45
on the other end of the connection. For Unix systems, the command is:
stty –crtscts < /dev/[serial port]
y
Serial Supervisor
devices use a simple RS-485 multidrop network running at
115,200 bps. It is possible that every
Serial Supervisor
device will not be
inputting/outputting data at the same rate at all time. However, since these devices
use interactive logins, it is unlikely that all channels would be busy at any one time.
Hardware handshaking is used to limit the output rate of individual channels as
needed.
y
A maximum of four users may simultaneously login to the same device. All users
may type commands at any time, and all users will see the same output. Note the
following:
y
All users have equal access to all channels.
y
A maximum of 16
Serial Supervisor
devices may be connected at any one
time.
You plug-in and unplug any
Serial Supervisor
device at any time. When reconnected,
it will automatically become available after a 15 second initialization period. Any log
entries will be retained by the
Serial Supervisor
device while deactivated, but will not
be available to users until it is re-initialized.