 SKS4 Steam to Steam Humidifier 

Modbus Communication Module User Guide

 

 

www.neptronic.com

 

Page | 1 

 

 

Introduction  

The  SKS4  Modbus  Communication  Module  User  Guide  provides  information  for  using  Neptronic

®

  communication 

feature. The controller uses Modbus communication protocol over serial line in the RTU mode and provides a Modbus 
network interface between client devices and Neptronic SKS4 devices.  
The SKS4 Modbus Guide assumes that you are familiar with Modbus terminology. 
 
The following are the requirements for Modbus: 

 

Data  Model

.  The  SKS4  Steam  to  Steam  Humidifier  Modbus  server  data  model  uses  only  the  Modbus 

Registers table. 

 

Register Address

:  

o

 

As per protocol base (base 0); for PLC add 1 to protocol base. 

o

 

As per holding register (base 400001). 

 

Note: Ensure that the Modbus communication software used does not have a limit on the range of the 
register addresses that can be viewed and supports 6-digit holding registers.  

 

Function  Codes

.  The  SKS4  Steam  to  Steam  Humidifier  Modbus  server  supports  a  limited  function  codes 

subset comprising:  

o

 

Read Holding Registers (0x03) 

o

 

Write Single Register (0x06) 

o

 

Write Multiple Registers (0x10) 

 

Exception Responses

. The SKS4 Steam to Steam Humidifier Modbus server supports the following exception 

codes: 

o

 

Illegal data address  

o

 

Illegal data value 

o

 

Slave device busy 

 

Serial Line

. The SKS4 Steam to Steam Humidifier Modbus over serial line uses RTU transmission mode over 

a two-wire configuration RS485 (EIA/TIA-485 standard) physical layer. 

o

 

The  physical  layer  can  use  fixed  baud  rate  selection  or  automatic  baud  rate  detection  (default)  as 
per the 

Modbus Auto Baud Rate

 device menu item or holding register index 1. 

o

 

The supported baud rates are 9600, 19200, 38400, and 57600.  

o

 

The physical layer also supports variable parity control and stop bit configuration as per the 

Modbus 

Comport Config

 device menu item or holding register index 2.   

o

 

In  auto  baud  rate  configuration,  if  the  device  detects  only  consecutive  bad  frames  (2  or  more)  for 
one second with any given baud rate, it will reinitialize itself to the next baud rate. 

 

Addressing

. The SKS4 Steam to Steam Humidifier device only answers at the following address:  

o

 

The device's unique address (1 to 246) that can be set through the device menu or through holding 
register index 0. 

 

 

Содержание SKS4 Modbus

Страница 1: ...SKS4 Modbus Guide 191017 SKS4 Steam to Steam Humidifier Modbus Communication Module User Guide ...

Страница 2: ...ising o Read Holding Registers 0x03 o Write Single Register 0x06 o Write Multiple Registers 0x10 Exception Responses The SKS4 Steam to Steam Humidifier Modbus server supports the following exception codes o Illegal data address o Illegal data value o Slave device busy Serial Line The SKS4 Steam to Steam Humidifier Modbus over serial line uses RTU transmission mode over a two wire configuration RS4...

Страница 3: ...ption Data Type Units Limits State Texts Writable Default Value 0 400001 Modbus Address and Product Type Unsigned MSB Product type not writable LSB Modbus Address 1 to 247 writable W 1 400002 Device Baud Rate Unsigned Scale 100 0 9600 19200 38400 and 57600 0 Auto Baud Rate Detection Value 100 e g 38400 baud 384 W 19200 2 400003 Modbus Slave Communication Port Configuration Unsigned 0 No parity 2 S...

Страница 4: ... RO 0Hz 2004 402005 Water Level Low Signal Unsigned Scale 1000 Unit Volt V Range 0V to 10V Value x 1000 e g 1V 1000 RO 0V 2005 402006 Water Level High Signal Unsigned Scale 1000 Unit Volt V Range 0V to 10V Value x 1000 e g 1V 1000 RO 0V 2006 402007 Water Temperature Signal Unsigned Scale 1000 Unit Volt V Range 0V to 10V Value x 1000 e g 1V 1000 RO 0V 2007 402008 Foam Signal Unsigned Scale 1000 Uni...

Страница 5: ...ure Unsigned Scale 100 Unit ºC ºF Range 0 C to 125 C or 32 F to 257 F Value x 100 e g 5 C 500 or 40ºF 4000 RO 50 C or 122 F 6006 406007 Water Temperature Min Unsigned Scale 100 Unit ºC ºF Range 0 C to 250 C or 32 F to 482 F Value x 100 e g 5 C 500 or 40ºF 4000 RO 0 C or 32 F 6007 406008 Water Temperature Max Unsigned Scale 100 Unit ºC ºF Range 0 C to 250 C or 32 F to 482 F Value x 100 e g 5 C 500 ...

Страница 6: ...e 1 Unit Hz Range 0 to 30000 Hz Value x 1 e g 1 Hz 1 RO 30000Hz 6019 406020 Water Probe Abs Low Pos Reading Unsigned Scale 1 Unit Hz Range 0 to 30000 Hz Value x 1 e g 1 Hz 1 RO 30000Hz 6020 406021 Water Probe Abs High Pos Reading Unsigned Scale 1 Unit Hz Range 0 to 30000 Hz Value x 1 e g 1 Hz 1 RO 30000Hz 6021 406022 Room RH Network Reading Unsigned Scale 100 Unit RH Range 0 RH to 100 RH Value x 1...

Страница 7: ...Low Dead Band 0 Unsigned Scale 100 Unit Range 0 to 100 Value x 100 e g 10 1000 W 1 6033 406034 Humidity Demand Low Dead Band 1 Unit Range 0 to 100 6034 406035 Network Timeout 0 Unsigned Scale 1 Unit Seconds sec Range 1 to 900 sec Value x 1 e g 10sec 10 W 900 sec 6035 406036 Network Timeout 1 Unit Seconds sec Range 1 to 900 sec 6036 406037 System Power Output Unsigned Scale 100 Unit Range 0 to 100 ...

Страница 8: ...b hr Value x 10 e g 10 kg hr 100 or 10 lb hr 100 RO 15 kg hr or 33 06 lb hr 6048 406049 Boiler Power Output Unsigned Scale 100 Unit Range 0 to 100 Value x 100 e g 10 1000 RO 0 6049 406050 Boiler Run Time 0 Unsigned Scale 100 Units Hours h Range 0 to 21474836 47 h Value x 100 e g 10h 1000 RO 0h 6050 406051 Boiler Run Time 1 Units Hours h Range 0 to 21474836 47 h 6051 406052 Boiler Run Time 2 Units ...

Страница 9: ...ned Scale 1 Unit Range 1 to 25 Value x 1 e g 1 1 W 5 6066 406067 Boiler Drain Interval Unsigned Scale 1 Units Hours h Range 0 to 24 h Value x 1 e g 1 h 1 W 6h 6067 406068 Boiler Drain Volume Unsigned Scale 1 Unit Range 25 to 100 Value x 1 e g 30 300 W 100 6068 406069 Boiler Max Steam Output Unsigned Scale 1 Unit Range 0 to 100 Value x 1 e g 30 300 W 100 6069 406070 Boiler Idle Time Drain Unsigned ...

Страница 10: ...h Limit Unsigned Scale 1 0 Closed 1 Open RO Closed 10002 410003 Interlock Unsigned Scale 1 0 Closed 1 Open RO Closed 10003 410004 Binary External Demand Unsigned Scale 1 0 0 1 100 RO 0 10004 410005 Water Leak Detection Unsigned Scale 1 0 Ok 1 Leak RO Ok 10005 410006 Thermal Cutout Unsigned Scale 1 0 Closed 1 Open RO Closed 10006 410007 RS485 Interface Unsigned Scale 1 0 No 1 Yes RO No 10007 410008...

Страница 11: ...Valve Unsigned Scale 1 0 Off 1 On RO Off 11005 411006 Drain Cooler Valve Unsigned Scale 1 0 Off 1 On RO Off 11006 411007 Drain Pump Unsigned Scale 1 0 Off 1 On RO Off 11007 411008 Drain Pump 2 Unsigned Scale 1 0 Off 1 On RO Off 11008 411009 Drain Pump 3 Unsigned Scale 1 0 Off 1 On RO Off 11009 411010 Alarm LED Unsigned Scale 1 0 Off 1 On RO Off 11010 411011 Power LED Unsigned Scale 1 0 Off 1 On RO...

Страница 12: ...nt Unsigned Scale 1 0 Unlock 1 Lock W Unlock 12006 412007 Notify Alarm Unsigned Scale 1 0 Off 1 On W Off 12007 412008 Notify Warning Unsigned Scale 1 0 Off 1 On W Off 12008 412009 Notify App Msg Unsigned Scale 1 0 Off 1 On W Off 12009 412010 Inhibit Resistive Probe Unsigned Scale 1 0 No 1 Yes W No 12010 412011 Boiler Service Operation Unsigned Scale 1 0 Not Allowed 1 Allowed W Allowed 12011 412012...

Страница 13: ... InternNetwork 5 Custom W Disabled 15005 415006 Occupancy State Unsigned Scale 1 0 Occupied 1 Unoccupied 2 Vacant 3 Off RO Occupied 15006 415007 Room RH Source Unsigned Scale 1 0 None 1 RoomRH 2 Network W None 15007 415008 Room RH Setpoint Source Unsigned Scale 1 0 None 1 Internal 2 ControlInput W None 15008 415009 Supply High Limit Reading Source Unsigned Scale 1 0 None 1 SuppyHLRH 2 Network W No...

Страница 14: ...eShot 1 Pulsed W Pulsed 15016 415017 Boiler Alarm Unsigned Scale 1 0 Normal 1 FailedPump 2 FillTimeout 3 BlockedPiping 4 HeatTimeout 5 Overheat 6 WaterLeak 7 Service 8 Foaming 9 TankBlocked 10 RefillDelay RO Normal 15017 415018 Boiler Idle Tank Rinse On Unsigned Scale 1 0 Off 1 On W Off 15018 415019 Boiler Idle Tank Rinse Off Unsigned Scale 1 0 Off 1 On W Off 15019 415020 Water Probe Auto Calib Un...

Страница 15: ...Notes ...

Страница 16: ...au blvd Montreal Qc H4N 1R6 Canada www neptronic com Toll free in North America 1 800 361 2308 Tel 514 333 1433 Fax 514 333 3163 Customer service fax 514 333 1091 Monday to Friday 8 00am to 5 00pm Eastern time ...

Отзывы: