This section is used for residential installation or mobile home installation. 

 

UNCONFINED SPACE: 

 

 

An unconfined space has a minimum air volume of 50 cubic feet for each 1,000 BTU/Hr (4.8m

3

 per 

Kw) input rating of all appliances in the space (Cubic feet equals Length x Width x Height of space).  
Include adjoining rooms only if there are doorless passageways or ventilation grills between the 
rooms. 

 

CONFINED SPACE: 

 

“The National Fuel Gas Code defines a confined space as a space whose volume is less than 50 cubic 
feet per 1,000 BTU per hour (4.8m

3

 per KW) of the aggregate input rating of all appliances installed 

in that space.   

“WARNING:  If the area in which the heater may be operated is smaller than that defined as an 
unconfined space, provide adequate combustion and ventilation air by one of the methods 
described in the National Fuel Gas Code, ANSI Z223.1,  1992, Section 5.3” 

DETERMINING FRESH-AIR FLOW FOR 

HEATER LOCATION 

 
DETERMINE IF YOU HAVE A CONFINED OR UNCONFINED SPACE 
 

Use this worksheet to determine if you have a confined or unconfined space. 
 

SPACE:

  Include the room in which you will install heater plus adjoining rooms with doorless 

passageways or ventilation grills between the rooms. 
 

1.  Determine the volume of the space (length x width x height). 
     Length x Width x Height= ________ cu.ft. (volume of space) 
     

EXAMPLE:

 

20 ft. (length) x 16 ft. (width) x 8 ft. (ceiling height) = 

 

 

        2560 cu. ft. (volume of space) 

 
If additional ventilation to adjoining room is supplied with grills or openings, add the volume of these 
rooms to the total volume of space. 
 

2.   Divide the space volume by 50 cubic feet to determine the maximum BTU/Hr the space 
     can support. 
    ________ 

(volume of space)  / 50 cu. ft = (maximum BTU/Hr the space can support) 

    EXAMPLE:  

2560 cu. ft. (volume of space) / 50 cu. ft. = 51.2 or 

                         51200 (maximum BTU/Hr the space can support.) 
 

NOTICE: Information on provisions for adequate combustion and ventilation air are located in 

the unvented room heater ‘s installation instructions. The unvented room heater’s instructions 

must be followed exactly.

 

PRODUCING ADEQUATE VENTILATION

 

13

Содержание Buck Stove ZCBB

Страница 1: ...RSAL BOX Carefully review the instructions supplied with the decorative type unvented room heater for the minimum fireplace size requirement DO NOT INSTALL AN APPLIANCE IN THIS FIREBOX UNLESS THIS FIR...

Страница 2: ......

Страница 3: ...FF 7 Finishing Your Firebox 8 Mantel Profiles For Zero Clearance 9 Optional Wooden Flush Mount Mantel Front FF 10 Optional Wooden Surround WS 11 Producing Adequate Ventilation 13 Ventilation Air from...

Страница 4: ...2...

Страница 5: ...state or local codes After Market Completion of sale not for purpose of resale from the manufacturer 3 This heater shall not be installed in a confined space or unusually tight construction unless pr...

Страница 6: ...0 for Producing Adequate Ventilation NOTE THIS IS A VENTLESS FIREBOX ENCLOSURE UNIVERSAL FOR GAS FIRED DECORATIVE TYPE UNVENTED ROOM HEATERS IT WILL ACCEPT ANY GAS LOGS UP TO 40 000 BTU S AS LONG AS T...

Страница 7: ...n may be best where space is limited Your Ventless Firebox Enclosure weighs no more than some of your fine furniture If the firebox is located near a load bearing wall additional supports to the found...

Страница 8: ...TORY INSTALLED CANOPY IT MAY NOT BE REPLACED WITH ANY OTHER MANUFACTURER S CANOPY 39 3 8 35 1 2 20 1 4 11 1 4 39 3 8 20 1 2 36 3 16 38 1 8 38 1 8 40 7 8 WARNING NOTCHING OF THE FRAMING AROUND THE STAN...

Страница 9: ...L BUILDING CODES SHOULD BE CONSULTED IN ALL CASES AS TO THE PARTICULAR REQUIREMENTS CONCERNING THE INSTALLATION OF FACTORY BUILT FIREBOXES Select the location for the firebox by taking into considerat...

Страница 10: ...irebox The space between the wall covering and the firebox should be sealed with a heat resistant material such as rock wool insulation or mortar NOTE An L shaped steel lintel must be installed across...

Страница 11: ...NIVERSAL BOX ZERO CLEARANCE CABINET MUST BE FOLLOWED A 3 3 4 3 1 2 4 B CANOPY STANDOFF COMBUSTIBLE MATERIALS ZCBB MANTEL CLEARANCES MANTEL WIDTH MANTEL HEIGHT A inches B inches above firebox opening 6...

Страница 12: ...e page 8 figure 4 2 Ceiling Clearances The ceiling height should not be less than 42 from the top of the firebox opening INSTALLATION INSTRUCTIONS 1 After removing the FF kit from its packaging follow...

Страница 13: ...dium Phillips Screwdriver Step 1 Lay out all components See diagram 1 Step 2 Assemble end panels A B to top front rail C Step 3 Stand end panels and top front rail onto base hearth and fasten down wit...

Страница 14: ...ear of the WS this gives you more area to hold the ZCBB and reduces the risk of scratching the surface of the front area of the base hearth area Flush and center the ZCBB s front in the WS You can att...

Страница 15: ...ERMINE IF YOU HAVE A CONFINED OR UNCONFINED SPACE Use this worksheet to determine if you have a confined or unconfined space SPACE Include the room in which you will install heater plus adjoining room...

Страница 16: ...____BTU Hr actual amount of BTU Hr used Example 51200 BTU Hr maximum the space can support 58000 BTU Hr actual amount of BTU Hr used The space in the above example is a confined space because the actu...

Страница 17: ...and 2 Figure 6 You can also remove door into adjoining room see Option 3 Figure 6 WARNING REWORK WORKSHEET ADDING THE SPACE OF THE ADJOINING UNCONFINED SPACE THE COMBINED SPACES MUST HAVE ENOUGH FRESH...

Страница 18: ...nings one within 12 of the ceiling and one within 12 of the floor Connect these items directly to the outdoors These spaces include attics and crawl spaces Follow the National Fuel Gas Code NFPA 54 AN...

Страница 19: ...Connect the black power cord wire to the 24 jumper wire provided then attach the jumper wire to the middle terminal on the ON OFF switch Next connect the remaining thermostat wire to 1 of the wires co...

Страница 20: ...d be done by a qualified service person This heater should be inspected before use and at least annually by a qualified service technician More frequent cleaning may be required due to excessive lint...

Страница 21: ...ANOPY 7 DOOR KIT PART MAZCBBDOORS PARTS MAY BE OBTAINED THROUGH YOUR LOCAL NBC DEALER IN ABSENCE OF A DEALER PLEASE CONTACT NEW BUCK CORPORATION AT P O BOX 69 8000 HWY 226 SOUTH SPRUCE PINE NC 28777 O...

Страница 22: ...parts that are not in original condition normal wear and tear or parts that fail or become damaged as a result of misuse accidents lack of proper maintenance or defects caused by improper installatio...

Отзывы: