3) Load segments: are commands to control two load segments when UPS
is in output mode.
4) Clear EPO status: once EPO status is enabled, the UPS output would be
cut off. To recover to normal status, first EPO connector should be closed,
and enter this menu to clear EPO status, then UPS would stop alarm and
recover to bypass or standby mode. And UPS needs be turned on by
manual operation.
5) Reset Fault status: when fault occurs, UPS would keep in Fault mode and
alarm. To recover to normal status, enter this menu to reset error status,
then UPS would stop alarm and recover to bypass or standby mode. And
the reason of fault should be checked and deleted before UPS is turned
on again by manual operation.
6) Clear event log: To clear all the event, alarm and fault have been
recorded.
7) Restore factory settings: all the settings would be recover to default
factory settings. It could only be done in bypass or standby mode.