5. Data Report 

 

Data report configuration and sending period are as following: 

 

 

 

 

 

Min Interval 

(Unit:second) 

Max Interval 

(Unit:second) 

Reportable Change 

Current Change

≥ 

Reportable Change 

Current Change

Reportable Change 

Any number between 

1~65535 

Any number between 

1~65535 

Can not be 0. 

Report 

per Min Interval 

Report 

per Max Interval 

The device will immediately send a version packet report along with an uplink packet including water leak status, temperature, 

humidity and battery voltage. The device sends data in the default configuration before any configuration is done. 

 

Default setting: 

MaxTime: 3600s (if there is special customized shipment, the setting will change according to the customer's requirements) 

MinTime: 3600s (by default, the current voltage value is detected every min interval) 

Battery Change: 0x01 (Unit:0.1v, 0.1V) 

Temperature Change: 0x64 (Unit:0.01°, 1°C) 

Humidity Change: 0x64 (Unit:0.01%, 1%) 

 

Water leak detection: 

When R718WAA detects water leakage, it will immediately report a leak status as "1" 

When R718WAA does not detect water leakage, it will immediately report a leak status as "0" 

 

Note:   

The device report interval will be programmed based on the default firmware which may vary. 

The interval between two reports must be the minimum time. 

 

Please refer Netvox 

LoRaWAN Application Command document

 and 

Netvox Lora Command Resolver

 to resolve uplink data. 

http://www.netvox.com.cn:8888/page/index

.

 

Содержание R718WAA

Страница 1: ...ight Netvox Technology Co Ltd This document contains proprietary technical information which is the property of NETVOX Technology It shall be maintained in strict confidence and shall not be disclosed...

Страница 2: ...eport 5 5 1 Example of ReportDataCmd 6 5 2 Example of ConfigureCmd 7 5 3 Example for MinTime MaxTime logic 7 6 Installation 9 7 Information about Battery Passivation 10 7 1 To determine whether a batt...

Страница 3: ...y LoRa is a wireless communication technology dedicated to long distance and low power consumption Compared with other communication methods LoRa spread spectrum modulation method greatly increases to...

Страница 4: ...configured via a third party software platform data can be read and alerts can be set via SMS text and email optional Applicable to third party platforms Actility ThingPark TTN MyDevices Cayenne Impr...

Страница 5: ...Had joined the network not at factory setting Turn on the device to search the previous network to join The green indicator stays on for 5 seconds success The green indicator remains off fail Failed t...

Страница 6: ...0s if there is special customized shipment the setting will change according to the customer s requirements MinTime 3600s by default the current voltage value is detected every min interval Battery Ch...

Страница 7: ...yte 0B Hardware Version V1 1 6th 9th byte 20200520 DateCode 2020 05 20 10th 11th byte 0000 Reserved Uplink 2 01BE012406701A9E010000 Status report 1st byte 01 Version 2nd byte BE DeviceType 0xBE R718WA...

Страница 8: ...02 Reserved 9Bytes Fixed 0x00 ReadConfig ReportRsp 0x82 MinTime 2bytes Unit s MaxTime 2bytes Unit s Battery Change 1byte Unit 0 1v Temperature Change 2byte Unit 0 01 HumidityChange 2byte Unit 0 01 1 C...

Страница 9: ...xTime interval 3 We do not recommend to set the MinTime Interval value too low If the MinTime Interval is too low the device wakes up frequently and the battery will be drained soon 4 Whenever the dev...

Страница 10: ...ater from the sensor the device will restore to the normal state and send the normal status message 2 Remove the 3M release paper as the red part of the above figure on the back of the sensor probe an...

Страница 11: ...orage period is more than one month from the date of battery production all the batteries should be activated If encountering the situation of battery passivation users can activate the battery to eli...

Страница 12: ...elt some plastic parts Do not store the device in places that are too cold Otherwise when the temperature rises to normal temperature moisture will form inside which will destroy the board Do not thro...

Отзывы: