FC Flow Computer
81
COMMUNICATION
6.13
COMMUNICATION
(Continued)
Select YES or NO for Modem Control.
Selection:
YES - Modem initializationand dialing commands are sent
during transactions.
NO - Modem initializationand dialing commands are NOT
sent during transactions.
Display:
YES
MODEM CONTROL
Select YES or NO for Device Master
Selection:
YES - Sets sole master device responsible for initializing
modem.
NO - Device will not be used to initialize modem.
Display:
YES
DEVICE MASTER
MODEM CONTROL
(Modem)
DEVICE MASTER
(Modem)
Select YES or NO for Send Inc. Tot. Only
Selection:
YES - Unit will send Inc. Tot. Only
NO - Unit will not send Inc. Tot. Only
Display:
YES
SEND INC. TOT. ONLY
Enter multiplying factor for Inc Only Scaler
Selection:
X1, X10, X100, X1000
Display:
X1
INC ONLY SCALER
Select YES or NO for Clear Datalog
Selection:
YES - Unit wil clear datalog contents
NO - Unit will not clear datalog contents
Display:
YES
CLEAR DATALOG
SEND INC. TOT. ONLY
INC ONLY SCALER
CLEAR DATALOG