SKS4 Steam to Steam Humidifier
Modbus Communication Module User Guide
Page | 13
Protocol
Base
Holding
Register
Description
Data Type
Units, Limits, State Texts
Writable
Default
Value
15013
4
15014
Boiler Request
Unsigned
Scale 1
0 = None
1 = Reset Alarms
2 = Drain
3 = Reset Counters
4 = Filling
5 = WaterCalib
W
None
15014
4
15015
Boiler State
Unsigned
Scale 1
0 = Off
1 = Idle
2 = LineRinse
3 = TankRinse
4 = Filling
5 = Draining
6 = Heating
7 = Boiling
8 = Alarm
RO
Off
15015
4
15016
Boiler Fill Mode
Unsigned
Scale 1
0 = OneShot
1 = Pulsed
W
Pulsed
15016
4
15017
Boiler Alarm
Unsigned
Scale 1
0 = Normal
1 = FailedPump
2 = FillTimeout
3 = BlockedPiping
4 = HeatTimeout
5 = Overheat
6 = WaterLeak
7 = Service
8 = Foaming
9 = TankBlocked
10 = RefillDelay
RO
Normal
15017
4
15018
Boiler Idle Tank Rinse On
Unsigned
Scale 1
0 = Off
1 = On
W
Off
15018
4
15019
Boiler Idle Tank Rinse Off
Unsigned
Scale 1
0 = Off
1 = On
W
Off
15019
4
15020
Water Probe Auto Calib
Unsigned
Scale 1
0 = None
1 = Once
2 = Always
W
Always
15020
4
15021
Boiler Startup Tank Rinse
Unsigned
Scale 1
0 = Off
1 = On
W
Off
15021
4
15022
Water Level Probe Warning
Unsigned
Scale 1
0 = Ok
1 = Calib
2 = Replace
RO
OK
15022
4
15023
Water Level Probe Failure
Unsigned
Scale 1
0 = None
1 = Capacitive
2 = Resistive
3 = Both
RO
None