Adjusting the alarm output volt low/high setting

See diagram with 

Section 2.6.2

. - Rectifier Fail/AC Fail. 

The High Volts and Low Volts Alarm Thresholds can be adjusted to suit the application. This adjustment requires a 

variable voltage power supply (that has a maximum voltage exceeding the over-voltage value to be set). 

Connect the variable voltage power supply across the load connections of the SPS (ensure that +v output of the 

variable supply is connected to the +v load connection). Disconnect the Temperature Compensation Probe. 

Connect an accurate voltmeter across the output. Turn AC and adjust the variable voltage power supply up until 

the alarm activates. Adjust the ‘Alarm Output High’ trimpot to adjust the alarm limits. Use the same procedure to 

adjust the ‘Alarm Output Low ‘ limits. 

Optional Accessories

Rackmount Kit: 

Model RM-SPS

DIN-Rail Kit: 

Contact Factory

Warranty and Factory Contact Information

Newmar warrants that Site Power System be free from defects in material and workmanship for two years from 

date of purchase. If a problem with your SPS, or if you have any questions about the installation and proper 

operation of the unit, please contact NEWMAR’s Technical Services Department:

 

Phone: 714-751-0488 - From the hours of 7:30 a.m. to 5:00 p.m. weekdays, P.S.T.

Fax: 714-957-1621 

E-mail: [email protected]
 

13

Содержание SPS 12-20

Страница 1: ...2 Troubleshooting 10 1 9 Input Over Voltage Shut Down 4 3 3 Fuses 10 1 10 Input Inrush Current Limiter 4 4 Adjustments 10 1 11 Over Temperature Shutdown 4 4 1 Standard Settings 11 1 12 Reverse Polari...

Страница 2: ...e the present state of the rectifier and diagnose faults AC On This LED glows green to indicate that AC power is connected to the unit and that the primary stages of the rectifier are operating Shutdo...

Страница 3: ...ches the battery ve supply the v is common with the battery Do not connect the Battery and Load v together The LVD voltage and the LVD Hysterisis voltage are preset in the factory but may be adjusted...

Страница 4: ...if they fail 1 13 Parallel Rectifier Operation The SPS may be connected in parallel to source more current or to provide a degree of redundancy The rectifiers should have the load share signal connect...

Страница 5: ...ethal even after the input supply has been removed The rectifier contains components at High Temperatures that may burn if touched 2 2 Positioning of SPS A great deal of care should be taken with posi...

Страница 6: ...t outlet be used so the rectifier will not be accidentally unplugged from the supply When hard wiring AC input the IEC AC cord provided should be wired as follows BLK WHT GRN 120 VAC L N Safety Ground...

Страница 7: ...w an internal protection fuse requiring the SPS to be returned for servicing Do not connect the Temperature Compensation Probe to the Site Power System until commissioning see Section 2 7 Start Up 2 5...

Страница 8: ...fier Fail alarm Rectifier Off Normal and the Low Volts alarms will also activate Note that the AC Fail Relay has its own Common connector but all the other alarm outputs share a Common contact 2 6 2 R...

Страница 9: ...y connections and then plug them into the SPS Re connect the mains and the Float Boost LED should glow first yellow then after about 10 seconds either green or yellow depending on the charge of the ba...

Страница 10: ...e current drawn by the battery from the SPS is as expected Check that the battery takes the charge Connect the DC load to the SPS with AC off and disconnect the battery Turn AC on and check that the c...

Страница 11: ...m back of unit with AC input socket on left 4 2 Adjust Float Voltage Connect a variable load set to minimum load to the battery connections of the rectifier Disconnect the Temperature Compensation Pro...

Страница 12: ...ction Disconnect the Temperature Compensation Probe Connect an accurate voltmeter across the output Turn the mains on to the rectifier and adjust the variable voltage power supply up until the unit go...

Страница 13: ...ature Compensation Probe Connect an accurate voltmeter across the output Turn AC and adjust the variable voltage power supply up until the alarm activates Adjust the Alarm Output High trimpot to adjus...

Страница 14: ...P O Box 1306 Newport Beach California 92663 Phone 714 751 0488 Fax 714 957 1621 E Mail techservice newmarpower com 7 Dimensional Drawings 14...

Отзывы: