6
Menu Configuration
Not all menu items display on standard meters.
Table 6-2. Front Panel Displays (Continued)
MENU
©
/DEV
¶
/MAX
DESCRIPTION
OT.CF
OUTPUT CONFIGURATION
O.1=
D
Disable analog output
E
Enable analog output
O.2=
V
Analog output = voltage
C
Analog output = current
O.3=
R
Regular analog output
P
Proportional analog output
O.4=
D
Proportional analog output
is direct acting
R
Proportional analog output
is reverse acting
O.5=
F
Analog output is 0-10 Vdc
H
Analog output is 0-5 Vdc
If you select O.2 = V, you may select your analog output to be 0-10 V or 0-5 V by
accessing submenu O.5. If you select O.3=P, you may select your proportional output
analog to be direct or reverse acting (4-20 or 20-4).
OT.S.O
OUTPUT SCALE AND OFFSET
Enter new value Show RD 1 and
and show:
prior value entered.
Scroll right one digit
OUT1.
Enter new value
Prior value entered. Change the flashing
and show:
Scroll right one digit
digit's value
RD 2.
Enter new value
Prior value entered. Change the flashing
and show:
digit's value
OUT2.
Scroll right one digit
Change the flashing
digit's value
P.BND
Scroll right one digit
Change the flashing
PROPORTIONAL BAND
text
digit's value
Select from 0000 through 9999
M.RST
Scroll right one digit
Change the flashing
MANUAL RESET
digit's value
Select from -1999 through 9999
34