BT100/105/120/200/205/220
Specification & Installation instruction
2
Mechanical installation
CLUTCH
MOUNTING
BRACKET
1.
Manually close the damper blades and positioned the
actuator at 0º or 90º.
2.
Slide the actuator onto the shaft.
3.
Tighten the nuts on the “U” bolt to the shaft with a 8mm
wrench to a torque of 60 in.lb. [6,7 Nm].
4.
Slide the mounting bracket under the actuator. Ensure free
movement of the slot at the base of the actuator. The
bracket pin must be placed in the mid distance of the slot.
5.
Fix the bracket to the ductwork with #8 self-tapping screws.
Wiring Diagrams
Caution: Risk of electric shock. Remove power prior to connect.
3 wire / 2 position
(ON-OFF)
LINE (+)
NEUTRAL (-)
DRIVE CW
1
2
3
3 wire / 3 point floating
DRIVE CCW
LINE (+)
NEUTRAL (-)
DRIVE CW
1
2
3
PC Board
Potentiometer
Only on model 105 & 205
1 2 3
Terminal
JP1
Rotation
direction
6 7 8
JP2
Feedback or switches terminal
Only on model 105, 120, 205 & 220
BBTHV1X00A
Rotation direction
CW
CCW
(0 to 90º)
(90 to 0º)
Stroke adjustment
To adjust the stroke, move the adjustment screws at the desired position.