background image

 

Networkable VAV Controller 

Specification and Installation Instructions 

 

EVCB14N-TRL54-V505-191004-ESA

 

 

Page | 1 

Models 

EVCB14NIT0S 

 

(0 TRIACS / pressure independent) 

EVCB14NIT2S   

(2 TRIACS / pressure independent) 

EVCB14NIT4S   

(4 TRIACS / pressure independent) 

EVCB14NIT4X

  

(4 TRIACS / independent / external motor) 

EVCB14NDT4X

 

(4 TRIACS / dependent / external motor) 

EVCB14NDT4S

 

(4 TRIACS / pressure dependent) 

EVCB14NIT0SF

 

(0 TRIACS / independent / feedback) 

EVCB14NIT4SF

 

(4 TRIACS / independent / feedback)

 

 

For use with either floating or modulating actuators 

TRL54 

 

      

(Thermostat 3x3) 

Description 

The EVCB Series is a combination controller and thermostat with 
support for networked communications via the BACnet MS/TP or 
Modbus protocol. The Networkable VAV Controller is designed for 
simple and accurate control of any variable air volume box in a 
number of zone control configurations. Its field configurable 
algorithms enable versatile implementation of required control 
sequences.   

 

 

EVCB Series / TRL54 

 

Typical Application 

 

 

Applications 

 

Single duct, cooling only 

 

Single duct cooling and/or heating 

 

Up to 4 stage reheat and/or cool 

 

Up to 4 On/Off heat and/or cool 

 

Up to 4 time proportioned (TPM) heat or reheat 

 

Up to 2 analog (0-10Vdc) reheat and/or cool 

 

Up to 2 floating heat and/or cool 

 

Pressure dependent or pressure independent 

 

With or without auto changeover 

 

Supply/exhaust (requires an additional EVC) 

Features 

 

Field configured VAV algorithms, inputs and outputs 

 

Built-in actuator, 70 lb-in. (select models, not available on 
EVCB14NIT4X and EVCB14NDT4X) 

 

Control external actuators using analog (0-10Vdc, adjustable) 
or floating signals with feedback (models EVCB14NIT4X and 
EVCB14NDT4X) 

 

On board differential pressure sensor (select models) 

 

Simple air balancing and commissioning via thermostat 

 

Automatically sets operation mode to pressure dependent or 
independent based on the presence of air flow 

 

Select direction on analog outputs 

 

Configurable PI (Proportional-Integral) function 

 

Independent, configurable proportional control band and dead 
band per ramp 

 

Selectable internal or external temperature sensor (10KΩ) 

 

External CO2 sensor input with integrated logic 

 

Changeover by contact or external temperature sensor 

 

Internal and external temperature sensor calibration 

 

Optional potentiometer feedback for increased precision of 
actuator position 

 

Freeze protection 

 

Removable, raising clamp, non-strip terminals 

Operational Features 

 

Backlit LCD with simple icon and text driven menus 

 

Select thermostat’s default display 

 

Network service port via on-board mini USB connector 

 

Manual night set back or no occupancy override 

 

Multi level lockable access menu and setpoint 

 

Selectable Fahrenheit or Celsius scale  

 

3-wire connection to controller and 4 push buttons 

Network Communication 

 

BACnet MS/TP or Modbus communication port  

 

Select MAC address via DIP switch or via network 

 

Automatic baud rate detection 

BACnet MS/TP® 

 

Automatic device instance configuration 

 

Copy & broadcast configuration via thermostat menu 
or via BACnet to other controllers 

 

BACnet scheduler 

 

Firmware upgradeable via BACnet 

 

Support for COV (change of value) 

Modbus 

 

Modbus @ 9600, 19200, 38400 or 57600 bps 

 

RTU Slave, 8 bits (configurable parity and stop bits) 

 

Connects to any Modbus master 

Содержание EVCB Series

Страница 1: ...CB14NDT4X Control external actuators using analog 0 10Vdc adjustable or floating signals with feedback models EVCB14NIT4X and EVCB14NDT4X On board differential pressure sensor select models Simple air...

Страница 2: ...perature 0 C to 50 C 32 F to 122 F Storage temperature 30 C to 50 C 22 F to 122 F Relative Humidity 5 to 95 non condensing Weight 1 26 kg 2 8 lb The actuator performs an auto stroke on power up When c...

Страница 3: ...an setting Alarm status Heating ON A Automatic Menu set up Lock Energy saving mode Minimum Maximum or C Celsius scale F Fahrenheit scale Dimensions EVC with a built in 70 in lb Actuator A 1 50 39mm B...

Страница 4: ...r blades and position the actuator to 0 or 90 2 Slide the actuator onto the shaft 3 Tighten the nuts on the U bolt to the shaft with an 8mm wrench to a torque of 150 in lb 17 Nm 4 Slide the mounting b...

Страница 5: ...rew BACnet or Modbus Address DIP Switch DS1 MAC address for communication are selectable by DIP switch using binary logic If you do not change device instance in program mode it will be automatically...

Страница 6: ...2 1 AO2 AO1 COM 2 analog outputs config Cool ramp 1 or 2 heat ramp 1 or 2 CO2 setpoint airflow 3 2 1 DI2 DI1 COM 2 digital inputs config DI2 Override normally cool heat DI1 OCC open close NSB open cl...

Страница 7: ...d PCH Pres mode auto change OFF disabled PoS C Motor mIn pos cooling 10 0 100 10 0 100 CH cool heat APP Control apps CL cool only scroll menu items YES confirm APP Confirm control apps NO cancel The A...

Страница 8: ...uT MM Go to OuT MM dI2 Main Menu Sub Menu Configuration rNP MM Ramps NEt MM Network BtN MM Buttons HrS MM Time Date SEt MM Settings Mt MM Motor tNP MM Temperature OUT MM Outputs InP MM Inputs scroll m...

Страница 9: ...changeover ramp StF setpnt airflow 0 10Vdc ANA analog 0 10Vdc Aut fan follows demand On fan continuously on CH1 cool heat 1 tO2 Go to tO3 Go to t2C TO2 Close Percent Go to to2 TO2 DIR REV to2 TO2 dire...

Страница 10: ...set value 0 0 Vdc 0 10 Vdc Go to tNP MM 10 0 Vdc 0 10 Vdc Go to tNP MM AFL airflow reading Main Menu Sub Menu Configuration AO1 AO2 tO4 tO3 tO2 Out Output config tO1 scroll menu items AFL airflow read...

Страница 11: ...mp 1 Mr Motor signal ramp OFF select set value Mr Motor direction dIr direct rEv reverse Go to SEt MM Air Airflow integral time 0 0 60 min Pb2 Heat prop band2 2 0 C 4 0 F 0 5 5 C 1 9 F db2 Heat dead b...

Страница 12: ...1 127 OP1 odd parity 1 stop bit CFG Modbus comport config nP2 no parity 2 stop bits EP1 even parity 1 stop bit MA Modbus address 1 1 246 Modifiable only if all DS2 DIP switches are set to OFF Go to Hr...

Страница 13: ...rature read by the external temperature sensor Adjust the offset by comparing it with a known value e g thermometer If the sensor is not connected or short circuited then the unit displays the sensor...

Страница 14: ...99 5 100 1 0 99 9 When balancing use only two of the four modes available either Close Motor and Open Motor or Minimum Airflow and Maximum Airflow more precise You must press the button to save any ch...

Страница 15: ...e Control Mode appears for 5 seconds Press the button to scroll through the following control modes These options can vary depending on the options selected in Temp Control Mode and Enable OnOff Contr...

Страница 16: ...pe On Off On Off On Off On Off On Off On Off On Off TO3 Close Pos 40 40 40 40 40 40 40 TO3 Open Pos 0 0 0 0 0 0 0 TO4 Ramp HR2 HR2 HR2 HR1 OFF HR1 HR1 TO4 Signal Type Pulse On Off Pulse On Off On Off...

Страница 17: ...Notes...

Страница 18: ......

Страница 19: ......

Страница 20: ...need to find the nearest Neptronic authorized distributor please consult www neptronic com 400 Lebeau blvd Montreal Qc H4N 1R6 Canada www neptronic com Toll free in North America 1 800 361 2308 Tel 51...

Отзывы: