...61 Chapter 10 Technical data NIBE F2120...
Страница 62: ...NIBE F2120 Chapter 10 Technical data 62...
Страница 64: ......
Страница 65: ......
Страница 66: ......
Страница 67: ......