2
key“
”adds 0.1
°
C, the key“
”minuses 0.1
°
C, press and hold it over 0.5 seconds can add or minus
rapidly
)
. After setting, press “set” again, then exit the state of parameter setting. (The setting temp range is
limited by the parameters F13 and F14, please refer to the advanced operation). Pressing the key “M” in the
setting process means cancel and exit, but the setting value will not be saved.
*
How to defrost manually?
When in the state of displaying current temperature, press the key “
” and hold it at least 5 seconds,
then the controller enters the defrosting state. In defrosting state, press the key “
” and hold it at least 5
seconds again, this can finish the defrosting forcibly.
*
How to read the temperature of the evaporator sensor?
When displaying current temperature, press “
” key, Controller will display defrosting temperature.
Loose “
” key, then return to current temperature. Notice that if you press the key and hold it for 5
seconds, the controller will enter or exit the defrosting state forcibly.
*
How to refrigerate (or heat) forcibly?
When displaying current temperature, the temperature is between “setting temperature
-
temperature
difference” and “setting temperature
+
temperature difference”, the system may or not refrigerate, here you
press the key “
” and hold it for 5 seconds, the controller will enter the refrigeration state forcibly when in
the refrigeration state, and stop refrigeration when the temperature is below “setting temperature
-
temperature difference”; the controller will enter the heat state forcibly when in the heat state, and stop
heating when the temperature is above “setting temperature
+
temperature difference”.
9
Advanced Operation
Press the key “M” and hold it for 5 seconds, and if you have set the password, the LED display the
“PAS” to hint you to enter the password, you can use the key “
” and “
” to enter the password, if the
password is correct, the LED will display the parameter code, use “
” or “
” to select the parameter
code
,
Pressing the “set” key can make it to show the value of the parameter after select the parameter, here
you use “
” or “
” to set the parameter(pressing the key and not release can add or minus rapidly), then
press the “set” key to return to the state of showing parameter code after finishing setting. Pressing the key
“M” can exit the parameter setting state when display the parameter code, pressing the key “M” means
cancel when in the process of setting parameter, and the parameter will not be changed.
Internal parameter code is showing below:
Sort Code Parameter Name
Range
Factory
setting
Unit Remark
F11
Setting temperature
F14 – F13
0
℃
/
℉
The setting range is limited by
F13 and F14
F12
Temperature difference
0.1 – 20
1.0
℃
/
℉
Control the temperature
difference, please refer to the
temperature controlling
F13
Max setting temperature
-58 - 302
302
℃
/
℉
F14
Min setting temperature
-58 – 302
-58
℃
/
℉
Notice: the controller will
follow the rule of
F14<F11<F13 forcibly, if you
find out that one parameter can
not be adjusted, it is because
the parameter is limited by
other parameters, you must
first adjust other parameters
F18
Evaporator sensor adjustment
-20 – 20
0.0
℃
/
℉
Adjust the evaporator sensor
bias
Temperature
F19
Temp sensor adjustment
-20 – 20
0.0
℃
/
℉
Adjust the temperature sensor
bias
F21
Compressor delay time
0 -- 10
3
min
Compressor
F29
Compressor controlling mode
(temp controlling mode)
COOL / HEAT
COOL
-
COOL: refrigeration mode
HEAT: Heat mode
F31
Defrost alternation time
(Enable when F35=1 and 2)
0.1 – 99.9
12
hour
F32
Defrost end temperature
0.0 – 100
15.0
℃
/
℉
F33
Defrost time
1 -- 99
15
min
F34
Dripping time
0 -- 99
5
min
Defrosting
F35
Defrost start mode
OFF
1 -- 2
1 -
OFF: defrost is off
1: time alternation start
2:time alternation start, the
alternation is compressor
accumulative running time