background image

Short Form Installation Manual 

 

Nextys SA. Via Luserte Sud 6, 6572 Quartino – Switzerland 

Phone: +41-(0)91 8401446 / 8401448; Fax: +41-(0)91 8401447 

Models 

DCW20 - 960W COMBO DC UPS / DC-DC Converter 

File No.: 

I.M.DCW20 

Rev.: 

A01 

 

 

Use latest device Documentation, Software and Firmware to ensure reliable operation of the system  

(downloadable fro

www.nextys.com

)

 

 

 

 

 

 

 

 

 

 

 

 

 

READ THIS CAREFULLY BEFORE INSTALLATION! 

LEGGERE ATTENTAMENTE PRIMA DELL’INSTALLAZIONE! 

A LIRE ATTENTIVEMENT AVANT L’INSTALLATION! 

Before operating, read this document thoroughly and retain it for 

future reference. 

Non-respect of these instructions may reduce performances and 

safety of the devices and cause danger for people and property. 

The products must be installed, operated, serviced and maintained 

by qualified personnel in compliance with applicable standards 

and regulations. 

Don’t open the device, it does not contain replaceable 

components, the tripping of the internal fuse (if included) is 

caused by an internal failure.  

Don’t repair or modify the device, if malfunction or failure should 

occur during operation, send unit to the factory for inspection. No 

responsibility is assumed by Nextys SA for any consequences 

deriving from the use of this material. 

Prima dell’installazione, leggere attentamente questo documento 

istruzioni e conservarle per future consultazioni.  

L’inosservanza delle presenti istruzioni può compromettere le 

caratteristiche e la sicurezza dell’apparecchio e causare pericolo per le 

persone e le cose. 

Il prodotto deve essere installato, utilizzato e riparato da personale 

qualificato e nel rispetto delle normative vigenti.  

Non aprire il prodotto, esso non contiene componenti sostituibili, il 

guasto del fusibile interno (se previsto) è causato da un guasto interno. 

Non tentare di riparare o modificare il prodotto, se durante il 

funzionamento si verificano guasti o anomalie, inviarlo al produttore per 

il controllo. 

Nextys SA non si assume nessuna responsabilità per qualunque 

conseguenza derivante dall’uso di questo materiale. 

Lire ces instructions avant l'installation, conserver ce manuel pour 

référence future.  

Défaut de se conformer à ces instructions peut affecter les 

caractéristiques et la sécurité du dispositif, et causer du danger aux 

personnes ou aux biens. 

Les produits doivent être installés, exploités et entretenus par du 

personnel qualifié et en conformité avec les règlements. 

N'ouvrez pas le produit, il ne contient aucune pièce réparable, le 

déclenchement du fusible interne (le cas échéant) est causé par un 

défaut interne. Ne pas essayer de réparer ou modifier le produit ; si 

des défaillances se produisent pendant le fonctionnement, retourner 

le produit  au fabricant pour inspection. Nextys SA n'assume aucune 

responsabilité des conséquences éventuelles découlant de 

l'utilisation des produits. 

CAUTION 

ATTENZIONE 

AVVERTISSEMENT 

RISK OF BURNS, EXPLOSION, FIRE, ELECTRICAL SHOCK, PERSONAL 

INJURY. 

Never carry out work on live parts! Danger of fatal injury! The 

product’s enclosure may be hot, allow time for cooling product 

before touching it. Do not allow liquids or foreign objects to enter 

into the products.  

To avoid sparks, do not connect or disconnect the device before 

having previously turned-off input power and wait for internal 

capacitors discharge (minimum 1 minute). 

RISCHIO USTIONI, ESPLOSIONE, INCENDIO, SCOSSA, LESIONI GRAVI. 

Non effettuare mai operazioni sulle parti sotto tensione! Pericolo di 

lesioni letali! Il contenitore può scottare, lasciar quindi raffreddare il 

dispositivo prima di toccarlo. Non far entrare liquidi o oggetti estranei 

nel dispositivo. 

Per evitare scintille, non collegare o scollegare l'apparecchiatura prima 

di avere tolto tensione di ingresso e prima che sia avvenuta la scarica 

dei condensatori interni (min. 1 minuto). 

RISQUE DE BRULURES, EXPLOSION, INCENDIE, ELECTROCUTION, 

DOMMAGE AUX PERSONNES. 

Ne jamais effectuer des opérations sur les parties sous tension! 

Danger de mort! Le boîtier peut produire des brûlures, le laisser 

refroidir avant de toucher l'appareil. Ne faire pas pénétrer des 

liquides ou des corps étrangers dans l'appareil. Pour éviter des 

étincelles, ne pas connecter ou déconnecter l'équipement jusqu'à ce 

que la tension d'entrée a été supprimée et avant qu'il n'ait eut lieu la 

décharge des condensateurs internes (minimum 1 minute).

 

INTENDED USE  

USO PREVISTO  

UTILISATION  

These are isolated devices suitable for 

SELV

 and 

PELV

 circuitry and 

are designed to be mounted on DIN rail and installed inside a 

protective enclosure. They are intended for general use such as in 

industrial control, communication, and instrumentation 

equipment.  

Don’t use these devices in applications where malfunction may 

cause injury or death. 

I dispositivi sono isolati, adatti per applicazioni 

SELV

 e 

PELV

, sono dotati 

di aggancio per il montaggio su guida DIN all’interno di quadri elettrici o 

contenitori di protezione, per l’utilizzo con controllori industriali, unità 

di comunicazione o apparecchi di misura.  

Non utilizzare in applicazioni in cui un eventuale guasto può comportare 

rischio di lesioni o di morte. 

Les produits sont isolés, appropriés pour les circuits 

TBTS

 et 

TBTP

 et 

sont équipés d'un crochet pour montage sur rail DIN dans des 

armoires ou conteneurs de protection, pour utilisation avec les 

contrôleurs industriels, des modules de communication ou des unités 

de mesure.  

Ne pas utiliser ces dispositifs dans une application où un 

dysfonctionnement pourrait entraîner le risque des blessures ou de 

mort. 

ENVIRONMENTAL CHARACTERISTICS 

CARATTERISTICHE AMBIENTALI 

CARACTÉRISTIQUES ENVIRONMENTALES 

Installation in a Pollution Degree 2 environment, Overvoltage 

Category I, according to IEC60664-1. 

Do not use in wet area or subject to moisture. 

Carefully recycle the product and related batteries according to 

local regulations. 

Usare in ambienti con Grado di Inquinamento 2 e Categoria di 

Sovratensione I, secondo IEC60664-1.  

Non far funzionare l'apparecchio in un ambiente umido o soggetto a 

formazione di condensa. Riciclare il prodotto e le batterie collegate, nel 

rispetto delle normative locali vigenti. 

Utiliser les produits dans des environnements avec degré de pollution 

2, catégorie de surtension I selon IECN60664-1.  

Ne pas employer l'appareil dans un environnement humide ou 

soumis à la condensation. Recycler les produits et les batteries, 

conformément à la réglementation locale.. 

 

Declaration of Conformity 

 

NEXTYS SA.

 

Via Luserte Sud 6, 6572 Quartino - Switzerland 

Phone: +41-(0)91 840 14 46 / 840 14 48; Fax: +41-(0)91 840 14 47 

E-mail

[email protected]

 

This Declaration of Conformity is suitable to the European Standard EN45014 "General criteria for supplier’s declaration of conformity". 

We declare under our sole responsibility that the device included in this box, has passed all processing inspections and the final test and it is in conformity with the product requirements, including all reference 

codes and supply specifications. 

ROHS compliance:

 the product respects the EC requirements related to ROHS substances, according to “Restriction of Hazardous Substances” as per document 2011/65/UE

 

REACH compliance:

 the product respects the EC requirements related to REACH SVHC directive (EC) 1907/2006 

 

Note:

 all the reported information comes from our suppliers, NEXTYS SA. has not run any test to evaluate if the specific elements are present. 

All indicated devices are designed according to the latest Reference standards, if not expressly indicated through the official documents or files, they have been tested through our internal pre-compliance 

testing. Consult directly on www.nextys.com the reference standards applied to each model. 

Code 

 

Description

 

DCW20 

 

Combo DC UPS / DC-DC Converter 960W 

Certifications and approvals

 

 

 

 

 

 

Reference standards 

2014/35/EU (2014) 

 

(Low Voltage Directive) 

2014/30/EU (2014) 

 

(EMC directive) 

UL508 

 

 

(Certified - IND. CONT. EQ. 4WX9 file no. E356563) 

EN61010-1   

 

(Safety Standard) 

EN61010-2-201 

 

(Safety Standard) 

EN61000-6-2 

 

(Generic immunity standard for industrial environments) 

EN61000-6-3 

 

(Generic emission standard for residential environments) 

Содержание DCW20

Страница 1: ...de mort Le boîtier peut produire des brûlures le laisser refroidir avant de toucher l appareil Ne faire pas pénétrer des liquides ou des corps étrangers dans l appareil Pour éviter des étincelles ne pas connecter ou déconnecter l équipement jusqu à ce que la tension d entrée a été supprimée et avant qu il n ait eut lieu la décharge des condensateurs internes minimum 1 minute INTENDED USE USO PREVI...

Страница 2: ...lso possible through RS485 connection 6 Inhibit input A voltage between 5VDC and 30VDC applied to this input activates the inhibit function 7 Auxiliary output supply Maximum 5A supply from the battery unregulated 8 Input connection 2 poles are provided for input connection This must be connected to a power supply rated 12 48VDC 9 Output connection 2 poles are provided for output connection It must...

Страница 3: ...h user settable limits When used as a DC DC converter the input supply must be connected to the battery connector as shown on to the side Additional Functions Battery health monitor Internal resistance measurement The resistance is periodically measured The internal resistance is a good indicator of the battery health status a sudden increase of the internal resistance indicates a potential proble...

Страница 4: ...e optional external sensor exceed the threshold specified in Battery max temperature field If active the battery charged is disabled Battery lifetime elapsed Bat lifetime Active when the actual calculated battery lifetime exceeds the threshold specified in Battery lifetime field Battery charge failure Bat charge fail Active when DCW20 could not charge the battery correctly When active the battery ...

Страница 5: ...harge 5 User Mounting Dismounting Instructions For DIN rail mounting according to IEC 60715 TH35 7 5 15 Mounting as shown in figure with input terminals on lower side with suitable cooling and maintaining a proper distance between adjacent devices as specified in the User manual Mounting 1 Tilt the unit slightly backwards 2 Fit the unit over the top edge of the rail 3 Slide it downward until it hi...

Страница 6: ...n Auxiliary connections Insertion force per pole Max 3N or 0 674 lbf Withdrawal force per pole Min 1 5N or 0 337 lbf IN OUT BATT IN connections Solid 2 5mm 12AWG Stranded 2 5mm 12AWG L 7 0 8 0mm 0 27 0 315in Auxiliary connections Solid 0 75mm 18AWG Stranded 0 75mm 18AWG L 7 0 8 0mm 0 27 0 315in NOTES ...

Страница 7: ...7 ...

Отзывы: