40
E
n
gl
is
h
Short circuit
clearance
<enable><disable>
If enable, inverter continues output for 4S,
if output voltage recover to more than 50
percent of rating voltage, UPS stay on the
original mode, otherwise, cut off the output.
If disable, inverter limits the current within
100ms, and then fault, cutting off the
output.
disable
Bypass voltage
low limit
<120V>……..<215V>
184V
Bypass voltage
high limit
<245V>……..<276V>
264V
Bypass frequency
low limit
<40.0HZ>……..<49.5HZ>
45.0HZ
Bypass frequency
high limit
<50.5HZ>……..<70.0HZ>
55.0HZ
HE voltage low
limit
<5%(218.5V)> ……..<10%(207.0V)>
5%(218.5V)
HE voltage high
limit
<5%(241.5V)> ……..<10%(253.0V)>
5%(241.5V)
HE frequency low
limit
<5%(47.5HZ)> ……..<10%(45.0HZ)>
5%(47.5HZ)
HE frequency
high limit
<5%(52.5HZ)> ……..<10%(55.0HZ)>
5%(52.5HZ)
External battery
module
<0>……..<9>
0 means no EXB connected.
1 means one EXB connected.
0
Dry contact signal
input
<disable><UPS ON><UPS
OFF><Maintain Byp On>
disable
Dry contact signal
output
<Summary alarm><On battery><Batt
low><UPS ok><On bypass>
Summary alarm
Set running time
Day:0000-9999
Hour:00-23
Minute:00-59
Second:00-59
Day:0000
Time:00:00:00
LCD contrast
<-5>……..<+5>
The LCD Contrast is adjustable and the
valid range is from -5 to +5.
This range covers the maximum
adjustment for contrasting the background
with the text in the visual display of the
control panel.
0