SL
set left travel limit
IMM
PGM
MIP
USAGE
♦
♦
♦
SYNTAX
xx
SL
nn or xx
SL
?
PARAMETERS
Description
xx
[ int ] -
axis number
nn
[float] -
left (negative) software limit
Range
xx
-
1
to
MAX AXES
nn
-
-2e9
∗
encoder resolution
to 0
Units
xx
-
none
nn
-
predefined motion units
Defaults
xx
missing:
error 37, AXIS NUMBER MISSING
out of range:
error 9, AXIS NUMBER OUT OF RANGE
nn
missing:
error 38, COMMAND PARAMETER MISSING
out of range:
error xx2, PARAMETER OUT OF RANGE
DESCRIPTION
This command defines the value for the negative (left) software travel limit. It
should be used to restrict travel in the negative direction to protect the motion
device or its load. For instance, if traveling full range, a stage could push its load
into an obstacle. To prevent this, the user can reduce the allowed travel by
changing
the
software
travel
limit.
Since a motion device must be allowed to find its home position, the home switch and/or
sensor must be inside the travel limits. This means that both positive and negative travel
limits cannot be set on the same side of the home position. A more obvious restriction is
that the negative limit cannot be greater than the positive limit. If any of these restrictions
is not respected, the controller will return PARAMETER OUT OF RANGE.
Note:
If the command is issued for an axis in motion, the new limit should not be set
inside
the
current
travel.
Note:
For software units to take effect they must be enabled using the
ZS
command.
CAUTION
Be careful when using this command. The controller does not know the real
hardware limits of the motion device. Always set the software limits inside the
hardware limits (limit switches). In normal operation, a motion device
should never hit a limit switch.
RETURNS
If the “?” sign takes the place of
nn
value, this command reports the current setting
REL. COMMANDS
OR
-
search for home
SR
-
set right software limits
EXAMPLE
1SL41.4 |
set negative travel limit of axis #1 to 41.4 units
Section 3 – Remote Mode
3-131
Содержание ESP300 Series
Страница 1: ...ESP300 Motion Controller Driver User s Manual...
Страница 4: ...ESP300 1999 EU Declaration of Conformity iv Preface...
Страница 29: ...This page is intentionally left blank Section 2 Modes of Operation 1 15...
Страница 30: ......
Страница 230: ...4 16 Section 4 Advanced Capabilities...
Страница 274: ...This page is intentionally left blank 6 6 Section 6 Servo Tuning...
Страница 290: ...This page is intentionally left blank B 6 Appendix B Trouble Shooting and Maintenance...