background image

User Manual

Version 5.3

1 - Introduction:

Congratulations for buying the NIBBLE FIREWALL Fire Alarm Control Panel!

In this manual you will find a detailed description of all functionalities and operating modes.
The NIBBLE Fire Alarm Control Panel is suited to conventional systems, offering high security patterns in different applications.
The FIREWALL complies with 

EN-54

 and its main features are:

Up to 16 zones,

 monitoring both short-circuits and open-circuits;

Up to 

32 conventional detectors

, by each zone;

Open-collector programmable auxiliary outputs

 (one by zone);

Up to 2 relays that can be programmed to signal several fails or fire alarm;

Monitored output against short-circuits and open-circuits for sounder of 24VDC and up to 500mA;

Configurable delay between detection and signaling of the fire alarm allows user to avoid false alarms that some detectors could generate
(normally during the day);

24VDC outputs

 allow to connect external circuits up to 500mA;

Backup power-supply through 

only one battery of 12 VDC / 7Ah

, or two batteries of 6 VDC / 12Ah in series.

User-friendly

 frontal panel.

2 - Features:

2.1  Delay mode:

Some detectors could generate false alarms because of electromagnetic or light interferences. To avoid the occurrence of such false alarms, the

FIREWALL could be configured to introduce a delay between the detection instant (by the detectors) and the actuation by the control panel.

This time period is programmable and allows the user to reset the control panel when he verifies the alarm doesn't exist.

2.2  Intelligent and automatic zones:

The circuits of detection can be constituted by conventional detectors and callpoints. In the case of callpoints, the signaling of the fire alarm

should be immediately executed.

An intelligent zone have the ability to distinguish if the alarm was generated from a detector or from a callpoint, and when in “Delay mode” the

delay is only applied to the detections which origin was a detector.

In an automatic zone, there is no difference between detectors and callpoints, and the alarm is immediately signaled.

2.3  Open-collector auxiliary outputs:

For each zone is available an auxiliary output that can be configured to signal a failure or an alarm detection in the corresponding zone. Each of

these open-collector outputs can sink up to 500mA

.

2.4  Automatic test: 

The FIREWALL has a test mode which resets the system automatically after an alarm (see  7.6) allowing the system to be tested by a single

person.

2.5  Smart setup: 

The FIREWALL can be configured to adapt to any detector, manual callpoint, or termination resistor (see  7.7). This way, it is possible to replace

another fire alarm panel by a NIBBLE FIREWALL without having to change the existing circuit.

2.6  Maintenance warning: 

In order to always ensure the safety of the premises, the FIREWALL can notify when it’s time to perform a check-up. The maintenance period can

be configured according to section 4.7.

3 - Mounting:

The FIREWALL is for indoor use with low humidity, and should be mounted in vertical position with screws.
It can be mounted either in flush or surface positions, keeping access to the frontal cover for mounting and maintenance purposes.

Note

: Detectors should be mounted near the fire alarm control panel. This allows to minimize the risk of control panel destruction

by the fire before emitting the alarm. Automatic fire extinguish systems should be placed avoiding control panel damaging when actuated
(eg. 'sprinkler').

4 - Connections:

With exception for power supply and relays, it is recommended to use shielded cables with a section of at least

0,25 mm

2

, and the shield should be connected to earth.

4.1  Main power supply:

There is a connector to connect the control panel to main power supply. It is recommended to use cable type

A05VV-F with 3 wires with section of 1,5 mm

2

.

This connector have also the main fusible (F4A L250V).
To power the control panel on and off the circuit switch, located upstream, should be used with a minimum of

16A.

Note

: Power on the control panel only after finishing all connections.

4.2  Zones:

For each zone there are available 4 terminals, 2

for   the   detection   circuit   and   2   for   an   open-collector
auxiliary output (Figure 2).

The   auxiliary   output   signals   the   detection   of   an

alarm   in   the   corresponding   zone.   When   activated,   it
closes   the   circuit   between   AUXn+   and   AUXn–

2 / 8

Figure 3: Zone with detectors and termination resistor.

R

Figure 2: Zone 
connectors.

Figure 1: Power supply 
connector

Содержание EN 54-2

Страница 1: ...o 16 ZONES EC Certificate of Conformity ref NGQ05020008 NIBBLE Engenharia Lda Rua Júlio Dinis 265 1D 4785 330 Trofa Portugal EN 54 2 EN 54 4 FIRE DETECTION AND FIRE ALARM SYSTEMS CONTROL AND INDICATING EQUIPMENT POWER SUPPLY EQUIPMENT FIRE ALARM CONTROL PANEL 1 8 ...

Страница 2: ... is available an auxiliary output that can be configured to signal a failure or an alarm detection in the corresponding zone Each of these open collector outputs can sink up to 500mA 2 4 Automatic test The FIREWALL has a test mode which resets the system automatically after an alarm see 7 6 allowing the system to be tested by a single person 2 5 Smart setup The FIREWALL can be configured to adapt ...

Страница 3: ...ion of fails due to short circuit or open circuit It should be used a termination resistor of 3300Ω 1 4W at the end of line and in parallel with the sounder s 4 5 Auxiliary power It is available an auxiliary output to power external equipments up to 500mA 24VDC 4 6 Battery It is mandatory to use a battery lead acid not included with the equipment of 12VDC 7Ah or two batteries of 6VDC 12Ah connecte...

Страница 4: ...le to detect short circuits or open circuits If a short circuit is detected this LED blinks fast in case of open circuit it will blink slowly This LED also indicates if a zone is active or not When permanently ON it indicates inactive zone 6 1 3 Zone alarm indication LED This LED indicates an alarm in the corresponding zone If it blinks fast it means that the alarm was signaled at a callpoint If i...

Страница 5: ...t circuit occurs the LED blinks fast and when an open circuit is detected the LED blinks slowly 6 1 16 Sounder fuse fail indication LED When the maximum specifications for sounders output is not respected 500mA the fuse opens the circuit to prevent damages When this happens the yellow LED indicates it 6 1 17 Disabled indication LED When any functionality of the FIREWALL is deactivated a zone for e...

Страница 6: ...a successful operation and a single beep otherwise 7 1 General These general configurations allow to change the access code and to reset all parameters to the default ones Note Resetting the parameters to the default values will also set the access code to the default one Buzzer Sounder Sounder Buzzer 7 1 1 Change access code 1 Press Z1 key 2 A double beep is emitted 3 Enter new code using any com...

Страница 7: ...f an alarm To enter the test mode follow the next procedure 1 Press the Buzzer and Siren keys to increase or decrease the alarm time before perform the automatic reset It can be configured with the values of 1s 5s 10s 15s 30s and 1min 2 The selected delay is represented by the LEDs Main power 24VDC Fuse Earth Battery and Battery state A delay of 1s is represented by all LEDs off and the maximum de...

Страница 8: ...elay is associated to LEDs Earth Battery and Battery state All LEDs OFF corresponds to maintenance disabled and the maximum maintenance period corresponds to all LEDs ON 3 Press Delay Mode key to accept and Reset key to cancel 4 A double beep will be emitted in case of a successful operation and a single beep otherwise backing to the previous state When the period is reached the FIREWALL will enab...

Отзывы: