Caution
Ensure that hazardous voltage wiring is performed only by
qualified personnel adhering to local electrical standards.
Caution
Do not mix hazardous voltage circuits and human-accessible
circuits on the same module.
Caution
Ensure that devices and circuits connected to the module are
properly insulated from human contact.
Caution
When module terminals are hazardous voltage LIVE (>42.4 Vpk/
60 VDC), you must ensure that devices and circuits connected to the
module are properly insulated from human contact. You must use the
NI 9940 backshell kit to ensure that the terminals are not accessible.
Safety Guidelines for Hazardous Locations
The NI 9205 is suitable for use in Class I, Division 2, Groups A, B, C, D, T4 hazardous
locations; Class I, Zone 2, AEx nA IIC T4 Gc and Ex nA IIC T4 Gc hazardous locations;
and nonhazardous locations only. Follow these guidelines if you are installing the
NI 9205 in a potentially explosive environment. Not following these guidelines may
result in serious injury or death.
Caution
Do not disconnect I/O-side wires or connectors unless power has
been switched off or the area is known to be nonhazardous.
Caution
Do not remove modules unless power has been switched off or
the area is known to be nonhazardous.
Caution
Substitution of components may impair suitability for Class I,
Division 2, or Zone 2.
ni.com
6
NI-9205 Getting Started