- 31 -
CHECKING GOOD RUNNING CONDITION
To check that your equipment is working properly put it into operation and wait at least 20 to 30 minutes
and then check the following conditions:
•
The air temperature at the outlet of the evaporator should be 3
°C
to 4
°C
lower than the temperature
of the inlet air.
DESCRIPTION OF PARAMETERS
Code
Type
Description
Min Max
Setting
Units
F01
Language
Portuguese
English
French
German
Italian
Spanish
Czech
---
---
English
---
F02
Clock
Date and Time
---
---
---
---
F03
Chrono Heat
Pump
Week
Weekend
ON/ OFF chrono
---
---
Chrono
=
OFF
---
F04
Chrono
Recirculation
Pump
Week
Weekend
ON/ OFF chrono
---
---
Chrono
=
OFF
---
F05
Mode
Eco
Boost
Auto
---
---
Eco
---
F06
Holidays
Number of days
1
99
0
---
F07
Disinfect
Disinfect function inactive
Disinfect function active once a week (weekly)
Disinfect function active once a month
(monthly)
---
---
Inactive
---
Number of days
2
366
0
---
F08
Parameters
P01
–
Setpoint Compressor 1
10
60
52
°C
H01
–
Gradient P01
2
20
2
°C
P02
–
Setpoint Electrical heater
10
65
52
°C
H02
–
Gradient P02
1
20
3
°C
P01
TCC
–
Setpoint Compressor
10
60
55
°C
H01 TCC
–
Gradient P01 TCC
2
20
2
°C
P02 TCC
–
Setpoint Electrical heater
10
65
65
°C