TFxB Series Thermostat Controller
Page | 10
ID
8
Name
Writable
Property
TF
C
B
24F
3XYZ
1
TF
C
B
24F
3XY
2
TF
H
B
24F
3XYZ
1
TF
H
B
24F
3XYZ
2
TF
C
B
24
P
3
-OE
1
TF
H
B
24
P
3
-OE
1
TF
H
B
24
P
3
-OE
2
Notes
MSV.11
DigitalInputMode Present
Value
x x x x
x
x
x
1= OccNorm.Open
2= OccNorm.Close
MSV.12
UniversalInput2Function Present
Value
x x x
x
x
x
States available if BV.5 is set to 2Pipe:
1= ChangeOverSensor
2= Ch.Ov.ContactNorm.Cool
3= Ch.Ov.ContactNorm.Heat
States available if BV.5 is set to 4Pipe except
for OE1 version.
1=Off
States available if BV.5 is set to “4 Pipe” in
OE1
version
1= Off
2= Extern.Sensor
MSV.13
OccupancyMode
14
Present
Value
x x x x
x
x
x
1= Occ.Locally
2= Occupancy
3= NoOccupancy
MSV.14
OccupancyStatus
15
Out of service
x x x x
x
x
x
1= NoOccupancy
2= Occupancy
3= Override
14
Occ.Locally lets the thermostat locally manage the occupancy or noOccupancy status for energy conservation. The other 2 states force
the thermostat into a specific state.
15
Read only. Override will only be active if AV.39 is other than 0 and the user presses a button.