Networkable VAV Controller 

Specification and Installation Instructions 

 

www.neptronic.com 

 

Page | 15

 

Page | 15

 

Temperature  

The thermostat displays the temperature reading for 8 seconds. If the sensor is disconnected or short circuited, then the unit 

displays the sensor's limits.

 

To toggle the temperature scale between ºC and ºF, press the 

 button.  

Temperature Setpoint  

To display the setpoint, press the 

 or 

 key twice. The set point appears for 5 seconds. To adjust the setpoint, press the arrow 

keys while the temperature is displayed. If the setpoint adjustment has been locked, the lock   symbol appears. 

Air Flow and Air Supply Temperature

  

Press and hold the 

 button for 5 seconds and use the arrow keys to view the: 

Flo

 

(airflow) 

FOS" 

(airflow setpoint) 

dPR" 

(actual damper position percent) 

aST 

(air supply temperature)

.

  

 

After 5 seconds without any action, the thermostat returns to operation mode. The air supply temperature appears only if analog 
input AI1 or AI2 are configured with the AST option. The airflow and airflow setpoint only appear when in pressure independent 
mode. The actual damper position percent only appear with the following standard models: EVCB14NIT0S, EVCB14NIT2S, 
EVCB14NIT4S, EVCB14NDT4S, EVCB14NIT0SF, and EVCB14NIT4SF 

Control Mode 

To access the Control Mode, press the 

 button. The Control Mode appears for 5 seconds. Press the 

 button to scroll 

through the following control modes. These options can vary depending on the options selected in "Temp Control Mode" and 
"Enable OnOff Control Mode". 
 

 

Auto (Automatic Cooling or Heating)  

 

Cooling only (on, with cooling symbol) 

 

Heating only (on, with heating symbol) 

 

OFF (if it is not disabled in Programming Mode) 

Night Set Back (NSB) or Occupancy Mode 

This function is only available if you set DI1 to 

nSb

 (Night set back contact) or 

Occ

 (occupancy mode). If the DI1 contact is 

triggered, the thermostat enters NSB or No Occupancy Mode (the   symbol appears) and uses the NSB or OCC heating and 
cooling setpoints.  
 
If not locked, you can override the night set back or no occupancy mode for a predetermined period by pressing any of the 4 
buttons. During the override period the 

 

symbol will flash. If the 

 symbol 

does not flash, the override period is finished or the night 

set back or no occupancy override has been locked in programming mode. 

Set Time and Date 

1.  Ensure that JP1 on the thermostat is set to run. 

2.  Press and hold the 

 button for 5 seconds 

3.  Use the arrow keys to set the desired value. Press the 

 button to save and got to the next step. Press the 

 button to 

go to the previous step without saving. 

= select / set value

Hours

12 

(1-24 or 1-12 am/pm)

Minutes

00 

(00-59)

Year

15 

(15-99)

Set Time Display format 

24 

(24-hour format)

12

 (AM/PM format)

Month

(1-12)

Day

(1-31)

Go to “PrSs"

Local Time

Local Date

Local Time

Local Date

Local Date

 

 

 

Содержание EVCB Series

Страница 1: ...CB14NDT4X Control external actuators using analog 0 10Vdc adjustable or floating signals with feedback models EVCB14NIT4X and EVCB14NDT4X On board differential pressure sensor select models Simple air...

Страница 2: ...perature 0 C to 50 C 32 F to 122 F Storage temperature 30 C to 50 C 22 F to 122 F Relative Humidity 5 to 95 non condensing Weight 1 26 kg 2 8 lb The actuator performs an auto stroke on power up When c...

Страница 3: ...an setting Alarm status Heating ON A Automatic Menu set up Lock Energy saving mode Minimum Maximum or C Celsius scale F Fahrenheit scale Dimensions EVC with a built in 70 in lb Actuator A 1 50 39mm B...

Страница 4: ...r blades and position the actuator to 0 or 90 2 Slide the actuator onto the shaft 3 Tighten the nuts on the U bolt to the shaft with an 8mm wrench to a torque of 150 in lb 17 Nm 4 Slide the mounting b...

Страница 5: ...rew BACnet or Modbus Address DIP Switch DS1 MAC address for communication are selectable by DIP switch using binary logic If you do not change device instance in program mode it will be automatically...

Страница 6: ...2 1 AO2 AO1 COM 2 analog outputs config Cool ramp 1 or 2 heat ramp 1 or 2 CO2 setpoint airflow 3 2 1 DI2 DI1 COM 2 digital inputs config DI2 Override normally cool heat DI1 OCC open close NSB open cl...

Страница 7: ...d PCH Pres mode auto change OFF disabled PoS C Motor mIn pos cooling 10 0 100 10 0 100 CH cool heat APP Control apps CL cool only scroll menu items YES confirm APP Confirm control apps NO cancel The A...

Страница 8: ...uT MM Go to OuT MM dI2 Main Menu Sub Menu Configuration rNP MM Ramps NEt MM Network BtN MM Buttons HrS MM Time Date SEt MM Settings Mt MM Motor tNP MM Temperature OUT MM Outputs InP MM Inputs scroll m...

Страница 9: ...changeover ramp StF setpnt airflow 0 10Vdc ANA analog 0 10Vdc Aut fan follows demand On fan continuously on CH1 cool heat 1 tO2 Go to tO3 Go to t2C TO2 Close Percent Go to to2 TO2 DIR REV to2 TO2 dire...

Страница 10: ...set value 0 0 Vdc 0 10 Vdc Go to tNP MM 10 0 Vdc 0 10 Vdc Go to tNP MM AFL airflow reading Main Menu Sub Menu Configuration AO1 AO2 tO4 tO3 tO2 Out Output config tO1 scroll menu items AFL airflow read...

Страница 11: ...mp 1 Mr Motor signal ramp OFF select set value Mr Motor direction dIr direct rEv reverse Go to SEt MM Air Airflow integral time 0 0 60 min Pb2 Heat prop band2 2 0 C 4 0 F 0 5 5 C 1 9 F db2 Heat dead b...

Страница 12: ...1 127 OP1 odd parity 1 stop bit CFG Modbus comport config nP2 no parity 2 stop bits EP1 even parity 1 stop bit MA Modbus address 1 1 246 Modifiable only if all DS2 DIP switches are set to OFF Go to Hr...

Страница 13: ...rature read by the external temperature sensor Adjust the offset by comparing it with a known value e g thermometer If the sensor is not connected or short circuited then the unit displays the sensor...

Страница 14: ...99 5 100 1 0 99 9 When balancing use only two of the four modes available either Close Motor and Open Motor or Minimum Airflow and Maximum Airflow more precise You must press the button to save any ch...

Страница 15: ...e Control Mode appears for 5 seconds Press the button to scroll through the following control modes These options can vary depending on the options selected in Temp Control Mode and Enable OnOff Contr...

Страница 16: ...pe On Off On Off On Off On Off On Off On Off On Off TO3 Close Pos 40 40 40 40 40 40 40 TO3 Open Pos 0 0 0 0 0 0 0 TO4 Ramp HR2 HR2 HR2 HR1 OFF HR1 HR1 TO4 Signal Type Pulse On Off Pulse On Off On Off...

Страница 17: ...Notes...

Страница 18: ......

Страница 19: ......

Страница 20: ...need to find the nearest Neptronic authorized distributor please consult www neptronic com 400 Lebeau blvd Montreal Qc H4N 1R6 Canada www neptronic com Toll free in North America 1 800 361 2308 Tel 51...

Отзывы: