Networkable VAV Controller 

Specification and Installation Instructions 

 

EVCB14NIT4X-TRL24-V411-170525-ESA.docx

 

EVCB14NIT4X 

Page | 1 

Models 

EVCB14NIT4X 

(4 TRIACS / independent / external motor) 

 

 

 

 

 

For use with external floating or modulating actuators

 

 
TRL24

 

 

 

(Thermostat 2x4) 

TRLH24   

 

(Thermostat 2x4 with Humidity) 

TRLG24

   

 

(Thermostat 2x4 with CO2) 

TRLGH24

 

 

(Thermostat 2x4 with CO2 and Humidity) 

 

Description 

The EVCB Series is a combination controller and thermostat with 
support for networked communications via the BACnet MS/TP or 
Modbus protocol. The Networkable VAV Controller is designed for 
simple and accurate control of any variable air volume box in a 
number of zone control configurations. Its field configurable 
algorithms enable versatile implementation of required control 
sequences.   

   

 

EVCB14NIT4X / TRL24 Series 

 

Features 

 

Field configured VAV algorithms, inputs and outputs 

 

Control external actuators using analog (0-10Vdc, adjustable) 
or floating signals with feedback 

 

On board differential pressure sensor 

 

Select direction on analog outputs 

 

Simple air balancing and commissioning via thermostat 

 

Configurable PI (Proportional-Integral) function 

 

Independent, configurable proportional control band and dead 
band per ramp 

 

Activate output with CO

2

 sensor from TRL or external input 

 

Sele

ctable internal or external temperature sensor (10KΩ) 

 

Changeover by contact or external temperature sensor 

 

Internal and external temperature sensor calibration 

 

Freeze protection 

 

Removable, raising clamp, non-strip terminals 

Operational Features 

 

Backlit LCD with simple icon and text driven menus 

 

Select thermostat’s default display 

 

Network service port via on-board mini USB connector 

 

Manual night set back or no occupancy override 

 

Multi level lockable access menu and setpoint 

 

Selectable Fahrenheit or Celsius scale  

 

3-wire connection to controller and 4 push buttons 

Network Communication 

 

BACnet MS/TP or Modbus communication port  

 

Select MAC address via DIP switch or via network 

 

Automatic baud rate detection 

BACnet MS/TP® 

 

Automatic device instance configuration 

 

Copy & broadcast configuration via thermostat menu or 
via BACnet to other controllers 

 

BACnet scheduler 

 

Firmware upgradeable via BACnet 

 

Support COV (change of value) 

Modbus 

 

Modbus @ 9600, 19200, 38400 or 57600 bps 

 

RTU Slave, 8 bits (configurable parity and stop bits) 

 

Connects to any Modbus master 

Controller Specifications 

Description 

EVCB14NIT4X 

Power consumption 

10 VA max 

Power supply 

22 to 26 Vac 50/60 Hz 

Inputs 

2 Universal inputs (

Thermistor 10KΩ Type 3, digital 24Vac/dry contact, or 0-10Vdc) 

2 digital inputs 

On-board differential pressure sensor 

0-

1.0” WC  

Outputs 

2 analog outputs (0-10 Vdc or 2-10Vdc; selectable) 

4 TRIAC outputs 24 Vac, 500mA max thermal fuse in series with each TRIAC output (on/off, pulse, or 2 
floating outputs) 

Real Time Clock 

Real-time clock (RTC) with super capacitor backup (approximately 3 days) 

BACnet 

BACnet

®

 MS/TP @ 9600, 19200, 38400 or 76800 bps (BAS-C) 

Modbus 

Modbus RTU slave @ 9600, 19200, 38400 or 57600. Selectable parity and stop bit configuration: 
No parity, 2 stop bit | Even parity, 1 stop bit | Odd parity, 1 stop bit  

Communication connection 

24 AWG twisted-shield cable (Belden 9841 or equivalent). Max 0ft (15m) between controller and thermostat 

Electrical connection 

0.8 mm

[18 AWG] minimum 

Operating temperature 

0ºC to 50ºC [32ºF to 122ºF] 

Storage temperature 

-30ºC to 50ºC [-22ºF to 122ºF] 

Relative Humidity 

5 to 95% non condensing 

Weight 

1.8 kg. [4 lb] 

Содержание EVCB14NIT4X/TRL24 Series

Страница 1: ...play Network service port via on board mini USB connector Manual night set back or no occupancy override Multi level lockable access menu and setpoint Selectable Fahrenheit or Celsius scale 3 wire con...

Страница 2: ...Nm 4 Slide the mounting bracket under the actuator Ensure free movement of the slot at the base of the actuator Place the bracket pin at mid distance of the slot 5 Affix the bracket to the ductwork w...

Страница 3: ...by 90 Display resolution 1 ppm Electrical connection 3 wires to VAV controller and 2 wires to BACnet Modbus network 0 8 mm2 18 AWG minimum Network service port Mini USB connector Power supply 24Vac o...

Страница 4: ...the screw BACnet or Modbus Address DIP Switch DS1 MAC address for communication are selectable by DIP switch using binary logic If you do not change device instance in program mode it will be automati...

Страница 5: ...g DI2 Override normally cool heat DI1 OCC open close NSB open close 3 2 1 COM 24Vac input TO2 TO1 TO1 4 TO2 7 6 5 COM 24Vac input TO3 TO4 TO3 8 TO4 4 TRIAC outputs config Cool 1 or 2 heat 1 or 2 CO2 O...

Страница 6: ...tion Motor Minimum Pos Cooling 10 0 100 Motor Minimum Pos Heating 10 0 100 ClHt cool heat Control Apps Cl cool only scroll menu items APPS APPS YES confirm Confirm Control apps NO cancel The APPS repr...

Страница 7: ...ange 2000 ppm CO2 Setpnt 800 ppm Go to AI2 Go to AI2 Go to AI2 ASt Air supply temp sensor CO2 carbon dioxide StFl setpnt airflow 0 10Vdc AI2 Signal Type EtS external temp sensor OFF disabled NoHt norm...

Страница 8: ...Networkable VAV Controller Specification and Installation Instructions www neptronic com EVCB14NIT4X Page 8 TRIAC Outputs Menu 3 of 7 TO1 and TO2...

Страница 9: ...DIR direct REV reverse Go to AO1 MSV 30 MSV 32 AV 81 AV 76 AV 83 AV 82 AV 84 BV 31 BV 34 BV 35 If CO2 was selected Go to TO4 Close Percent ANLg analog 0 10Vdc CH1 cool heat 1 CO2 carbon dioxide Hr2 he...

Страница 10: ...R direct REV reverse CO2 carbon dioxide Hr2 heating ramp 2 Hr1 heating ramp 1 Cr2 cooling ramp 2 Cr1 cooling ramp 1 AO2 Ramp OFF select set value AO2 Minimum Voltage 0 0 Vdc Go to tmp AO2 Maximum Volt...

Страница 11: ...Networkable VAV Controller Specification and Installation Instructions www neptronic com EVCB14NIT4X Page 11 Settings Menu 6 of 7 Temp Motor and Settings...

Страница 12: ...nth 1 1 12 Day 1 1 31 Go to OPt scroll menu items 1001 AV 166 AV 165 1000 BV 90 AV 167 Local Time Local Date Local Time Local Date Local Date Refer to Copy Config Annnex for a complete list of message...

Страница 13: ...shows the temperature read by the external temperature sensor Adjust the offset by comparing it with a known value e g thermometer If the sensor is not connected or short circuited then the unit disp...

Страница 14: ...s 1 10 100 Maximum Cooling Airflow 1000 Min cool airflow to Kfactor Airflow Setting COOl HEAt Minimum Cooling Airflow 200 0 to max cool airflow Maximum Heating Airflow 1000 Min heat airflow to Kfactor...

Страница 15: ...ustment has been locked Setpnt Locked the lock symbol appears Humidity If enabled in the Options menu see Settings Menu 7 of 7 Ramps Network Time and Options on page 12 the thermostat displays the tem...

Страница 16: ...ers NSB or No Occupancy Mode the symbol appears and uses the NSB or OCC heating and cooling setpoints If not locked you can override the night set back or no occupancy mode for a predetermined period...

Страница 17: ...ype On Off On Off On Off On Off On Off On Off On Off TO3 Close Pos 40 40 40 40 40 40 40 TO3 Open Pos 0 0 0 0 0 0 0 TO4 Ramp HR2 HR2 HR2 HR1 OFF HR1 HR1 TO4 Signal Type Pulse On Off Pulse On Off On Off...

Страница 18: ...Notes...

Страница 19: ...Notes...

Страница 20: ...need to find the nearest Neptronic authorized distributor please consult www neptronic com 400 Lebeau blvd Montreal Qc H4N 1R6 Canada www neptronic com Toll free in North America 1 800 361 2308 Tel 51...

Отзывы: