background image

 

 

 

11

8.0 – OPERATION

 

 
See Figure 8.0.1 on the opposite page for a general 
view of the EP. 
 

8.1 – Initial Power-up

 

 
This procedure provides a quick check to verify the 
system is wired and functioning correctly.  With the 
system wired completely as in Section 7.3: 
 

1.  Turn the INPUT & OUTPUT switches OFF: 

 

The AC indicator should be dark.

 

 

The ALARM indicator should be lit.

 

 

The LOAD indicator should be dark.

 

 

2.  Turn the OUTPUT switch ON: 

 

The AC indicator should be dark.

 

 

The ALARM indictor should be lit.

 

 

The LOAD indicator should be lit

 

 

3.  Turn the INPUT switch ON: 

 

The AC indicator should be lit. 

 

The ALARM indicator should be dark. 

 

The LOAD indicator should be lit.

 

 

8.2 – Normal Operation

 

 
In normal operation, LINE-UP mode, both the AC 
and LOAD indicators should be lit and the ALARM 
indicator should be dark.  The EP is supplying 
energy to charge the battery and power the load.  
The battery voltage should either be: at the 
maximum charging voltage, about 13.8 Volts for a 
12 Volt system, 27.6 Volts for 24 Volt system; or 
rising slowly to these levels.  These voltages vary 
with temperature, lower at high temperatures, higher 
at low temperatures. 
 
In back-up operation, LINE-DOWN mode, the AC 
indicator should be dark and both the ALARM and 
LOAD indicators should be lit.  The battery is 
supplying the energy to the load.  The battery 
voltage should be falling slowly. 
 
In either mode, you may monitor the battery voltage 
to check the charging function.  Generally, a rising 
voltage indicates a charging battery while a falling 
voltage indicates a discharging battery.  If the 
system has a large battery capacity, these changes 
may occur too slowly to observe.  If so, record the 
voltage and allow several minutes or hours and 
check the voltage again. 
 
If you suspect the system is not functioning properly, 
see the troubleshooting points in Section 8.3. 

8.3 – Troubleshooting

 

 
The following is a list of problems you may 
experience and the most likely remedy:  
 

The INPUT switch trips and will not reset: 

 

Check the incoming voltage.  The voltage 
across terminals L and N should less than 
265 VAC or 370 VDC.  Excessive input 
voltage will damage the DC-UPS.

 

 
The AC indicator fails to light with the INPUT 
switch ON: 

 

Check the incoming voltage.  The voltage 
across terminals L and N should be at least 
85 VAC or 110 VDC. 

 

Check for a shorted battery or battery wiring.  
Examine the battery wiring, if good remove 
the positive connection at the battery.  If the 
AC indicator lights, the battery is defective. 

 

The ALARM indicator fails to light with the INPUT 
switch OFF: 

 

Check the battery wiring for shorts. 

 

Check the battery for proper voltage at least 
11.5 Volts for a 12 Volt system and 23 Volts 
for a 24 Volt system.  If the battery voltage is 
less than this; the battery is probably 
defective or worn out. 

 

Check the fuse. 

 

The battery fails to charge while the AC indicator 
is lit: 

 

Check the fuse. 

 

Check the battery wiring. 

 

Check the battery; the battery may be 
defective or worn out. 

 

The LOAD indicator fails to light with the 
OUTPUT switch ON: 

 

Check the battery for low voltage.

 

 

Check the fuse.

 

 

The load fails to operate properly: 

 

Check the polarity of the load connections. 

 

Check the voltage at the load. 

 

Determine if the load requires a regulated 12 
or 24 volt output.  If so, a DC/DC converter 
should be used at the load output.  

 

The load equipment may be faulty. 

 
 

The EP is generating heat: 

 

This heat is normal.  The EP will generate 
more heat, as much as 30 Watts, after 
power is restored due to heavy battery 
charging. 

 

Содержание EP 12-10

Страница 1: ...Enclosure Power Supply Models EP 12 10 EP 24 5 Newmar 2911 W Garry Ave Santa Ana CA 92704 Tel 714 751 0488 Fax 714 957 1621 M EP As of April 2008...

Страница 2: ...________ 9 7 1 LOCATION 7 2 MOUNTING 7 3 WIRING 8 0 OPERATION ________________________________________________________ 11 8 1 INITIAL POWER UP 8 2 NORMAL OPERATION 8 3 TROUBLESHOOTING 9 0 MAINTENANCE...

Страница 3: ...rom the system battery provides continuous load power free of sharp transients Wide Operating Temperature of 20 60 C 4 140 F makes it suitable for indoor or outdoor use Input Fused provides protection...

Страница 4: ...Fig 4 2 1 In LINE DOWN mode the power supply delivers no power All load power is supplied by the battery In the LINE DOWN mode the alarm contacts are closed in the N O position Fig 4 2 1 shows the cu...

Страница 5: ...densing Efficiency 75 78 EMC Emissions Radiated Noise 30mHz 1gHz per FCC Class B Conducted Noise 150kHz 30mHz per FCC Class B ALARM CONTACTS DC Current Rating at 30 VDC max 1 0 1 0 Amps AC Current Rat...

Страница 6: ...5 0 4 Shipping Data PARAMETER EP SERIES UNIT MIN TYP MAX WEIGHTS DIMS Weight 3 lbs Shipping Weight 5 lbs Shipping carton size 11 5 x 9 x 5 Inches Shipping volume 0 3 cubic feet Storage temperature 30...

Страница 7: ...p hours 17 Amp hours Max Bat Cap 400 Amp hours 200 Amp hours The correct battery capacity for your system will depend on two factors your load and the length of time you wish to have back up power The...

Страница 8: ...nt Amps To determine the minimum required Battery Capacity 1 Draw a vertical line through the Average Load Current 2 Draw a horizontal line through the desired HOLD UP Time 3 Mark the intersection 4 F...

Страница 9: ...el vertical and the text horizontal As shown in the figures below at least 1 of clearance should be allowed above and below the unit for airflow Do not block the ventilation holes on the top back and...

Страница 10: ...Pay close attention to the battery wiring 1 With mains power and the INPUT switch OFF make connections to the AC input The N terminal should be used for L2 in high voltage AC systems In DC powered sys...

Страница 11: ...f so record the voltage and allow several minutes or hours and check the voltage again If you suspect the system is not functioning properly see the troubleshooting points in Section 8 3 8 3 Troublesh...

Страница 12: ...method can be employed in the field If the battery can supply the load for the desired time it can be deemed good If the battery will not accept charge or cannot deliver the required energy it is wor...

Страница 13: ...he end of Section 8 3 to determine if your battery has sufficient capacity for your application Hold up discharge and recovery times are shown in Graphs 6 5 1 and 6 5 2 in Section 6 5 Lead and other m...

Страница 14: ...scillation will not occur once an LVD has been triggered This also ensures that the battery is given the full output of the DC UPS to recharge before resuming supply to the load A value of 13 1 Volts...

Отзывы: