nextys OR50 Скачать руководство пользователя страница 4

OR50 

Instruction Manual 

 

 

 

SI000036A01_I.S.OR50.doc 

www.nextys.com 

Page 4/5 

 

 

 

Fig.4 

Mounting / Dismounting Instructions 

For DIN rail fastening according to IEC 60715 TH35-7.5(-15) 

Mounting as shown in figure, with input terminals on lower side, with suitable cooling and maintaining a proper distance between adjacent devices as specified in the I.S. 

manual of each family. 

Mounting: 

1.

 

Tilt the unit slightly backwards. 

2.

 

Fit the unit over the top edge of the rail. 

3.

 

Slide it downward until it hits the stop. 

4.

 

Press against the bottom for locking. 

 

 

 

 

 

 

Dismounting: 

1.

 

Pull down the slide clamp lever 

2.

 

Tilt the unit upward 

3.

 

Unhook the unit from the rail

 

 

 

1 & 2 

 

 

Fig.5 

Recommended connecting cable

 

 

Recommended Tightening torque 

Input / output 

1.2NM 

10.4 lbf in 

 

Signals 

0.2-0.25Nm 

1.17-2.21 lbf in 

 

 

 

Input / output 

Solid: 0.75-16.0mm² / 18-6AWG 

Stranded: 0.75-16.0mm² / 18-6AWG 

L: 13-14mm / 0.51-0.55in 

 

Signals 

Solid: 0.05-1.5mm² / 30-14AWG 

Stranded: 0.05-1.5mm² / 30-14AWG  

L: 5-6mm / 0.20-0.24in 

 

Содержание OR50

Страница 1: ...odel 50A Max Extremely low loss up to 99 efficiency Pluggable connectors Hot pluggable Easy acknowledgment of the power supplies availability status Easy correct current share status Up to 75 C operating temperature with no derating INDEX Page Installation Requirements 2 Declaration of Conformity 2 User Instructions 3 Connections 3 Dimensions 3 Distances 3 Mounting 4 Dismounting 4 Set up 5 Environ...

Страница 2: ... LESIONI GRAVI Non effettuare mai operazioni sulle parti sotto tensione Pericolo di lesioni letali Il contenitore può scottare lasciar quindi raffreddare il dispositivo prima di toccarlo Non far entrare liquidi o oggetti estranei nel dispositivo Per evitare scintille non collegare o scollegare l apparecchiatura prima di avere tolto tensione di ingresso e prima che sia avvenuta la scarica dei conde...

Страница 3: ... and are also present on 2 relays dry contacts for remote monitoring of the unit 0BIN1 IN2 OK LED Indicates that the voltage present on IN1 IN2 is 0 9 Vout It is an indication of the presence of the correct voltage from the power supply connected to IN1 IN2 1BFAIL LED Indicates that the system has a problem and the redundancy is no more guaranteed It can have 3 status OFF continuously means that t...

Страница 4: ...t the unit slightly backwards 2 Fit the unit over the top edge of the rail 3 Slide it downward until it hits the stop 4 Press against the bottom for locking 1 2 3 4 Dismounting 1 Pull down the slide clamp lever 2 Tilt the unit upward 3 Unhook the unit from the rail 1 2 3 Fig 5 Recommended connecting cable Recommended Tightening torque Input output 1 2NM 10 4 lbf in Signals 0 2 0 25Nm 1 17 2 21 lbf...

Страница 5: ...5 95 r H non condensing UL certified up to 75 C No Derating Note Data may change without prior notice in order to improve the product Please refer to the latest version of the Instruction Manual for each product by visiting www nextys com See also the products below that can be used in conjunction with OR50 units This device can be used in conjunction with every each our power supply that is able ...

Отзывы: