Example of data configuration: 

FPort

0x07 

Bytes 

Var(Fix =9 Bytes) 

 

CmdID 

DeviceType 

NetvoxPayLoadData 

CmdID

– 1 byte 

DeviceType

– 1 byte – Device Type of Device 

NetvoxPayLoadData

– var bytes (Max=9bytes) 

 

 

(1) Configure device parameters MinTime = 1min, MaxTime = 1min, BatteryChange = 0.1v 

       Downlink: 0151003C003C0100000000 

Description 

Device 

Cmd 

ID 

Devi

ceTy

pe 

NetvoxPayLoadData 

Config 

ReportReq 

R313FC 

0x01 

0x51 

MinTime 

(2bytes Unit:s) 

MaxTime 

(2bytes Unit:s) 

BatteryChange 

(1byte Unit:0.1v) 

Reserved 

(4Bytes,Fixed 0x00) 

Config 

ReportRsp 

0x81 

Status 

(0x00_success) 

Reserved 

(8Bytes,Fixed 0x00) 

ReadConfig 

ReportReq 

0x02 

Reserved 

(9Bytes,Fixed 0x00) 

ReadConfig 

ReportRsp 

0x82 

MinTime 

(2bytes Unit:s) 

MaxTime 

(2bytes Unit:s) 

BatteryChange 

(1byte Unit:0.1v) 

Reserved 

(4Bytes,Fixed 0x00) 

SetR313F 

TypeReq 

0x03 

R313FType (1Byte) 

0x01_R313FA, 

0x02_R313FB, 

0x03_R313FC 

Reserved 

(8Bytes,Fixed 0x00) 

SetR313F 

TypeRsp 

0x83 

Status 

(0x00_success) 

Reserved 

(8Bytes,Fixed 0x00) 

GetR313F 

TypeReq 

0x04 

Reserved 

(9Bytes,Fixed 0x00) 

GetR313F 

TypeRsp 

0x84 

R313FType (1Byte) 

0x01_R313FA, 

0x02_R313FB, 

0x03_R313FC 

Reserved 

(8Bytes,Fixed 0x00) 

SetActive 

ThresholdReq 

0x05 

Threshold 

(2Bytes) 

Deactivetime 

(1Byte,Unit:1s) 

Reserved 

(6Bytes,Fixed 0x00) 

SetActive 

ThresholdRsp 

0x85 

Status 

(0x00_success) 

Reserved 

(8Bytes,Fixed 0x00) 

GetActive 

ThresholdReq 

0x06 

Reserved 

(9Bytes,Fixed 0x00) 

GetActive 

ThresholdRsp 

0x86 

Threshold 

(2Bytes) 

Deactivetime 

(1Byte,Unit:1s) 

Reserved 

(6Bytes,Fixed 0x00) 

Содержание R313FC

Страница 1: ...This document contains proprietary technical information which is the property of NETVOX Technology It shall be maintained in strict confidence and shall not be disclosed to other parties in whole or in part without written permission of NETVOX Technology The specifications are subject to change without prior notice ...

Страница 2: ...1 Table of Content 1 Introduction 2 2 Appearance 3 3 Main Features 3 4 Set up Instruction 4 5 Data Report 5 6 Installation 9 7 Relative Devices 10 8 Important Maintenance Instruction 10 ...

Страница 3: ...ation methods LoRa spread spectrum modulation method greatly increases to expand the communication distance Widely used in long distance low data wireless communications For example automatic meter reading building automation equipment wireless security systems industrial monitoring Main features include small size low power consumption transmission distance anti interference ability and so on LoR...

Страница 4: ...ass A Frequency hopping spread spectrum technology Configuration parameters can be configured through third party software platforms data can be read and alarms can be set via SMS text and email optional Available third party platform Actility ThingPark TTN MyDevices Cayenne Low power consumption and long battery life Indicator Function Key ...

Страница 5: ...oin The green indicator stays on for 5 seconds success The green indicator remains off fail Had joined the network Turn on the device to search the previous network to join The green indicator stays on for 5 seconds success The green indicator remains off fail Fail to join the network when the device is on Suggest to check the device verification information on the gateway or consult your platform...

Страница 6: ...0xFF Threshold Threshold Critical value 9 8 0 0625 The gravitational acceleration at standard atmospheric pressure is 9 8 m s2 The scale factor of the threshold is 62 5 mg R313FC vibration alarm The device detects sudden movement or vibration and the quiescent state changes The device waits for a certain period of time DeactiveTime to enter the quiescent state and calculate the duration sends a re...

Страница 7: ...ved 9Bytes Fixed 0x00 ReadConfig ReportRsp 0x82 MinTime 2bytes Unit s MaxTime 2bytes Unit s BatteryChange 1byte Unit 0 1v Reserved 4Bytes Fixed 0x00 SetR313F TypeReq 0x03 R313FType 1Byte 0x01_R313FA 0x02_R313FB 0x03_R313FC Reserved 8Bytes Fixed 0x00 SetR313F TypeRsp 0x83 Status 0x00_success Reserved 8Bytes Fixed 0x00 GetR313F TypeReq 0x04 Reserved 9Bytes Fixed 0x00 GetR313F TypeRsp 0x84 R313FType ...

Страница 8: ...000000000 The device returns 8451020000000000000000 current device type R313FB 5 Configure the Threshold to 10 Deactive Time to 6s Downlink 0551000A06000000000000 The device returns 8551000000000000000000 configuration succeeded 8551010000000000000000 configuration failed 6 Read the current device type Downlink 0651000000000000000000 The device returns 8651000A06000000000000 current device type R3...

Страница 9: ...ed the device reports according to MaxTime interval 3 We do not recommend to set the MinTime Interval value too low If the MinTime Interval is too low the device wakes up frequently and the battery will be drained soon 4 Whenever the device sends a report no matter resulting from data variation button pushed or MaxTime interval another cycle of MinTime MaxTime calculation is started Wakes up and c...

Страница 10: ... transmission of the device 2 When the device detects a sudden movement or vibration of the object or electrical machinery Wait for a certain period of time DeactiveTime default 5 seconds can be modified to enter the quiescent state and it sends a report of duration of vibrations and restarts the calculation for the next detection the timer data will clear Note If the vibration continues to occur ...

Страница 11: ...when the temperature rises to normal temperature moisture will form inside which will destroy the board Do not throw knock or shake the device Rough handling of equipment can destroy internal circuit boards and delicate structures Do not clean the device with strong chemicals detergents or strong detergents Do not apply the device with paint Smudges might block in the device and affect the operati...

Отзывы: