Neptronic TROB24 Series Скачать руководство пользователя страница 4

 

TROB24 Series Thermostat 

 

Page  | 3  

Getting Started 

The following BACnet

®

 properties are configurable and may need to be modified to effectively establish 

communication on the network and to guarantee uniqueness of each device in a BACnet

®

 system.  

 

 

MAC Address 

(Default: 001) 

Set to between 000 and 254 via thermostat menu* (128-254 represent MS/TP non-token-passing slave 
devices). 
 

 

Device Instance 

(Default: Auto) 

The thermostat automatically configures its device instance to  MAC address. Can also be set 
manually via thermostat menu* or through the WriteProperty service to 

Device Object.Object_Identifier.

 

The device’s Object_Identifier is a combination of the Device Object_Type (8) and the Device_Instance 
(0-4194302), therefore its decimal or hexadecimal representation tends to be incomprehensible. For 
example, the Device_Instance=1000 has an equivalent Object_Identifier of 0x020003E8 hexadecimal or 
33555432 decimal. While it’s the device’s Object_Identifier property that can be changed using a 
BACnet

®

 WriteProperty service, this document refers mostly to Device_Instance. 

 

 

Baud Rate

 (Default: 0 = Auto) 

The thermostat automatically configures its baud rate by detecting the network speed upon connection. 
Can also be set manually via thermostat menu* or through the WriteProperty service to 

Device 

Object.proprietary property #1001

. This value is Unsigned type, and available values are 9600, 19200, 

38400, 76800. 

 

 

Max_Master

 (Default: 127) 

To increase network efficiency or if there are less than 127 devices on the network, the Max_Master 
value can be configured through WriteProperty service to the 

Device Object.Max_Master

. For more 

information, refer to the MAC address and Max_Master section on page 4. 
 

 

Device Object.Object_Name 

Name of device, for example TROB24T4XYZ1. This value can be configured through WriteProperty 
service to the 

Device Object.Object_Name

 

* NOTE: When referring to the thermostat menu in this section, it includes the Quick Access Menu when in 
operation mode (RUN) and the Installer Menu when in programming mode (PGM).Refer to the thermostat’s 
Specification & Installation Manual for more details. 

Quick Setup 

Take advantage of the Auto Baud Rate Detection, Auto Device Instance Configuration, and default Max_Master 
value, to get up and running with no programming. 
  

1)  Connect the thermostat to the network and then power up the thermostat. The thermostat automatically 

configures the baud rate and device instance.  

2)  If you need to set a unique MAC address (default 001), continue to step 3. If not, setup is complete. 
3)  With the thermostat in Operation Mode (jumper = RUN), go to the Quick Access Menu by pressing and 

holding both function buttons on the thermostat for 5 seconds. Refer to the thermostat’s 

Specification & 

Installation Manual

 for more details. 

4)  Enter the password (637). 
5)  Set a unique MAC address. 
6)  Power down and then power up the thermostat 

Manual Setup 

If your site has more than one TROB24 network and/or you wish to use a Device_Instance other than 153,000, 
follow these instructions. 
 

1)  With the thermostat in Operation Mode (jumper = RUN), go to the Quick Access Menu by pressing and 

holding both function buttons on the thermostat for 5 seconds. Refer to the thermostat’s 

Specification & 

Installation Manual

 for more details. 

Содержание TROB24 Series

Страница 1: ...TROB24 Series Thermostat BACnet Communication Module User Guide TROB24 SERIES BACNET USER GUIDE TROB24 120926 EUL doc...

Страница 2: ...ries Thermostat 1 Table of Contents 1 Introduction 2 BACnet Overview 2 Getting Started 3 Quick Setup 3 Manual Setup 3 Copy Config 4 MAC address and Max_Master 4 Device Object Properties 5 Object Types...

Страница 3: ...e refer to the Getting Started section on page 3 For more information on the thermostat menu please refer to the thermostat s Specification Installation Manual for more details BIBB Support The thermo...

Страница 4: ...x_Master value can be configured through WriteProperty service to the Device Object Max_Master For more information refer to the MAC address and Max_Master section on page 4 Device Object Object_Name...

Страница 5: ...ess and Max_Master A poor combination of MAC addresses and Max_Master can lead to a slower network due to lost time polling for masters that are not present Unless there are 126 other units on the MS...

Страница 6: ...ays 0x00 0x09 0x40 0x02 0x60 i e a bitstring in BACnet order writeProperty readProperty deviceCommunicationControl unconfirmedPrivateTransfer who Is who Has Protocol_Object_Types_Supported Always 0x00...

Страница 7: ...Multi State Value 5 Description Reliability States_Text Present_Value6 N A Out of Service Neptronic thermostats offer the use of the Out of Service writable property When set to true this property di...

Страница 8: ...nds AV 42 CoolingDemand2 N A 0 100 Resolution 0 1 AV 43 CoolingPropBand2 Present Value 0 5 5 C or 1 10 F Resolution 0 5 C 1 F AV 44 CoolingDeadBand2 Present Value 0 3 5 C or 0 6 10 F Resolution 0 1 C...

Страница 9: ...ng 4 Off only if BV 3 is set to Enable States available if MSV 4 is set to Cool 1 Cooling 2 Off only if BV 3 is set to Enable States available if MSV 4 is set to Heat 1 Heating 2 Off only if BV 3 is s...

Страница 10: ...Value 1 ChangeOverDemand 2 CoolingDemand1 3 CoolingDemand2 4 HeatingDemand1 5 HeatingDemand2 States available if MSV 23 is set to Pulsing 1 HeatingDemand1 2 HeatingDemand2 MSV 20 TO3Source Present Va...

Страница 11: ...n_Off 1 20 2 40 3 60 4 80 MSV 29 TO4ClosePos Present Value Ignored if MSV 25 is other than On_Off 1 20 2 40 3 60 4 80 MSV 31 PressureIndOutput Present Value if MSV 22 and MSV 24 are set to Floating 1...

Страница 12: ...treal Qc H4N 1R6 CANADA www neptronic com Toll free in North America 1 800 361 2308 Tel 514 333 1433 Fax 514 333 3163 Customer service Fax 514 333 1091 Business hours from Monday to Friday 8 00am to 5...