7
Example of Report configuration
FPort
:
0x07
Bytes
1
1
Var(Fix =9 Bytes)
CmdID DeviceType
NetvoxPayLoadData
CmdID
– 1 bytes
DeviceType
– 1 byte – Device Type of Device
NetvoxPayLoadData
– var bytes (Max=9bytes)
(
1
)
Command Configuration:
MinTime = 1min
、
MaxTime = 1min
、
BatteryChange = 0.1v
、
TemperatureChange = 1℃
、
HumidityChange = 1%
Downlink
:
0101003C003C0100640064 003C(H
ex)
= 60(D
ec)
,0064(H
ex)
= 100(D
ec)
Response
:
8101000000000000000000
(
Configuration success
)
8101010000000000000000
(
Configuration failure
)
(
2
)
Read Configuration:
Downlink
:
0201000000000000000000
Response
:
8201003C003C0100640064
(
Current configuration
)
Description
Device
CmdID
Device
Type
NetvoxPayLoadData
Config
ReportReq
R712
0x01
0x01
MinTime
(2bytes Unit:s)
MaxTime
(2bytesUnit:s)
Battery
Change
(1byte
Unit:0.1v)
Temperature
Change
(2byte
Unit:0.01℃)
Humidity
Change
(2byte
Unit:0.01%)
Config
ReportRsp
0x81
Status
(0x00_success)
Reserved
(8Bytes,Fixed 0x00)
ReadConfig
ReportReq
0x02
Reserved
(9Bytes,Fixed 0x00)
ReadConfig
ReportRsp
0x82
MinTime
(2bytes Unit:s)
MaxTime
(2bytes Unit:s)
Battery
Change
(1byte
Unit:0.1v)
Temperature
Change
(2byte
Unit:0.01℃)
Humidity
Change
(2byte
Unit:0.01%)