5. Data Report
The device will immediately send a version package report and a report data with temperature and voltage values after the device is powered on.
The device sends data in the default configuration before any configuration is done.
Maximum time: Max Interval
Minimum time: Min Interval (by default, the current voltage value is detected every Min Interval)
Default reportchange:
Battery --- 0x01 (0.1V)
Air temperature default reportchange: 1
℃
Note: The data transmission cycle of the device is subject to the real programming configuration before shipment.
The interval between two reports must be the minimum time
R718AD default Max Interval = 15min, Min Interval = 15min
(if there is special custom shipment, the setting will be changed according to customer requirements)
The data reported by the device can be decoded with the Netvox LoraWAN Application Command document and
http://www.netvox.com.cn:8888/page/index
Data report configuration and sending period are as following:
6. Command Configuration Setting
FPort
:
0x07
Bytes
1
1
Var(Fix =9 Bytes)
CmdID DeviceType
NetvoxPayLoadData
CmdID
– 1 bytes
DeviceType
– 1 byte – Device Type of Device
NetvoxPayLoadData
– var bytes (Max=9bytes)
Report Command Configuration Setting
Min Interval
(Unit:second)
Max Interval
(Unit:second)
Reportable
Change
Current
Change≥
Reportable Change
Current Change
<
Reportable Change
Any number between
1~65535
Any
number
between 1~65535
Can not be 0.
Report
per Min Interval
Report
per Max Interval
Description
Device
CmdID
DeviceTy
pe
NetvoxPayLoadData
ConfigReportRe
q
R718A
D
0x01
0x9C
MinTime(2
bytes
Unit:s)
MaxTime(2by
tes Unit:s)
BatteryChange
(1byte
Unit:0.1v)
TemperatureCh
ange(2byte
Unit:0.01
℃
)
Reserved
(2Bytes,Fixed
0x00)
ConfigReportRs
p
0x81
Status(0x00
_success)
Reserved (8Bytes,Fixed 0x00)
ReadConfigRepo
rtReq
0x02
Reserved (9Bytes,Fixed 0x00)
ReadConfigRepo
rtRsp
0x82
MinTime(2
bytes
Unit:s)
MaxTime(2by
tes Unit:s)
BatteryChange
(1byte
Unit:0.1v)
TemperatureCh
ange(2byte
Unit:0.01
℃
)
Reserved
(2Bytes,Fixed
0x00)