The minimum distance in front of the stove opening to combustible parts of the building 
or interior decoration must be at least 1,4 m.

The dimension diagrams only show the minimum permitted installation distances for the 
stove. When connecting to a steel flue, also note the safety distance requirements of 
the flue. The safety distance between an uninsulated flue and a combustible part of the 
building should be at least 500 mm.

Installation distances 

A =  height from floor to chimney connection upwards
B =  height from floor to c/c chimney connection rear
C =  height from floor to air inlet

**   To prevent discolouration of painted non-flammable walls we recommend that the same side distance as to combustible walls is used.
***  Example of an approved firewall is 120 mm solid brick or 100 mm aerated concrete.

INSTALLATION AGAINST COMBUSTIBLE WALLS

INSTALLATION AGAINST FIREWALLS

C210

170

**50

305

**50

570

150

500

Fire-retardant wall of

brick or concrete

***

Constructional

Hearth

320

200

250

400

150

150

500

Combustible wall

Constructional

Hearth

365

100

520

775

500

800

Combustible wall

Constructional

Hearth

315

**50

445

700

500

800

Fire-retardant wall of

brick or concrete

Constructional

Hearth

***

650

1875

615

500

250

Combustible roof

Constructional

Hearth

B 505

A 605

125

C 100

410

500

25

15

355

115

Air inlet Ø80

Ø126

Constructional

Hearth

Combustible floor

2100

275

500

250

880

845

 B 735

Combustible roof

Combustible floor

Содержание Contura C210

Страница 1: ...C210 C210G contura eu ...

Страница 2: ...laration 9 EU försäkran om överrenskommelse 10 Montering 15 Facts 3 Installation distances 4 Declaration of performance 5 EU Declaration of Conformity 6 Assembly 15 Fakta 11 Installasjonsavstand 12 Ytelseserklæring 13 EU samsvarserklæring 14 Montering 15 ...

Страница 3: ...of the strong heat radiated through the hatch glass Placing flammable material closer than the safe distance indicated may cause a fire Pyre lighting can cause quick gas ignition with the risk of damage to property and personal injury Connection to chimney The stove must be connected to chimneys dimensioned for a minimum flue gas temperature of 400 C The stove should not be installed in a chimney ...

Страница 4: ...on of painted non flammable walls we recommend that the same side distance as to combustible walls is used Example of an approved firewall is 120 mm solid brick or 100 mm aerated concrete INSTALLATION AGAINST COMBUSTIBLE WALLS INSTALLATION AGAINST FIREWALLS C210 170 50 305 50 570 150 500 Fire retardant wall of brick or concrete Constructional Hearth 320 200 250 400 150 150 500 Combustible wall Con...

Страница 5: ...e classification A1 Minimum distance to flammable materials Rear 200 mm Side 250 mm Ceiling 1200 mm Front 1400 mm Floor 0 250 mm Corner 100 mm Fire hazard due to burning fuel falling out Pass EN 13240 2001 A2 2004 AC 2007 Cleanability Pass Emissions from combustion CO 1500 mg Nm3 13 O2 Surface temperatures Pass Temperature on the handle Pass Mechanical resistance Pass Temperature in the space for ...

Страница 6: ...control No In standby mode elSB kW With mechanic thermostat room temperature control No With electronic room temperature control No With electronic room temperature control plus day timer No With electronic room temperature control plus week timer No OTHER CONTROL OPTIONS Room temperature control with presence detection No Room temperature control with open window detection No With distance contro...

Страница 7: ...løse deler demonteres Demontering av ildstedsbekledning er beskrevet til slutt i denne veiledningen 1 Brennplater og hvelv Vermikulitt 2 Typeskilt 3 Kubbestopper 4 Rist 5 Innvendig bunnplate 6 Varmluftsgitter 7 Serienummer Prior to installation If the stove needs to be laid down for it to be moved loose components should be removed A description of how to remove hearth cladding can be found at the...

Страница 8: ...16 10 10 VA NA DIU M No 7 CHROME 1 2 LEK 10 10 VA NA DI UM No 7 CHRO M E ...

Страница 9: ...17 Ø ca 180 mm 2 1 4 3 SE NO GB Bakåtanslutning till murad skorsten Bakmontering til murt skorstein Rear connection to a masonry chimney ...

Страница 10: ...18 HK HK 1 2 SE GB NO Tilluft Tillbehör Supply Accessory Tilluft Tilbehør ...

Страница 11: ...19 1 3 2 ...

Страница 12: ...20 4 3 1 2 SE GB NO Demontera eldstadsbeklädnaden Vermiculit How to remove the hearth surround Vermiculite Slik demonterer du ildstedsbekledningen Vermikulitt Handle with care ...

Страница 13: ...21 7 5 6 ...

Страница 14: ...rmanent stop to prevent closure of the air control unit beyond 31 open position Note When refuling open the air control fully for 3 5 minutes before closing down to the minimum air setting Mandatory for smoke control areas The permanent stop must be installed if the appliance is to be used in a smoke control area this stop must not be removed in smoke control areas otherwise an offence will be com...

Страница 15: ...23 1 2 SE GB NO Placering på vedfack Tillbehör Positioning the log box Accessory Plassering av vedrom Tilbehør ...

Страница 16: ...24 4 5 3 ...

Страница 17: ...25 6 7 8 ...

Страница 18: ...26 1 3 2 SE GB NO Montering av nedre lucka Tillbehör Installing the bottom door Accessory Montering av dør til nedre del Tilbehør ...

Страница 19: ......

Страница 20: ...811482 IAV SE EX C210 2 2022 08 31 NIBE AB Box 134 285 23 Markaryd Sweden contura eu ...

Отзывы: