Reference Manual
September 2012
MAN-0131, Revision 2
8
•
For analog and analog-HART model detectors, the signal output in alarm (20mA), can be
measured using a current measuring device placed in the analog loop or across the meter test
jacks inside the junction box.
•
For relay model detectors, changes in fire alarm relay status may be monitored at the detector
relay terminals or panel.
•
For digital model detectors, digital responses may be monitored at a PLC/panel.
•
After successful fire simulation, release the test lamp pushbutton and discontinue external
system bypass (return external system to normal operating mode).
Figure 3-2: IR3S Flame Detector Orientations and Target Sensor Location
A. IR3S Flame Detector window, typical orientation
B. IR3S Flame Detector window, 180° orientation
3.2
Response test for UV/IRS flame detectors
Follow the steps below to ensure accurate testing and fire simulation using the test lamp.
Important
When completing a fire simulation, ensure that the external system is in bypass or erroneous
activation of the safety system may occur.
•
Point the test lamp at the detector window, no greater than 20 feet (6.06 meters) from the
detector, as shown in
Figure 3-1
, then press and hold the test lamp pushbutton.
•
To simulate a fire condition, press and hold the test lamp pushbutton while directing the IR laser
(red dot) at the detector’s IR sensor as shown in
Figure 3-3
. After the detector time delay has
elapsed, the detectors red LED will flash to indicate a fire condition. Refer to the detector
manual (MAN-0015 or MAN-0075) for time delay settings.
•
For analog and analog-HART model detectors, the alarm signal output (20mA) can be measured
using a current measuring device placed in the analog loop or across the meter test jacks inside
the junction box.
•
For relay model detectors, changes in fire alarm relay status may be monitored at the detector
relay terminals or panel.
•
After a successful fire simulation, release the test lamp pushbutton and discontinue external
system bypass (return external system to normal operating mode).
Содержание TL-MP-KIT
Страница 1: ...Reference Manual Part Number MAN 0131 rev 2 Release September 2012 Multipurpose test lamp kit...
Страница 2: ......
Страница 6: ......
Страница 8: ......
Страница 26: ...Reference Manual September 2012 MAN 0131 Revision 2 18...
Страница 27: ......