National Instruments Corp.
13
FP-AIO-600 and cFP-AIO-600
Caution
For Zone 2 applications, install a protection
device across the external power supply and the COM
terminal. The device must prevent the external power
supply voltage from exceeding 42 V if there is a transient
overvoltage condition.
Special Conditions for Hazardous Locations Use in Europe
The cFP-AIO-600 has been evaluated as EEx nC IIC T4 equipment
under DEMKO Certificate No. 03 ATEX 0251502X. Each module
is marked
II 3G and is suitable for use in Zone 2 hazardous
locations.
Specifications
The following specifications are maximums for the range –40 to
70 °C unless otherwise noted. Specifications are subject to change
without notice.
Input and Output Characteristics
Number of input channels................. 4
Number of output channels............... 4
ADC resolution................................. 12 bits
Type of ADC..................................... Successive approximation
DAC resolution ................................. 12 bits
Type of DAC ..................................... R-2R
Hardware update rate
(all 8 channels).................................. 1.7 kHz (588
s period)
Voltage Inputs
Effective resolution ........................... 11.3 bits
Input impedance................................ 1.5 M
Signal input bandwidth (–3 dB)........ 350 Hz
Voltage input accuracy by voltage input range
Voltage Input
Range (with
Overranging)
Accuracy
at 15 to 35
°
C
(% of Reading;
% of Full Scale)
Accuracy
at – 40 to 70
°
C
(% of Reading;
% of Full Scale)
0–6 V
0.04%;
0.15%
0.16%;
0.25%
0–12 V
0.04%;
0.12%
0.16%;
0.17%