Networkable Universal Wall-Mount Controller 

Specification and Installation Instructions 

 

TSUB-200306 

 

Page | 1 

Models 

 

 Model 

Temp 

RH 

PIR 

TSUB00-100 
TSUB30-100 
TSUB60-100 

● 

 

 

TSUB00-101 
TSUB30-101 
TSUB60-101 

● 

● 

 

TSUB00-104 
TSUB30-104 
TSUB60-104 

● 

 

● 

TSUB00-105 
TSUB30-105 
TSUB60-105 

● 

● 

● 

 

 

TSUB00 Series 

 

TSUB30 Series 

TSUB60 Series

 

Description 

The TSUB is a universal wall-mount controller with a

 

built-in temperature sensor. The unit is designed for simple and accurate 

control of a fan coil unit or heating/cooling equipment. Its field configurable algorithms enable versatile implementation of 
required control sequences. 

 

 

Featuring an external humidity sensor input for accurate humidity control, this comprehensive unit also provides a 
dehumidification sequence compensated by auto activation of reheat output. 

 

The controller is available with additional sensors, such as the PIR motion detection and humidity sensor, providing more 
functionality for the terminal device. 

Features 

 

Fan control: 1, 2 or 3-speed (auto/on), or analog (ECM) 

 

Optional internal/external humidity sensor input for 
simple and accurate humidity control 

 

Dehumidification sequence compensated by auto 
activation of reheat output 

 

Real time clock (RTC) with 24-hour backup 

 

7-day programmable schedule 

 

Precise temperature control with configurable PI 
(Proportional-Integral) function 

 

Selectable internal or external temperature sensor  

 

Low limit set protection (10°C / 50°F) 

 

Occupancy and night set back (NSB) mode 

 

Select direction on outputs 

 

Select controller’s default display 

 

Multi-level lockable access menu and setpoint 

 

Selectable Fahrenheit or Celsius scale  

 

Option of pulse/floating/on-off output on binary outputs 

 

Internal/external occupancy input 

 

Compressor anti-cycling delay (configurable) 

 

ΔT control (on request) 

Onboard Sensors 

 

Temperature sensor (°C/°F) 

 

Humidity sensor (%RH), select models 

 

PIR motion detection sensor, select models   

Network Communication 

 

BACnet

® 

MS/TP or Modbus communication port  

(selectable via configuration menu) 

 

Select MAC address via menu or via network 

 

Automatic baud rate detection 

BACnet MS/TP

®

 

 

Automatic device instance configuration 

 

Copy & broadcast configuration via menu or via BACnet 
to other controllers 

 

BACnet scheduler (up to 6 events per day) 

 

Firmware upgradeable via BACnet 

 

Supports COV (change of value) 

Modbus 

 

Modbus @ 9600, 19200, 38400 or 57600 bps 

 

RTU Slave, 8 bits (configurable parity and stop bits) 

 

Connects to any Modbus master 

 
 
 
 
 
 
 
 
 
 
 

Содержание TSUB00 Series

Страница 1: ...l Dehumidification sequence compensated by auto activation of reheat output Real time clock RTC with 24 hour backup 7 day programmable schedule Precise temperature control with configurable PI Proport...

Страница 2: ...er Inputs 2 Universal Inputs 0 10Vdc 10K sensor dry contact Outputs 5 Binary Outputs OptoFET 250mA max 2 Analog Outputs 0 10Vdc adjustable Power supply 22 to 26 Vac 50 60Hz Power consumption 1 VA max...

Страница 3: ...n speed 2 Fan speed 2 select any ramp Fan speed 2 Fan speed 2 9 BO6 Fan speed 1 Fan speed 1 Fan speed 1 select any ramp Fan speed 1 Fan speed 1 Fan speed 1 10 BO7 select any ramp select any ramp 11 AO...

Страница 4: ...hat s holding the base and the front cover of the unit together B Lift the front cover of the unit to separate it from the base C Pull all wires through the holes in the base D Secure the base to the...

Страница 5: ...example a controller placed right under the air diffuser 2 Minimum User Setpnt Default Range Increment 15 C 59 F 10 C to 40 C 50 F to 104 F 0 5 C 1 0 F In Operation mode you cannot decrease the setpoi...

Страница 6: ...ontrol Mode Default Range yES Enable yES Enable No Disable If set to yES the user can set the unit to Off via the Control Mode see page 33 If set to No the Off selection does not appear in the Control...

Страница 7: ...to Mode will not be available If you select ENA Step 15 EMH Auto Mode will be available 15 EMH Auto Mode Default Range NO Disable YES Enable NO Disable This option appears only if you have selected EN...

Страница 8: ...e If you select VFdt or VFdP Steps 28 to 33 will not be available If you select CH1 Step 27 Minimum Cool 1 Heat 1 Percent will be available If you select FAN Step 28 Fan Spd Signal will not be availab...

Страница 9: ...utput based on carbon dioxide levels 6W 6 way Valve If selected the controller will modulate the 6 way valve depending on the heating or cooling demand dto Delta temperature control If selected the co...

Страница 10: ...peed contacts The fan symbol is also displayed 29 Fan Speed Option Default Range Std Standard AdV Advanced Std Standard Select between the Standard Neptronic and Advanced OE1 fan speed specifications...

Страница 11: ...e available options Cr1 Cooling Ramp 1 or Cr2 Cooling Ramp 2 The Cr1 and Cr2 ramps are used for cooling If selected the controller performs cooling based on the cooling proportional integral and dead...

Страница 12: ...type for BO3 to either Pulsing On Off or Floating Binary Output 4 BO4 The Binary Output 4 settings appear only if you have selected either fan speed 1 or 2 at Step 28 Fan Spd Signal or VFdP VFdt or F...

Страница 13: ...Range Increment 20 of the demand 15 to 80 1 This option does not appear if the signal ramp for BO5 is set to OFF Step 48 BO5 Ramp Select the percentage at which you want BO5 to close at of demand of...

Страница 14: ...for BO6 is set to OFF Step 54 BO6 Ramp Select the percentage at which you want BO6 to close at of demand of the ramp selected at Step 54 BO6 Ramp 56 BO6 Open Percent Default Range Increment 0 of the...

Страница 15: ...does not appear if the signal ramp for BO7 is set to OFF Step 60 BO7 Ramp Select the closing delay for BO7 output 65 BO7 Signal Type BO7 Default Range OnOF On Off tPm Pulsing OnOF On Off FLot Floating...

Страница 16: ...1 F to 9 F 0 5 C 1 F Select the desired proportional band value of the cooling ramp 2 The cooling symbol is also displayed 75 Cool 2 Dead Band Default Range Increment 0 3 C 0 6 F 0 0 C to 5 0 C 0 F t...

Страница 17: ...arm to indicate that the window is open If you select win Steps 107 Window Open Mode and 108 Window Fan Mode will be available door If selected the controller activates an alarm to indicate that the d...

Страница 18: ...e Select the minimum voltage for UI1 82 UI1 Contact UI1 Default Range NO Normally Open NO Normally Open NC Normally Close This option appears only if you have selected any one of the options OCC nSb o...

Страница 19: ...Normally Open NO Normally Open NC Normally Close This option appears only if you have selected any one of the options OCC nSb oVrd win door dFt FLS oVht SEL at Step 84 UI2 Signal Type Select the desi...

Страница 20: ...lue for carbon dioxide CO2 93 CO2 Setpnt Default Range Increment 800 PPM 100 to 2000 PPM 10 PPM This step appears only if you have selected CO2 at Step 80 UI1 Signal Type or Step 84 UI2 Signal Type In...

Страница 21: ...2 0 C 72 F 10 0 C to 40 0 C 50 F to 104 F 0 5 C 1 F Select the desired VFD temperature setpoint The fan symbol is also displayed 101 VFD Temp Dead Band Default Range Increment 0 3 C 0 6 F 0 0 C to 5 0...

Страница 22: ...setpoints when the window is open OFF If selected the controller is forced into OFF mode when the window is open 108 Window Fan Mode Default Range AUto Automatic AUto Automatic LO Low mEd Medium HI H...

Страница 23: ...F 0 5 C 1 F This option appears only if you have selected nSb at Step 80 UI1 Signal Type or Step 84 UI2 Signal Type Set the cooling setpoint that will be used when the system is in Night Set Back NSB...

Страница 24: ...the following conditions if you have selected HU at Step 80 UI1 Signal Type or Step 84 UI2 Signal Type or for the models with the built in humidity sensor unless otherwise specified 122 Extern Humidt...

Страница 25: ...umidty Control Mode In Operation mode you cannot increase the setpoint to more than the value set as the maximum humidity setpoint The maximum value is restricted by the minimum value set at Step 127...

Страница 26: ...ontrol Mode and also OCC at Step 80 UI1 Signal Type or Step 84 UI2 Signal Type Adjust the dehumidify setpoint during No Occupancy Mode The dehumidify setpoint is restricted by the humidify setpoint at...

Страница 27: ...pied mode controller is idle and occupancy state is inactive Use the and buttons to increase or decrease the backlight or contrast level Network Settings 142 Select Network Proto Default Range bAC BAC...

Страница 28: ...ges copy config succeed Copy config was successful copy config progerr Copy config failed because the target device is in Program Mode copy config typeerr Copy config failed because the target device...

Страница 29: ...automatically configures its baud rate by detecting the network speed upon connection to the network 154 Modbus Bauds Rate Default Range No default information display only 9 6k 19 2k 38 4k 57 6k If y...

Страница 30: ...ibed in Programming Mode on page 4 The controller will return to normal mode if you navigate through the entire menu and do not make any selection or if you do not press any key for 5 minutes The chan...

Страница 31: ...exit the Event menu press the button Reset Schedule 11 Reset Schedul Default Range nO yES nO Select whether to reset and delete the scheduled events or not Network Setup Menu This menu is accessible t...

Страница 32: ...ure For example a controller placed right under the air diffuser 2 Extern Temp Sensor Offset Range Offset Increment 40 0 C to 100 C 40 F to 212 F Max 5 C 9 F 0 1 C 0 2 F This option appears only if yo...

Страница 33: ...played If a sensor is disconnected or short circuited then the unit displays the sensor s limits To toggle the temperature scale between C and F press both the up and down arrow keys for 3 seconds Tem...

Страница 34: ...y Minutes The symbol flashes to indicate that the NSB mode is overridden during this time the standard setpoints are used No Occupancy Mode This function is only available if you have set input to OCC...

Страница 35: ...Notes...

Страница 36: ...need to find the nearest Neptronic authorized distributor please consult www neptronic com 400 Lebeau blvd Montreal Qc H4N 1R6 Canada www neptronic com Toll free in North America 1 800 361 2308 Tel 51...

Отзывы: