TROB24 Series Thermostat 

 

Page  | 2  

Introduction 

This document provides information on using the Neptronic thermostat communications feature. This product 
provides a BACnet

®

 network interface between BACnet

®

 client devices and Neptronic products. It uses the 

BACnet

®

 Master Slave/Token Passing (MS/TP) protocol at the BACnet

®

 MAC layer.  

 
This document assumes you are familiar with BACnet

®

 and BACnet

®

 terminology. 

BACnet

®

 Overview 

Performance 

The thermostat uses a synchronous implementation for BACnet

®

 messages. Each BACnet

®

 confirmed service 

request is answered as quickly as possible without using Reply Postponed. In particular, MS/TP implementation 
performs within Tusage_delay of 15ms in order to assure Tusage_timeout values within 20ms. 

Support for MS/TP 

The thermostat supports a Full Master Node state machine for MS/TP. All parameters are configured via the 
thermostat menu or via the BACnet

®

 WriteProperty service. Changes made via the WriteProperty take effect 

immediately and does not require a restart of the thermostat. For more information on the configurable 
properties, please refer to the 

Getting Started

 section on page 3. For more information on the thermostat menu, 

please refer to the thermostat’s 

Specification & Installation Manual

 for more details. 

BIBB Support 

The thermostat generally behaves as a B-ASC type profile server. The following specific BIBBs are supported 
per their relevant definitions in Annex K to BACnet

®

: DS-RP-B, DS-RPM-B, DS-WP-B, DS-WPM-B, DM-DDB-B, 

DM-DOB-B, DM-DCC-B 

Object Support (in general) 

The thermostat supports a table-based fixed list of BACnet

®

-visible values which appear as Present_Values of 

various BACnet

®

 standard object types, in addition to a Device object.  

Alarms 

Although the thermostat supports the ability to indicate various alarm conditions through value changes in 
properties of several of its objects, it 

does not

 generate BACnet

®

 Event Notifications.  

Features 

Neptronic thermostats also offer the following time-saving features. 

Auto Baud Rate Detection 

The thermostat automatically configures its baud rate by detecting the network speed upon connection.  

Auto Device Instance Configuration 

The thermostat automatically configures its device instance to  MAC address.  

Copy Configuration 

Copy the thermostat’s entire configuration and broadcast it to other thermostats of the same type on the 
same network. 
 

Содержание TROB24 Series

Страница 1: ...TROB24 Series Thermostat BACnet Communication Module User Guide TROB24 SERIES BACNET USER GUIDE TROB24 120926 EUL doc...

Страница 2: ...ries Thermostat 1 Table of Contents 1 Introduction 2 BACnet Overview 2 Getting Started 3 Quick Setup 3 Manual Setup 3 Copy Config 4 MAC address and Max_Master 4 Device Object Properties 5 Object Types...

Страница 3: ...e refer to the Getting Started section on page 3 For more information on the thermostat menu please refer to the thermostat s Specification Installation Manual for more details BIBB Support The thermo...

Страница 4: ...x_Master value can be configured through WriteProperty service to the Device Object Max_Master For more information refer to the MAC address and Max_Master section on page 4 Device Object Object_Name...

Страница 5: ...ess and Max_Master A poor combination of MAC addresses and Max_Master can lead to a slower network due to lost time polling for masters that are not present Unless there are 126 other units on the MS...

Страница 6: ...ays 0x00 0x09 0x40 0x02 0x60 i e a bitstring in BACnet order writeProperty readProperty deviceCommunicationControl unconfirmedPrivateTransfer who Is who Has Protocol_Object_Types_Supported Always 0x00...

Страница 7: ...Multi State Value 5 Description Reliability States_Text Present_Value6 N A Out of Service Neptronic thermostats offer the use of the Out of Service writable property When set to true this property di...

Страница 8: ...nds AV 42 CoolingDemand2 N A 0 100 Resolution 0 1 AV 43 CoolingPropBand2 Present Value 0 5 5 C or 1 10 F Resolution 0 5 C 1 F AV 44 CoolingDeadBand2 Present Value 0 3 5 C or 0 6 10 F Resolution 0 1 C...

Страница 9: ...ng 4 Off only if BV 3 is set to Enable States available if MSV 4 is set to Cool 1 Cooling 2 Off only if BV 3 is set to Enable States available if MSV 4 is set to Heat 1 Heating 2 Off only if BV 3 is s...

Страница 10: ...Value 1 ChangeOverDemand 2 CoolingDemand1 3 CoolingDemand2 4 HeatingDemand1 5 HeatingDemand2 States available if MSV 23 is set to Pulsing 1 HeatingDemand1 2 HeatingDemand2 MSV 20 TO3Source Present Va...

Страница 11: ...n_Off 1 20 2 40 3 60 4 80 MSV 29 TO4ClosePos Present Value Ignored if MSV 25 is other than On_Off 1 20 2 40 3 60 4 80 MSV 31 PressureIndOutput Present Value if MSV 22 and MSV 24 are set to Floating 1...