background image

 

 

11.0 LOW VOLTAGE DISCONNECT 
 

The LVD function operates simply: 
 

o

  When the battery voltage falls to 11.9 (23.8) Volts, the load is disconnected.  This value of voltage 

is very conservative, but it is also based on the fact that typical applications have large batteries 
and light loads… loads in the area of C/100 tend to be typical.  Popular thought suggests that a 
lower value of voltage could be used… perhaps 11.5 Volts.  This arises from published data 
based on testing from more heavily loaded batteries… C/20.  In the case of a sealed lead-acid 
battery, a lightly loaded battery at 11.8 Volts is truly dead… 0% SOC.  So… changes in LVD set 
point should be made very cautiously.  The purpose of the LVD is prevent battery damage.  The 
temptation on the part of designers and users, to avoid battery capacity or extend hold-up time, is 
to lower the set-point to a value that defeats its purpose.  Obviously, this is not advisable. 

 

o

  When the battery voltage rises to 13.1 (26.2) Volts, the load is reconnected.  This value of voltage 

ensures that load cycling or oscillation will not occur once an LVD has been triggered.  This also 
ensures that the battery is given the full output of the DC-UPS to recharge before resuming 
supply to the load.  A value of 13.1 Volts corresponds VERY roughly to a SOC of 50-80%... a 
safe point to resume the load and thereby divert some available charge current to the load. 

 

 

o

  The logic employs filtering so that transients lasting less than a second or so are ignored.  This is 

a simple RC filter, so the magnitude of the transient affects the time period.  This avoids 
“nuisance tripping” of the disconnect. 

 

 

Both of the LVD set-points are temperature compensation in the same way as the charge voltage.  
Because the “float charge” voltage and the “resting voltage“ of a battery do not exactly track, especially at 
low temperatures, the use of the LVD in function in low temperatures, less than 10 C, may cause 
problems.  Specifically, the LVD may disconnect prematurely, leaving usable battery capacity unavailable.  
This is a function of battery chemistry.  For systems operating below 10 C, testing should be performed to 
establish proper implementation.  Again, careful consideration should be paid to the use of the LVD… at 
temperatures of -10 C and below… the LVD function is counter-productive. 

 

Содержание EP 12-10

Страница 1: ...Enclosure Power Supply Models EP 12 10 EP 24 5 Newmar 2911 W Garry Ave Santa Ana CA 92704 Tel 714 751 0488 Fax 714 957 1621 M EP As of April 2008...

Страница 2: ...________ 9 7 1 LOCATION 7 2 MOUNTING 7 3 WIRING 8 0 OPERATION ________________________________________________________ 11 8 1 INITIAL POWER UP 8 2 NORMAL OPERATION 8 3 TROUBLESHOOTING 9 0 MAINTENANCE...

Страница 3: ...rom the system battery provides continuous load power free of sharp transients Wide Operating Temperature of 20 60 C 4 140 F makes it suitable for indoor or outdoor use Input Fused provides protection...

Страница 4: ...Fig 4 2 1 In LINE DOWN mode the power supply delivers no power All load power is supplied by the battery In the LINE DOWN mode the alarm contacts are closed in the N O position Fig 4 2 1 shows the cu...

Страница 5: ...densing Efficiency 75 78 EMC Emissions Radiated Noise 30mHz 1gHz per FCC Class B Conducted Noise 150kHz 30mHz per FCC Class B ALARM CONTACTS DC Current Rating at 30 VDC max 1 0 1 0 Amps AC Current Rat...

Страница 6: ...5 0 4 Shipping Data PARAMETER EP SERIES UNIT MIN TYP MAX WEIGHTS DIMS Weight 3 lbs Shipping Weight 5 lbs Shipping carton size 11 5 x 9 x 5 Inches Shipping volume 0 3 cubic feet Storage temperature 30...

Страница 7: ...p hours 17 Amp hours Max Bat Cap 400 Amp hours 200 Amp hours The correct battery capacity for your system will depend on two factors your load and the length of time you wish to have back up power The...

Страница 8: ...nt Amps To determine the minimum required Battery Capacity 1 Draw a vertical line through the Average Load Current 2 Draw a horizontal line through the desired HOLD UP Time 3 Mark the intersection 4 F...

Страница 9: ...el vertical and the text horizontal As shown in the figures below at least 1 of clearance should be allowed above and below the unit for airflow Do not block the ventilation holes on the top back and...

Страница 10: ...Pay close attention to the battery wiring 1 With mains power and the INPUT switch OFF make connections to the AC input The N terminal should be used for L2 in high voltage AC systems In DC powered sys...

Страница 11: ...f so record the voltage and allow several minutes or hours and check the voltage again If you suspect the system is not functioning properly see the troubleshooting points in Section 8 3 8 3 Troublesh...

Страница 12: ...method can be employed in the field If the battery can supply the load for the desired time it can be deemed good If the battery will not accept charge or cannot deliver the required energy it is wor...

Страница 13: ...he end of Section 8 3 to determine if your battery has sufficient capacity for your application Hold up discharge and recovery times are shown in Graphs 6 5 1 and 6 5 2 in Section 6 5 Lead and other m...

Страница 14: ...scillation will not occur once an LVD has been triggered This also ensures that the battery is given the full output of the DC UPS to recharge before resuming supply to the load A value of 13 1 Volts...

Отзывы: