I) OVERVIEW

The DST is a high density Rackmount Secondary Distribution Panel 
designed to accommodate virtually any communication site power 
distribution requirement.

The panel accommodates up to 10 or 20 circuit breakers, 
depending on model, within a compact housing occupying only 2 
RU of rack space. The plug-in breakers only require front access for 
quick, easy installation during initial system configuration, as well 
as future system expansion.

Model DST-20A

 features dual isolated A and B buses, each rated 

at 450 amps, which accept up to 10 breakers each and enable 
redundant power, dual voltage and/or dual ground reference 
configurations. The A and B inputs can also be paralleled to make a 
single 900 amp bus (see INSTALLATION OPTION section). Model DST-
10 has a single 450 amp bus which accepts up to 10 breakers.

The plug-in circuit breakers feature compression power contacts 
which insert securely into sockets recessed in the panel. Breaker 
alarm contacts which are part of the plug-in assembly feed an 
output connector at the rear of the panel for optional remote tripped 
breaker alarm/indication. A “mid-trip” function of the breaker 
moves the toggle to a 90 degree position when an over-current 
situation is encountered, providing quick visual identification of 
a failed circuit. It distinguishes between an over-current trip and 
intentional shut-off, allowing the technician to turn off individual 
loads without unnecessarily activating the alarm.

Input/output wiring is via rear access bus bars that accept single 
or double hole lugs. There is no internal power wiring or terminals, 
eliminating multiple points of failure. Input/output buses are 
secured to the load breaker sockets via nickel-plated copper bus 
bars.

Mounting brackets are provided to adapt the panel for 19" or 
23" racks. Snap-in hole covers are provided for unused breaker 
ports and a clear protective toggle guard is provided to prevent 
accidental breaker switching and for convenient placement of 
identification labels.

The panel is shipped standard without breakers. These are sold 
separately and are plugged into the unit during installation. Refer 
to the Circuit breaker Specifications and Ordering Guide section at 
the end of this manual for available values.

Warranty period for the panel is two years, parts and labor.

For questions or comments on Newmar Distribution Panels, 
please call 800-854-3006 or e-mail sales@newmarpower.
com.

II)  IMPORTANT SAFETY INFORMATION

1) This equipment shall be installed in a Restricted 
Access Location in accordance with Articles 
110-16, 110-17 and 110-18 of the National 
Electrical Code, ANSI/NFPA 70.

2) Never restrict air flow through the vents of 
the DST panel.

3) Reliable Earthing (Grounding) of rackmounted equipment shall 
be maintained.

4) The power connections shall be made with copper conductors. 
Refer to NEC for proper dc wire gauge.

5) For use with Carling Technologies, C-Series circuit breakers, 
special purpose, single pole, rated 80V dc, 5-100 amps, Airpax 
LML series, or Circuit Breaker Industries D frame series orientated 
so that the ON position is in the UP position. (Suitable breakers are 
available from NEWMAR.)

III) MATERIALS  LIST

Prior to installation, carefully go over the following list to verify 
all necessary items have been provided. Note: Some items are 
provided in the hardware accessory package; others are taped to 
the main DST assembly or installed. For any missing items please 
contact the factory at US Headquarters. (Contact information may 
be found on the bottom of any page of this manual.)

Hardware/parts provided with both models

(1 ea.) Rackmount Distribution Panel Assembly
(2 ea.) Mounting Brackets for 19" rack (stamped 13917)*
(6 ea.) 6-32 X 5/16" Phillips Screws (for mounting bracket installation)
(1 ea.) Molex-to-Molex Connector Assembly (four wires installed)
(19 ea./DST-20A, 9 ea./DST-10) Open Circuit Position Covers (factory 
installed)
(1 ea.) Clear Protective Toggle Guard
(2 ea.) Toggle Guard Mounting Screws, 6-32 x 1 3/8"
(2 ea.) Toggle Guard Nylon Stand-Offs
(2 ea.) Flat Washers, # 6 (for toggle guard assembly)
(8 ea.) Lock Washers, # 6 (2 ea. for toggle guard assembly; 6 ea. for 
mounting bracket installation)
(1 ea.) Circuit Identification Label Set (25 ea., blank)
(1 ea.) Circuit Breaker Extraction Tool
(2 ea.) Circuit Breaker Extraction Screws, 6-32 x 3/8"
(1 ea.) Installation/Operation Manual

Additional hardware provided with model DST-20A

(4 ea.) Bolts, Hex-Head, 1/4" - 20 x 1"
(4 ea.) Flat Washers, 1/4"
(40 ea.) Bolts, Hex-Head, 1/4" - 20 x 3/4"
(4 ea.) Nuts, Hex, 1/4" - 20
(44 ea.) Lock Washers, 1/4"

Additional hardware provided with model DST-10

(2 ea.) Bolts, Hex-Head, 1/4" - 20 x 1"
(2 ea.) Flat Washers, 1/4"
(20 ea.) Bolts, Hex-Head, 1/4" - 20 x 3/4"
(2 ea.) Nuts, Hex, 1/4" - 20
(22 ea.) Lock Washers, 1/4"
(1 ea.) RC-DST, Rear Terminal Cover Assembly (See RC-DST  

 

            instructions attached to cover for mounting) 

* 23" Mounting Brackets (Newmar Part # 699-3918-0) are not 
supplied with DST, contact factory

Содержание DST-20A

Страница 1: ...EL INSTALLATION 3 A Panel Mounting B Input Wiring C Output Load Wiring V CIRCUIT BREAKER AND SUMMARY ALARM INSTALLATION 3 A Breaker Installation B Breaker Removal C Remote Summary Alarm Wiring VI CIRC...

Страница 2: ...s Warranty period for the panel is two years parts and labor For questions or comments on Newmar Distribution Panels please call 800 854 3006 or e mail sales newmarpower com II IMPORTANT SAFETY INFORM...

Страница 3: ...A ten are provided with model DST 10 Use of any of the outputs requires installation of a plug in breaker at that position Outputs 1 10 are fed by BUS A only outputs 11 20 are fed by BUS B only unless...

Страница 4: ...g For version 2 alarm harness plug the connector end of the harness into the keyed connector on the rear of the DST which is labeled BREAKER STATUS The pigtail end can be wired to an unused STATUS CON...

Страница 5: ...s are provided for each bus on model DST 20A A and B status contact wiring cannot be paralleled in applications where the buses are at different voltages or ground reference Maximum power through the...

Страница 6: ...INCLUDED RETURN HOT GROUND RETURN GROUND HOT TO BUS B LOAD CHASSIS GROUND BUS B HOT SOURCE BUS A HOT SOURCE DST 20A SHOWN AS VIEWED FROM WIRING SIDE SPLIT BUS INSTALLATION MODEL DST 20A ONLY UP TO 10...

Страница 7: ...marpower com PoweringTheNetwork com XII OUTLINE AND MOUNTING DRAWING 82 1 00 312 X 500 SLOT 312 63 TYP 1 4 20 PRESS IN NUT TYP ROTATED VIEW 1 1 1 1 1 1 14 10 56 8 56 2X 6 00 3 47 17 00 8X 25 2X 3 00 2...

Отзывы: