on a table top. The handle should move to mid-trip position. Plug 
breaker into DST and verify alarm contact closure on rear of panel 
connector.

VII) INSTALLATION OPTION - Single 900 Amp Bus 

(For model DST-20A only)

If the installation requires, the 450 amp A and B input buses may 
be paralleled to constitute a single 900 amp bus. This may be 
accomplished by:

Running separate 450 amp cables to each of the buses from a 
single power source or power source tie point, or

Running a single 900 amp cable to the A bus and a second 450 
amp cable from the A bus to the B bus (or vice versa).

Refer to the Typical Wiring Diagrams on page 9. See Single Bus 
Installation.

Note: 

The maximum total breaker current rating for positions 1-10 

(BUS A) and positions 11-20 (BUS B) remains at 450 amps each, even 
when the two buses are wired in parallel.

VIII) SPECIFICATIONS

Electrical:
Nominal Input/Output:

 

48, 24 or 12 VDC; positive or negative ground

Total Circuit Capacity:

DST-20A: 20 breakers
DST-10: 10 breakers

Total Current Capacity:

DST-20A: 900 amps (dual 450 amp buses)
DST-10: 450 amps (one 450 amp bus)

Maximum Circuits per Bus:

 10

Environmental:
Temperature Rating:

 Up to 50° C ambient

Alarm/Indicator:

Tripped Breaker Contacts via 

Rear Panel Connector

; Normally 

Open (N.O.) configuration.

Note:

 

Separate contacts are provided for each bus on model DST-20A. A 

and B status contact wiring cannot be paralleled in applications where 
the buses are at different voltages or ground reference.

Maximum power through the alarm contacts:

1 amp @ 125 VAC
5 amps @ 30 VDC

Mechanical:
Bus Bars:

 Nickel-plated copper; accept single or double hole lugs 

Front Panel:

 Anodized aluminum

Cover and Rear Panel:

 Vinyl-laminated aluminum 

Dimensions:

 3.5" H x 17" W* x 11.75" D; Occupies 2 RU

*19" and 23" rack mounting brackets provided

Weight (without breakers):

DST-20A: 12 lbs.        DST-10: 9 lbs.

Compliances
UL Listed:

 Listing # 31ZT

UL 1801 First Edition:

 Subject Standard for Power Distribution Center 

for Telecommunications Equipment 

C22.2 No. 225-M90:

 Canadian Standards for Telecommunication 

Equipment Carries the CE Mark

Warranty:

 Two Years

IX) CIRCUIT BREAKER SPECIFICATIONS AND ORDERING GUIDE

Current Ratings: See list below (breaker value stamped beside 
toggle)

Voltage Rating:

 80 VDC max.

Type:

 Magnetic-Hydraulic Plug-in with Auxiliary Contacts 

(Normally Open) and Mid-Trip Function

UL Listed Telecom Breaker
CSA Certified
10,000 Amp Interrupt Capacity

To order additional or replacement breakers for the DST refer to the 
following NEWMAR model or Carlingswitch part numbers:

  Rating 

NEWMAR Model

  5 amp 

PBA-5 

  6 amp 

PBA-6 

  10 amp 

PBA-10 

  15 amp 

PBA-15

  20 amp 

PBA-20 

  25 amp 

PBA-25 

  30 amp 

PBA-30 

  40 amp 

PBA-40 

  50 amp 

PBA-50

  63 amp 

PBA-63 

  75 amp 

PBA-75 

  100 amp 

PBA-100 

Note:

 

Other circuit breaker values are available on a special order 

basis. Typical lead time is 10 weeks.

X) DST ACCESSORIES

Ground Bus Bar Assembly

* 800 amps: Model BBA-800

Rear Terminal Cover Assembly

* Specify Model RC-DST

Содержание DST-20A

Страница 1: ...EL INSTALLATION 3 A Panel Mounting B Input Wiring C Output Load Wiring V CIRCUIT BREAKER AND SUMMARY ALARM INSTALLATION 3 A Breaker Installation B Breaker Removal C Remote Summary Alarm Wiring VI CIRC...

Страница 2: ...s Warranty period for the panel is two years parts and labor For questions or comments on Newmar Distribution Panels please call 800 854 3006 or e mail sales newmarpower com II IMPORTANT SAFETY INFORM...

Страница 3: ...A ten are provided with model DST 10 Use of any of the outputs requires installation of a plug in breaker at that position Outputs 1 10 are fed by BUS A only outputs 11 20 are fed by BUS B only unless...

Страница 4: ...g For version 2 alarm harness plug the connector end of the harness into the keyed connector on the rear of the DST which is labeled BREAKER STATUS The pigtail end can be wired to an unused STATUS CON...

Страница 5: ...s are provided for each bus on model DST 20A A and B status contact wiring cannot be paralleled in applications where the buses are at different voltages or ground reference Maximum power through the...

Страница 6: ...INCLUDED RETURN HOT GROUND RETURN GROUND HOT TO BUS B LOAD CHASSIS GROUND BUS B HOT SOURCE BUS A HOT SOURCE DST 20A SHOWN AS VIEWED FROM WIRING SIDE SPLIT BUS INSTALLATION MODEL DST 20A ONLY UP TO 10...

Страница 7: ...marpower com PoweringTheNetwork com XII OUTLINE AND MOUNTING DRAWING 82 1 00 312 X 500 SLOT 312 63 TYP 1 4 20 PRESS IN NUT TYP ROTATED VIEW 1 1 1 1 1 1 14 10 56 8 56 2X 6 00 3 47 17 00 8X 25 2X 3 00 2...

Отзывы: