Networkable VAV Controller 

Specification and Installation Instructions 

 

www.neptronic.com 

 

Page | 4

 

Mechanical Installation 

 

1.  Manually close the damper blades and position the actuator 

to 0º or 90º. 

2.  Slide the actuator onto the shaft.  
3. 

Tighten the nuts on the “U” bolt to the shaft with an 8mm 
wrench to a torque of 60 in-lb [6.7 Nm]. 

4.  Slide the mounting bracket under the actuator. Ensure free 

movement of the slot at the base of the actuator. Place the 
bracket pin at mid distance of the slot. 

5.  Affix the bracket to the ductwork with #8 self-tapping screws. 

 

Do not press the clutch when the actuator is powered. 

EVC with a built-in 70 in. lb. Actuator 

 

1.  Manually close the damper blades and position the actuator 

to 0º or 90º. 

2.  Slide the actuator onto the shaft.  
3. 

Tighten the nuts on the “U” bolt to the shaft with an 8mm 
wrench to a torque of 150 in.lb. [17 Nm]. 

4.  Slide the mounting bracket under the actuator. Ensure free 

movement of the slot at the base of the actuator. Place the 
bracket pin at mid distance of the slot. 

5.  Affix the bracket to the ductwork with #8 self-tapping screws. 
6.  Connect the cable from the EVC to the terminal in the 

actuator as shown. 

 

Do not press the clutch when the actuator is powered. 

EVC with a separate 180 in. lb. Actuator 

 

Terminals on the Actuator 

 

Signal cable from EVC controller (models EVCB14NIT4X 
and EVCB14NDT4X) 

Use to connect the external motor on EVCB14NIT4X and 
EVCB14NDT4X. 

 

 
 

 

CLUTCH

MOUNTING
BRACKET

1

2

3

4

5

COMMON (-) (black)

SUPPLY (+) (red)

FEEDBACK (green)

CONTROL (white)

Green:  Feedback
White:  Control
Red: 

24Vac

Black: 

Common

Содержание EVCB Series

Страница 1: ...CB14NDT4X Control external actuators using analog 0 10Vdc adjustable or floating signals with feedback models EVCB14NIT4X and EVCB14NDT4X On board differential pressure sensor select models Simple air...

Страница 2: ...perature 0 C to 50 C 32 F to 122 F Storage temperature 30 C to 50 C 22 F to 122 F Relative Humidity 5 to 95 non condensing Weight 1 26 kg 2 8 lb The actuator performs an auto stroke on power up When c...

Страница 3: ...an setting Alarm status Heating ON A Automatic Menu set up Lock Energy saving mode Minimum Maximum or C Celsius scale F Fahrenheit scale Dimensions EVC with a built in 70 in lb Actuator A 1 50 39mm B...

Страница 4: ...r blades and position the actuator to 0 or 90 2 Slide the actuator onto the shaft 3 Tighten the nuts on the U bolt to the shaft with an 8mm wrench to a torque of 150 in lb 17 Nm 4 Slide the mounting b...

Страница 5: ...rew BACnet or Modbus Address DIP Switch DS1 MAC address for communication are selectable by DIP switch using binary logic If you do not change device instance in program mode it will be automatically...

Страница 6: ...2 1 AO2 AO1 COM 2 analog outputs config Cool ramp 1 or 2 heat ramp 1 or 2 CO2 setpoint airflow 3 2 1 DI2 DI1 COM 2 digital inputs config DI2 Override normally cool heat DI1 OCC open close NSB open cl...

Страница 7: ...d PCH Pres mode auto change OFF disabled PoS C Motor mIn pos cooling 10 0 100 10 0 100 CH cool heat APP Control apps CL cool only scroll menu items YES confirm APP Confirm control apps NO cancel The A...

Страница 8: ...uT MM Go to OuT MM dI2 Main Menu Sub Menu Configuration rNP MM Ramps NEt MM Network BtN MM Buttons HrS MM Time Date SEt MM Settings Mt MM Motor tNP MM Temperature OUT MM Outputs InP MM Inputs scroll m...

Страница 9: ...changeover ramp StF setpnt airflow 0 10Vdc ANA analog 0 10Vdc Aut fan follows demand On fan continuously on CH1 cool heat 1 tO2 Go to tO3 Go to t2C TO2 Close Percent Go to to2 TO2 DIR REV to2 TO2 dire...

Страница 10: ...set value 0 0 Vdc 0 10 Vdc Go to tNP MM 10 0 Vdc 0 10 Vdc Go to tNP MM AFL airflow reading Main Menu Sub Menu Configuration AO1 AO2 tO4 tO3 tO2 Out Output config tO1 scroll menu items AFL airflow read...

Страница 11: ...mp 1 Mr Motor signal ramp OFF select set value Mr Motor direction dIr direct rEv reverse Go to SEt MM Air Airflow integral time 0 0 60 min Pb2 Heat prop band2 2 0 C 4 0 F 0 5 5 C 1 9 F db2 Heat dead b...

Страница 12: ...1 127 OP1 odd parity 1 stop bit CFG Modbus comport config nP2 no parity 2 stop bits EP1 even parity 1 stop bit MA Modbus address 1 1 246 Modifiable only if all DS2 DIP switches are set to OFF Go to Hr...

Страница 13: ...rature read by the external temperature sensor Adjust the offset by comparing it with a known value e g thermometer If the sensor is not connected or short circuited then the unit displays the sensor...

Страница 14: ...99 5 100 1 0 99 9 When balancing use only two of the four modes available either Close Motor and Open Motor or Minimum Airflow and Maximum Airflow more precise You must press the button to save any ch...

Страница 15: ...e Control Mode appears for 5 seconds Press the button to scroll through the following control modes These options can vary depending on the options selected in Temp Control Mode and Enable OnOff Contr...

Страница 16: ...pe On Off On Off On Off On Off On Off On Off On Off TO3 Close Pos 40 40 40 40 40 40 40 TO3 Open Pos 0 0 0 0 0 0 0 TO4 Ramp HR2 HR2 HR2 HR1 OFF HR1 HR1 TO4 Signal Type Pulse On Off Pulse On Off On Off...

Страница 17: ...Notes...

Страница 18: ......

Страница 19: ......

Страница 20: ...need to find the nearest Neptronic authorized distributor please consult www neptronic com 400 Lebeau blvd Montreal Qc H4N 1R6 Canada www neptronic com Toll free in North America 1 800 361 2308 Tel 51...

Отзывы: