background image

 

 

 

TFxB Series Thermostat Controller 

 

BACnet

®

 Communication Module  

User Guide 

 
 

 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

 

 

TFxB-SERIES-BACNET-USER GUIDE 

TFxB24-Bacnet-121026-EUA.doc 

 

Содержание TFCB24F3XY2

Страница 1: ...TFxB Series Thermostat Controller BACnet Communication Module User Guide TFxB SERIES BACNET USER GUIDE TFxB24 Bacnet 121026 EUA doc...

Страница 2: ...xB Series Thermostat Controller 1 Table of Contents 1 Introduction 2 BACnet Overview 2 Getting Started 3 Quick Setup 3 Manual Setup 3 Copy Config 4 MAC address and Max_Master 4 Device Object Propertie...

Страница 3: ...Started section on page 3 For more information on the thermostat menu please refer to the thermostat controller s Specification Installation Manual for more details BIBB Support The thermostat control...

Страница 4: ...e can be configured through WriteProperty service to the Device Object Max_Master For more information refer to the MAC address and Max_Master section on page 4 Device Object Object_Name Name of devic...

Страница 5: ...sed on the MAC address and Max_Master A poor combination of MAC addresses and Max_Master can lead to a slower network due to lost time polling for masters that are not present Unless there are 126 oth...

Страница 6: ...APDU_Retries Always 0 Protocol_Services_Supported Always 0x00 0x09 0x40 0x00 0x60 i e a bitstring in BACnet order Protocol_Object_Types_Supported Always 0x00 0xB4 0x80 0x10 i e a bitstring in BACnet o...

Страница 7: ...hermostat controllers offer the use of the Out of Service writable property When set to true this property disconnects the object from the physical input enabling you to input other values This could...

Страница 8: ...geMin 2pipes Present Value x x x x x x x 0 Volt to AV 20 Resolution 0 1 Volt AV 18 CoolingVoltageMin 4pipes Present Value x x x x x x x 0 Volt to AV 21 Resolution 0 1 Volt AV 19 HeatingVoltageMin 4pip...

Страница 9: ...x x 0 Off 1 On MSV 1 UniversalInputFunction 12 Present Value x x x x x 1 Off 2 Extern Sensor States of TFCB24F3XY2 product States available if BV 5 is set to 2Pipe 1 ChangeOverSensor 2 Ch Ov ContactNo...

Страница 10: ...Cooling 1 Cooling 2 Fan 3 Off only if BV 3 is set to Enable States available if MSV 4 is set to Heating 1 Heating 2 Fan 3 Off only if BV 3 is set to Enable States available if MSV 4 is set to HeatingO...

Страница 11: ...m Heat States available if BV 5 is set to 4Pipe except for OE1 version 1 Off States available if BV 5 is set to 4 Pipe in OE1 version 1 Off 2 Extern Sensor MSV 13 OccupancyMode 14 Present Value x x x...

Страница 12: ...treal Qc H4N 1R6 CANADA www neptronic com Toll free in North America 1 800 361 2308 Tel 514 333 1433 Fax 514 333 3163 Customer service Fax 514 333 1091 Business hours from Monday to Friday 8 00am to 5...

Отзывы: