The Home Basic Edition can be configured locally using
the rotary switches and dip switches on the chargepoint.
Make sure that the charge point is not yet powered on
before configuring the features described in this chapter.
6.1 POWER SETTING
Select the maximum allowed current for the installed
circuit. Take the MCB, RCD, grid connection and local
regulations into account. Use table 1.1 to determine your
desired position of the left rotary switch, as indicated in
the ’3.4.3 Overview Installing Accessories’ section. In
case of the 11 kW chargepoint, the maximum allowed
current can only be 16 A. The left rotary switch will have
no functionality. Take the MCB, RCD, grid connection and
local regulations into account.
Rotary
Position
Maximum
allowed current
7,4 kW
Maximum
allowed current
11 kW
0
16 A
16 A
1
20 A
16 A
2
25 A
16 A
3
32 A
16 A
4
16 A
16 A
5
20 A
16 A
6
25 A
16 A
7
32 A
16 A
Table 1.1: Maximum allowed current
6.2 CABLE LOCK
If the installation requires a tethered cable solution, the
permanent cable lock feature can be enabled. Move
the righter dip switch underneath the rotary switches
downwards to enable the permanent cable lock feature.
Plug in the charge cable before turning on the power. As
soon as the power of the charge point is turned on, the
cable will be permanently locked. The only way to then
unlock the cable is to turn off the power of the charge
point. When the dip switch is in the upward position, the
lock will only be operative during charge sessions.
6. LOCAL CONFIGURATION
6.3 LOAD SHEDDING SETTING
Enable Load Shedding if the CT for 7,4 kW charge
point or Load Shedding module for 11 kW charge point
is installed. Use table 1.2 to determine your desired
position of the right rotary switch, as indicated in the
’3.4.3 Overview Installing Accessories’ section. Select
the maximum allowed Load Shedding current for the
installed circuit. This is the maximum current of the grid
connection.
Rotary Position Load Shedding current
0
Load Shedding disabled
1
16 A
2
20 A
3
25 A
4
32 A
5
35 A
6
40 A
7
50 A
8
63 A
9
70 A
A
80 A
B
90 A (7,4 kW model only)
C or greater
100 A (7,4 kW model only)
Table 1.2: Load Shedding current