background image

 

TFxB Series Thermostat Controller 

 

Page  | 4  

2)  Enter the password (637). 
3)  In this mode you can manually configure the MAC address, Device Instance and Baud Rate. 
4)  Power down the thermostat controller, connect it to the network and then power up the unit. 
5)  Repeat steps 1 to 4 for each thermostat controller. 
6)  To increase network efficiency or if there are less than 127 devices on the network, the Max_Master 

value can be configured through WriteProperty service to the 

Device Object.Max_Master

. For more 

information, refer to the 

MAC address and Max_Master

 section on page 4. 

Copy Config 

Copy the thermostat controller’s entire configuration and broadcast it to other thermostat controllers of the same 
type on the same network. 

1)  With the thermostat controller in Operation Mode (jumper = RUN), go to the Quick Access Menu by 

pressing and holding both function buttons on the thermostat for 5 seconds. Refer to the 

Specification & 

Installation Manual

 for more details. 

2)  Enter the password (637). 
3)  Scroll to “Copy Config” and select yes. Follow onscreen instructions. 

MAC address and Max_Master 

The MAC address must be unique on the entire MS/TP network. However, having a unique MAC address and a 
high baud rate does not guarantee efficient operation of the thermostat controller and other MS/TP units on the 
MS/TP network. Some MAC address and Max_Master combinations are more efficient than others. BACnet

®

 

requires token-passing units to occasionally “poll” for other masters based on the MAC address and 
Max_Master. A “poor” combination of MAC addresses and Max_Master can lead to a slower network due to lost 
time polling for masters that are not present. Unless there are 126 other units on the MS/TP network, the default 
Max_Master of 127 is not the most efficient choice for the thermostat controller. The Max_Master default of 127 
was selected to ensure that any master, specifically a BACnet

®

 client, can be found when the thermostat 

controller is first started. 
 

Example 1: 

This example is slow and inefficient because every time either unit is required to find another master unit it has 
to poll 126 units until it finds the right one to pass the token. 

 MAC=0. 

Max_Master=127 

 MAC=1, 

Max_Master=127 

 

Example 2: 

This example is better but it’s still slower. The Max_Master is set to the most efficient value; however because 
of the gap between the two MAC addresses, each unit must poll 4 units until it finds the right one to pass the 
token. 

 MAC=0. 

Max_Master=5 

 

MAC=1 to MAC=4 are not used 

 MAC=5, 

Max_Master=5 

 

Example 3: 

This example is an incorrect configuration. The MAC=0 will never find MAC=2 because it will never poll for the 
master MAC address=2. 

 MAC=0. 

Max_Master=1 

 MAC=2, 

Max_Master=2 

 

Example 4: 

As a general guideline, the most efficient set up for an MS/TP network is one in which the units are 
consecutively numbered starting at MAC address 0 and all have Max_Master=the maximum MAC address in 
the system. If consecutive numbering is not possible, then the next most efficient set up is one in which all units 
have Max_Master=the maximum MAC address in the system. 

 MAC=0. 

Max_Master=3 

 MAC=1, 

Max_Master=3 

 MAC=2, 

Max_Master=3 

 MAC=3, 

Max_Master=3 

Содержание TFCB24F3XY2

Страница 1: ...TFxB Series Thermostat Controller BACnet Communication Module User Guide TFxB SERIES BACNET USER GUIDE TFxB24 Bacnet 121026 EUA doc...

Страница 2: ...xB Series Thermostat Controller 1 Table of Contents 1 Introduction 2 BACnet Overview 2 Getting Started 3 Quick Setup 3 Manual Setup 3 Copy Config 4 MAC address and Max_Master 4 Device Object Propertie...

Страница 3: ...Started section on page 3 For more information on the thermostat menu please refer to the thermostat controller s Specification Installation Manual for more details BIBB Support The thermostat control...

Страница 4: ...e can be configured through WriteProperty service to the Device Object Max_Master For more information refer to the MAC address and Max_Master section on page 4 Device Object Object_Name Name of devic...

Страница 5: ...sed on the MAC address and Max_Master A poor combination of MAC addresses and Max_Master can lead to a slower network due to lost time polling for masters that are not present Unless there are 126 oth...

Страница 6: ...APDU_Retries Always 0 Protocol_Services_Supported Always 0x00 0x09 0x40 0x00 0x60 i e a bitstring in BACnet order Protocol_Object_Types_Supported Always 0x00 0xB4 0x80 0x10 i e a bitstring in BACnet o...

Страница 7: ...hermostat controllers offer the use of the Out of Service writable property When set to true this property disconnects the object from the physical input enabling you to input other values This could...

Страница 8: ...geMin 2pipes Present Value x x x x x x x 0 Volt to AV 20 Resolution 0 1 Volt AV 18 CoolingVoltageMin 4pipes Present Value x x x x x x x 0 Volt to AV 21 Resolution 0 1 Volt AV 19 HeatingVoltageMin 4pip...

Страница 9: ...x x 0 Off 1 On MSV 1 UniversalInputFunction 12 Present Value x x x x x 1 Off 2 Extern Sensor States of TFCB24F3XY2 product States available if BV 5 is set to 2Pipe 1 ChangeOverSensor 2 Ch Ov ContactNo...

Страница 10: ...Cooling 1 Cooling 2 Fan 3 Off only if BV 3 is set to Enable States available if MSV 4 is set to Heating 1 Heating 2 Fan 3 Off only if BV 3 is set to Enable States available if MSV 4 is set to HeatingO...

Страница 11: ...m Heat States available if BV 5 is set to 4Pipe except for OE1 version 1 Off States available if BV 5 is set to 4 Pipe in OE1 version 1 Off 2 Extern Sensor MSV 13 OccupancyMode 14 Present Value x x x...

Страница 12: ...treal Qc H4N 1R6 CANADA www neptronic com Toll free in North America 1 800 361 2308 Tel 514 333 1433 Fax 514 333 3163 Customer service Fax 514 333 1091 Business hours from Monday to Friday 8 00am to 5...

Отзывы: