background image

OPERATING INSTRUCTIONS FOR ALL NEWBURN WOOD FIRED HEATING 
UNITS.

FUEL
The NEWBURN is suitable for burning split wood and logs only.    Do not use other fossil fuels,
wastepaper, briquettes etc.  Seasoned, dry firewood should only be used.  The fuel quality is directly
linked with the economy of the NEWBURN system and its reliability.  Poor fuel will jeopardise the life
of the firebox and fire bricks.  Do not use green wood as it will cause excessive build up of creosote.

LIGHTING THE FIRE
If the NEWBURN has been used previously, clean out any excessive ash build up before re-lighting.
Ensure the power supply is on and turn the room thermostat up above room temperature and the
combustion air damper will open.  Place several pieces of crumpled paper in the bottom of the firebox
and cover with dry kindling and a few pieces of split wood.  Do not use flammable liquid to start the
fire.  Light the fire, then close the firebox door.  Ensure the room thermostat is turned up to set point
(21 degrees)

RE-FUELLING
Crack open the firebox door for a few seconds before slowly opening fully.
Place wood in the firebox with care to avoid damage to firebrick lining.   Space pieces of wood to
allow   air   circulation   between   them.     Close   the   firebox   door   tightly.     DO   NOT   OVERLOAD   THE
FIREBOX.  The wood should not be placed higher than halfway up the fire door opening.  Care taken
in loading will extend the   life of the firebrick lining which must be replaced if showing any signs of
deterioration.

COMBUSTION AIR DAMPER OPERATION
The  Combustion  Air  damper  is  the  heart  of  the  NEWBURN as  it  controls  the  amount  of  air  for
combustion and therefore fire size.  The damper is  controlled by the room thermostat to open when
the room temperature falls below what the thermostat has been set and to close when the desired
temperature is reached.     A High Limit thermostat to override the room thermostat and close the
damper if the heat exchanger starts to overheat is also incorporated.   The room thermostat will
operate normally again once the heat exchanger has cooled down.

6

Содержание Newburn

Страница 1: ...WOODFIRED CENTRAL HEATING FURNACE INSTALLATION and OPERATION MANUAL METALFAB 125 WILSON ST BURNIE TASMANIA Telephone 03 6431 4766 Facsimile 03 6431 6811 Email sales newmansplumbing com au ...

Страница 2: ...imum 50mm air space around the sides back and above the unit from combustible surfaces Also the unit should be installed on a level concrete slab of not less than 50 mm thickness FLUE INSTALLATIONS The flue must be 150 mm diameter of 0 6 mm stainless steel and all joints be sealed and lapped so that the lower section of flue is entered into the top section of the adjoining piece This will stop any...

Страница 3: ...hanger The ductwork must be designed to recognised standards and installed by competent tradesperson with experience in this field to ensure correct operation RETURN AIR DUCT For maximum economy it is recommended that a minimum 350 mm diameter return air duct be connected to deliver room air back to the furnace for reheating The return air duct should be insulated for noise absorption and thermal ...

Страница 4: ...larly that the combustion damper is working correctly and is unobstructed Check that the firebox door gasket is intact and sealing correctly Check the Return Air filter is clean or replace Clean out the ash regularly to prevent excessive build up and obstruction of combustion air intake Check the condition of the firebricks and baffle plates Inspect and clean your flue at least annually 4 ...

Страница 5: ...5 ...

Страница 6: ...or Ensure the room thermostat is turned up to set point 21 degrees RE FUELLING Crack open the firebox door for a few seconds before slowly opening fully Place wood in the firebox with care to avoid damage to firebrick lining Space pieces of wood to allow air circulation between them Close the firebox door tightly DO NOT OVERLOAD THE FIREBOX The wood should not be placed higher than halfway up the ...

Страница 7: ...the switch on this controller is in the Auto out position In manual mode the fan will run continuously which is undesirable OVERNIGHT BURNING For successful overnight burning it is essential that there is a moderate fire already burning before loading the firebox with DRY wood Turn the room thermostat back to its lowest setting The furnace will now burn on low fire for approximately 6 to 8 hours I...

Страница 8: ...n is critical to avoid overheating and damage to the firebox Ensure that the combustion air damper door is closed and un obstructed Do not open the fire box door in this situation If the door is opened the fire will build up and overheating will occur It is recommended that if the supply air fan fails turn the wall thermostat down to ensure that the combustion air damper remains closed off and the...

Страница 9: ... to the other side of the firebox and then remove the remaining ash This ash will be very hot Handle and dispose of it carefully 4 Reposition the hot coals and unburned wood centrally and reset the fire with kindling and more wood Close the firebox door Reset thermostat to required temperature 5 Periodically allow the heater to go out in order to inspect the firebricks Cleaning should be done on a...

Страница 10: ...10 ...

Страница 11: ...11 ...

Страница 12: ...12 ...

Страница 13: ...r repairs to damage caused by burning coal or briquettes neglect abuse or accident No responsibility will be accepted for damage caused directly or indirectly by incorrect electrical wiring by incorrect installation or operation of the Heater The guarantee will not be recognised unless the form below is filled in and returned to the manufacturer WARRANTY REGISTRATION NEWBURN WOOD FIRED CENTRAL FUR...

Отзывы: